C4 SERIES OUTPUT MODULES
• Plug into mounting boards for C4 Series modules
• AC Outputs (Black Case)
• DC Outputs (Red Case)
• 4kV Optical isolation
• Replaceable 2 AG Type Fuse
• Industry standard packaging
• Built-in LED Status Indicator
SPECIFICATIONS (1)
Input
Part Number
Nominal Voltage VDC
Minimum Voltage VDC
Maximum Voltage VDC
Drop-out Voltage
Maximum Current (2) (3)
Resistance
C4OAC
4-32
4.0
32
1.0
22
Regulated Input
C4OACA
4-32
4.0
32
1.0
22
Regulated Input
C4OACR
4-32
4.0
32
1.0
22
Regulated Input
C4OACAR
4-32
4.0
32
1.0
22
Regulated Input
C4ODC
4-32
4.0
32
1.0
16
Regulated Input
C4ODCA
4-32
4.0
32
1.0
16
Regulated Input
Output
Nominal Line Voltage
Minimum Line Voltage
Maximum Line Voltage
Max Off-State Voltage (4)
Max Off-State Leakage (5)
Static Off-State dv/dt (6)
Maximum Rated On-State Current (7)
Minimum On-State Current
Max Surge Current (8)
On-State Voltage Drop or Resistance
(9)
HP Rating
Maximum Turn-On Time [msec] (10)
Maximum Turn-Off Time [msec]
Input/Output Isolation Voltage (11)
Input/Output Capacitance
Operating Temperature Range
Storage Temperature Range
Line Frequency Range
Weight
120 VAC
12 VAC
140 VAC
600 Vpeak
0.1mArms
200 V/usec
3.0 Arms
50 mArms
100 Apeak
1.6 V
1/4
8.33
8.33
4000
4
-30 to 80°C
-40 to 100°C
47 to 63 Hz
1.1 oz. (31.2g)
240 VAC
12 VAC
280 VAC
600 Vpeak
0.1mArms
200 V/usec
3.0 Arms
50 mArms
100 Apeak
1.6 V
1/4
8.33
8.33
4000
4
-30 to 80°C
-40 to 100°C
47 to 63 Hz
1.1 oz. (31.2g)
120 VAC
12 VAC
140 VAC
600 Vpeak
0.1mArms
200 V/usec
3.0 Arms
50 mArms
100 Apeak
1.6 V
1/4
0.1
8.33
4000
4
-30 to 80°C
-40 to 100°C
47 to 63 Hz
1.1 oz. (31.2g)
240 VAC
12 VAC
280 VAC
600 Vpeak
0.1mArms
200 V/usec
3.0 Arms
50 mArms
100 Apeak
1.6 V
1/4
0.1
8.33
4000
4
-30 to 80°C
-40 to 100°C
47 to 63 Hz
1.1 oz. (31.2g)
5-48 VDC
5.0 VDC
60 VDC
60 VDC
10 uA
n/a
3.0 A
10 mA
5.0 Apeak
1.6 V
n/a
0.05
0.05
4000
4
-30 to 80°C
-40 to 100°C
DC
1.1 oz. (31.2g)
5-150 VDC
3 VDC
250 VDC
250 VDC
10 uA
n/a
1.0 A
10 mA
5.0 Apeak
1.6 V
n/a
0.05
0.05
4000
4
-30 to 80°C
-40 to 100°C
DC
1.1 oz. (31.2g)
General Notes:
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
Specifications apply to an ambient temperature of -30 to 80 °C unless otherwise noted.
At 32 VDC typical.
13 ma at 5 VDC for AC output modules only.
Maximum 1 minute duration.
At maximum rated line voltage, TA=80°C.
Minimum DV/DT per EIA/NARM RS443, method RS397, DV/DT ratings do not apply to DC output models.
Without any external heat sink in still air, TA=45°C, at 40°C derate 40 mA/°C to 80°C.
At 25°C for 1 second maximum duration: 1 AC cycle for AC modules, 1 second for DC modules.
At peak rated current.
Before zero voltage, Vin=4V AC modules only based on 60Hz. Vin=15V for DC modules.
For 1 second maximum duration TA= 25°C.