Solid State Relays
G3NA
CSM_G3NA_DS_E_5_1
Wide Lineup of General-purpose Solid State
Relays with Applicable Loads of 5 to 90 A
• AC Output Relays with 75-A and 90-A output currents have
been added to the G3NA Series.
• All models feature the same compact dimensions to provide a
uniform mounting pitch.
• Built-in varistor effectively absorbs external surges.
(except G3NA-D210B)
• Operation indicator enables monitoring operation.
• Protective cover for greater safety.
• Standard models certified by UL and CSA and -UTU models by
TÜV.
(except G3NA-410B, G3NA-420B, and G3NA-440B)
Refer to
Safety Precautions for All Solid State
Relays.
Model Number Structure
■
Model Number Legend
G3NA-@@@@@-@
1
2 3 4 5 6
7
5. Terminal Type
B:
Screw terminals
6. Zero Cross Function
Blank:
Equipped with zero cross function
(AC-output models only)
7. Certification
Blank:
Standard models (certified by UL and CSA)
UTU:
Certified by UL, CSA, and TÜV
1. Basic Model Name
G3NA:
Solid State Relay
2. Load Power Supply
Blank:
AC output
D:
DC output
3. Rated Load Power Supply Voltage
2:
200 VAC or 200 VDC
4:
400 VAC
4. Rated Load Current
05:
5A
10:
10 A
20:
20 A
40:
40 A
50:
50 A
75:
75 A
90:
90 A
1
G3NA
Ordering Information
■
List of Models
Isolation
Phototriac Coupler
Photocoupler
Phototriac Coupler
Photocoupler
Phototriac Coupler
Photocoupler
Phototriac Coupler
Photocoupler
Phototriac Coupler
Photocoupler
Phototriac Coupler
Photocoupler
---
Yes
Zero cross
function
Yes
Indicator
Yes
(Yellow)
Applicable output load
(See note 1.)
5 A at 24 to 240 VAC
(See note 2.)
10 A at 24 to 240 VAC
(See note 2.)
20 A at 24 to 240 VAC
(See note 2.)
40 A at 24 to 240 VAC
(See note 2.)
75 A at 24 to 240 VAC
(See note 2.)
90 A at 24 to 240 VAC
(See note 2.)
10 A at 5 to 200 VDC
10 A at 200 to 480 VAC
20 A at 200 to 480 VAC
40 A at 200 to 480 VAC
50 A at 200 to 480 VAC
(See note 2.)
75 A at 200 to 480 VAC
(See note 2.)
90 A at 200 to 480 VAC
(See note 2.)
Rated input voltage
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
5 to 24 VDC
100 to 240 VAC
5 to 24 VDC
100 to 240 VAC
Model
G3NA-205B DC5-24
G3NA-205B AC100-120
G3NA-205B AC200-240
G3NA-210B DC5-24
G3NA-210B AC100-120
G3NA-210B AC200-240
G3NA-220B DC5-24
G3NA-220B AC100-120
G3NA-220B AC200-240
G3NA-240B DC5-24
G3NA-240B AC100-120
G3NA-240B AC200-240
G3NA-275B-UTU DC5-24
G3NA-275B-UTU AC100-240
G3NA-290B-UTU DC5-24
G3NA-290B-UTU AC100-240
G3NA-D210B DC5-24
G3NA-D210B AC100-240
G3NA-410B DC5-24
G3NA-410B AC100-240
G3NA-420B DC5-24
G3NA-420B AC100-240
G3NA-440B DC5-24
G3NA-440B AC100-240
G3NA-450B DC5-24
G3NA-475B-UTU DC5-24
G3NA-475B-UTU AC100-240
G3NA-490B-UTU DC5-24
G3NA-490B-UTU AC100-240
*The standard models are certified by UL and CSA. To order a TÜV-certified model, add “-UTU” to the model number.
Note: 1.
The applicable load is the value for when the SSR is used with silicon grease applied to the specified heat sink. The applicable load de-
pends on the ambient temperature. Refer to
Load Current vs. Ambient Temperature
in
Engineering Data
on page 5.
2.
Loss time increases under 75 VAC. (Refer to page 14.) Confirm operation with the actual load.
■
Accessories (Order Separately)
One-touch Mounting Plates
Model
R99-12 FOR G3NA
Mounting Bracket
Model
R99-11
Applicable SSR
G3NA-240B, G3NA-440B
Heat Sinks
Slim Models Enabling DIN-track Mounting
Model
Y92B-N50
Y92B-N100
Y92B-N150
Y92B-P250
Y92B-P250NF
(See note.)
