Generator Control
Advanced
sigmA sERiEs
Generator Control and Protection System
1
Description
The SIGMA Generator Control and Protection System is a range of
integrated modules for protection and control of marine and land
based generators. The modules are marine approved and include all
relevant functions, such as protection of generators, synchronizing
and active/ reactive load sharing and Power Management.
1
IO/P Module S6000
2
Input/ Output and Protection Module
The SIGMA S6000 performs all measurements on the
generator side (voltages, currents, frequency), does the
generator protection, includes a non-essential load trip in
two steps and includes three measurement transducers.
Synchronizing and Load-Sharing Module
This module performs the control functions like synchronizing
and active and reactive load sharing. It performs the
measurements on the busbar side.
2
S/LS Module S6100
Simplified Circuit Diagram
A
S6610
(Power
Manager
Module)
Accessories
S6500
B
S6500
B
(User-Interface
Module)
(User-Interface
Module)
S6500
B
(User-Interface
Module)
A
2
S6100
2
(Synchronizing &
Load-Sharing
Module)
S6100
2
(Synchronizing &
Load-Sharing
Module)
S6100
S6610 Power Manager Module
Controls the number of generators that are
supplying to the bus. It will issue start and
stop signals to the generators depending
on power requirement. There are 10 inputs
for large consumer requests.
Σ
SIGMA
(Synchronizing &
Load-Sharing
Module)
B
Gen.
Volt.
Amp.
kW
kVAr
Misc.
Prot.
Page
PAGE
PM
DOWN
1
S6000
(Input/Output &
Protection
Module)
1
S6000
(Input/Output &
Protection
Module)
1
S6000
C/B CLOSED
PROTECTION TRIP
IN OPERATION
OFF DUTY
ENGINE ERROR
Mode
Enter
Enter
(Input/Output &
Protection
Module)
Yes
No
Reset
Test
Duty
S6500 User Interface Module
This unit is optional, as the S6000/S6100
also can be programmed from a PC.
It is possible to use one or more units
per installation.
PWR1
PWR2
ALARM
GEN
A
GEN
B
GEN
C
Ordering Information
oRdERing
numbER
dEscRiption
S6000.0010
S6000.0020
S6100.0010
AccEssoRiEs
Input/ Output and Protection Module– 5 A C/T
Input/ Output and Protection Module–1 A C/T
Synchronization and Load Sharing Module
REquiREmEnt
S6500.0010
S6610.0010
Optional
Optional
© 2013 Littelfuse Protection Relays & Controls
www.littelfuse.com/s6000
Rev: 4-A-050313
Advanced
Generator Control
SIGMA Technical Data
FEAtuREs
Features & Benefits
s/Ls
pm
ui
sigmA moduLE moduLE moduLE
s6000
s6100
s6610
s6500
FEAtuREs
3-phase true RMS
measurement
Analog outputs for speed
and voltage control
PWM outputs for speed
and voltage control
Pulse outputs for speed
and voltage control
Large consumer request
inputs with load feed back
Type-approved by marine
classification societies
bEnEFits
Reliable measurement, high noise immunity
Fits most electronic governors and ECUs
Compatible with e.g. CAT and Woodward
Compatible with conventional governors,
motorized potentiometers and some ECUs
Optimizes quantity of running generators
and saves fuel
Pre-configured Marine Power
Management System
Reverse power protection
Overcurrent trip
Short-circuit trip
Power trip
Excitation loss relay trip
Over/ Undervoltage trip
Nonessential load trip in 2 steps
RS485/ Modbus RTU (RS485)
Synchronizer
Load sharer
VAR load sharer
Indication of measurements
Programming of the
S6000 and S6100 modules
Load depending start and
stop of generators
Large consumer request
Large consumer inhibit
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Specifications (S6000)
Primary Supply
Backup Supply
Environmental Temp Range
Gen. Phase-Phase Voltage (GPPV)
Gen. Indicated Voltage (GIV)
CT Secondary Current (CTSC)
Gen. Rated Frequency (GRF)
Gen. Maximum Current (GMC)
+24 Vdc (-30%/+30 %) Isolated, 500 mA
+24 Vdc (-30%/+30 %) Isolated, 500 mA
–15°C to +70°C
63.0-690.0 Vac (-2 % /+2 %) 3-phased
63-32 kV AC
1 A or 5 A (consumption 25 mW or
125 mW) 3-phased
40.0-500.0 Hz
0.5-3,000.0 A / 500-30,000 A
AC: 8 A, 250 Vac; DC: 8 A, 35 Vdc
AC: 8 A, 250 Vac; DC: 8 A, 35 Vdc
AC: 8 A, 250 Vac; DC: 8 A, 35 Vdc
AC: 8 A, 250 Vac; DC: 8 A, 35 Vdc
Screw terminals,2-wire with COM
(limp back function)
CANopen derivative
Customized plug, 4-wire (non-isolated)
Configuration, Debugging or
firmware update
ANSI terminal
Screw terminals, 2-wire (isolated)
MODBUS-RTU
EN 50081-2:1993, EN 50263: 1999
EN 60945:1997, IACS E10:1997
Plug-in screw terminals
(spring terminals available as option)
Screw mounting (4 pcs. 4.2 x 12 mm)
1,150 g
H
145 mm (5.7”)
W
190 mm (7.5”)
D
64.5 mm (2.5”)
Wiring Diagram
SHAFT GENERATOR
(GRID)
Frequency Control
Sync On
Next S6100
Protection Functions
C/B Trip Relay
Contact rating:
NE1 Trip Relay
Contact rating:
NE2 Trip Relay
Contact rating:
Alarm Relay
Contact rating:
CAN Bus
Connection:
Protocol:
Connection:
Function:
Protocol:
Connection:
Protocol:
RS232
RS485
EMC
Marine Tests
Connections
Mounting
Weight
Dimensions
Next S6000 / S6100
© 2013 Littelfuse Protection Relays & Controls
www.littelfuse.com/s6100
Rev: 4-A-050313