Applicable SSR
G3NA-205B, G3NA-210B, G3NA-D210B,
G3NA-410B, G3NA-210T(L)
G3NA-220B, G3NA-420B, G3NA-220T(L)
G3NA-240B, G3NA-440B
G3NA-450B
G3NA-275B-UTU, G3NA-290B-UTU,
G3NA-475B-UTU, G3NA-490B-UTU
Low-cost Models
Model
Y92B-A100
Y92B-A150N
Y92B-A250
Applicable SSR
G3NA-205B, G3NA-210B, G3NA-D210B,
G3NA-220B, G3NA-410B, G3NA-420B
G3NA-240B, G3NA-440B
G3NA-440B
Note:
The Y92B-P250NF is scheduled for release on May 1, 2004.
2
G3NA
Specifications
■
Ratings
Input (at an Ambient Temperature of 25°C)
Model
G3NA-2@@B
Rated voltage
5 to 24 VDC
100 to 120 VAC
200 to 240 VAC
G3NA-4@@B
G3NA-D210B
5 to 24 VDC
100 to 240 VAC
Operating voltage
4 to 32 VDC
75 to 132 VAC
150 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
4 to 32 VDC
75 to 264 VAC
Impedance
(See note 1.)
Voltage level
Must operate voltage
Must release voltage
1 VDC min.
7 mA max. (See note 2.) 4 VDC max.
72 kΩ±20%
36 kΩ±20% (See note 4.) 75 VAC max. (See note 3.) 20 VAC min. (See note 3.)
150 VAC max. (See note 3.) 40 VAC min. (See note 3.)
(See note 5.)
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
1 VDC min.
20 VAC min.
75 VAC max.
4 VDC max.
75 VAC max.
4 VDC max.
75 VAC max.
5 mA max. (See note 2.) 4 VDC max.
72 kΩ±20%
15 mA max.
72 kΩ±20%
7 mA max.
72 kΩ±20%
G3NA-275B-UTU
5 to 24 VDC
G3NA-290B-UTU
100 to 240 VAC
G3NA-475B-UTU
5 to 24 VDC
G3NA-490B-UTU
100 to 240 VAC
Note: 1.
The input impedance is measured at the maximum value of the rated supply voltage (for example, with the model rated at 100 to 120 VAC,
the input impedance is measured at 120 VAC).
2.
With constant current input circuit system. The impedance for the G3NA-2@@B-UTU is 15 mA max.
3.
Refer to
Temperature Characteristics (for Must Operate Voltage and Must Release Voltage)
in
Engineering Data
on page 6 for further
details.
4.
The G3NA-240B(-UTU) is 72kΩ±20%.
5.
The G3NA-240B(-UTU) is 20 VAC min.
Output
Model
Rated load voltage
Load voltage range
Applicable load
Load current (See note 1.)
With heat sink
(See note 2.)
G3NA-205B
G3NA-210B
G3NA-410B
G3NA-220B
G3NA-420B
G3NA-240B
G3NA-440B
G3NA-450B
G3NA-D210B
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
24 to 240 VAC
200 to 480 VAC
200 to 480 VAC
5 to 200 VDC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
180 to 528 VAC
4 to 220 VDC
19 to 264 VAC
180 to 528 VAC
19 to 264 VAC
180 to 528 VAC
24 to 240 VAC
19 to 264 VAC
0.1 to 5 A (at 40°C)
0.1 to 10 A (at 40°C)
0.2 to 10 A (at 40°C)
0.1 to 20 A (at 40°C)
0.2 to 20 A (at 40°C)
0.1 to 40 A (at 40°C)
0.2 to 40 A (at 40°C)
0.2 to 50 A (at 40°C)
0.1 to 10 A (at 40°C)
1 to 75 A (at 40°C)
1 to 75 A (at 40°C)
1 to 90 A (at 40°C)
1 to 90 A (at 40°C)
Without heat sink
0.1 to 3 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 4 A (at 40°C)
0.2 to 4 A (at 40°C)
0.1 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.2 to 6 A (at 40°C)
0.1 to 4 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
1 to 7 A (at 40°C)
20 A (10 ms)
800 A (60 Hz, 1 cycle)
800 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
1,000 A (60 Hz, 1 cycle)
440 A (60 Hz, 1 cycle)
220 A (60 Hz, 1 cycle)
60 A (60 Hz, 1 cycle)
150 A (60 Hz, 1 cycle)
Inrush current
G3NA-275B-UTU
24 to 240 VAC
G3NA-475B-UTU
200 to 480 VAC
G3NA-290B-UTU
24 to 240 VAC
G3NA-490B-UTU
200 to 480 VAC
Note: 1.
The load current varies depending on the ambient temperature. Refer to
Load Current vs. Ambient Temperature
under
Engineering Data
on page 5.
2.
When an OMRON Heat Sink (refer to
Options)
or a heat sink of the specified size is used.
3
G3NA
■
Characteristics
Item
G3NA-
205B
G3NA-
210B
G3NA-
220B
G3NA-
240B
G3NA-
410B
G3NA-
420B
G3NA-
440B
G3NA-
450B
G3NA-
D210B
1 ms
max. (DC
input)
30 ms
max. (AC
input)
5 ms
max. (DC
input)
30 ms
max. (AC
input)
1.5 V
max.
5 mA
max.
(at 200
VDC)
G3NA-
275B-
UTU
G3NA-
290B-
UTU
G3NA-
475B-
UTU
G3NA-
490B-
UTU
Operate time
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1/2 of load power source cycle + 1 ms
max. (DC input)
3/2 of load power source cycle + 1 ms
max. (AC input)
Release time
1/2 of load power source cycle + 1 ms max. (DC input)
3/2 of load power source cycle + 1 ms max. (AC input)
1/2 of load power source cycle + 1 ms
max. (DC input)
3/2 of load power source cycle + 1 ms
max. (AC input)
Output ON
voltage drop
Leakage
current
1.6 V (RMS) max.
5 mA max. (at 100 VAC)
10 mA max. (at 200 VAC)
1.8 V (RMS) max.
10 mA max. (at 200 VAC)
20 mA max. (at 400 VAC)
1.6 V (RMS) max.
5 mA max. (at
100 VAC)
10 mA max. (at
200 VAC)
1.8 V (RMS) max.
10 mA max. (at
200 VAC)
20 mA max. (at
400 VAC)
Insulation
resistance
Dielectric
strength
Vibration
resistance
Shock
resistance
Ambient
temperature
Ambient
humidity
Weight
100 MΩ min. (at 500 VDC)
2,500 VAC, 50/60 Hz for 1 min
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude)
Destruction: 1,000 m/s
2
Operating:
Storage:
–30°C to 80°C (with no icing or condensation)
–30°C to 100°C (with no icing or condensation)
4,000 VAC, 50/60 Hz for 1 min
Operating: 45% to 85%
Approx. 60 g
Approx. Approx. 80 g
70 g
Approx.
70 g
Approx. 120 g
4
G3NA
Engineering Data
Load Current vs. Ambient Temperature
G3NA-205B
G3NA-210B/410B
20
16
G3NA-220B/420B
Load current (A)
Load current (A)
With
standard heat sink
(Y92B-A100 or
Y92B-N50) or aluminum
plate measuring 75 mm
x 75 mm x t3.2 mm
(W x H x t)
Without
heat sink
10
With
standard heat sink
(Y92B-A100 or
Y92B-N50) or aluminum
8
plate measuring 150 mm
x 150 mm x t3.2 mm
6 (W x H x t)
5
With
iron plate measuring
100 x 100 x t0.8 (W x H x t)
4
Without
heat sink
2
Load current (A)
With
standard heat sink
(Y92B-A100 or
Y92B-N100) or aluminum
plate measuring 200 mm
x 200 mm x t3.2 mm
(W x H x t)
With
iron plate measuring
100 x 100 x t0.8 (W x H x t)
Without
heat sink
0
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
G3NA-240B
50
45
40
With
standard heat
sink (Y92B-A150N or
Y92B-N150)
G3NA-440B
50
45
40
With
Y92B-A250
or heat sink
with
a
radiation efficiency
of 1°C/W.
60
50
G3NA-450B
Load current (A)
Load current (A)
Load current (A)
With
standard heat sink
(Y92B-P250)
40
30
20
10
6
30
30
With
standard heat
sink (Y92B-A150N
or Y92B-N150)
20
With
iron plate measuring
12
100 x 100 x t0.8 (W x H x t)
10
Without
heat sink
6
4
2
0
−30−20
0
20
40
60
20
12
10
Without
heat sink
6
4
2
0
−30−20
0
20
40
With
iron plate measuring
100 x 100 x t0.8 (W x H x t)
Without
heat sink
80
100
60
80
100
0
−30 −20
0
20
40
60
80
100
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
G3NA-275B-UTU
G3NA-475B-UTU
80
75
70
0.6°C/W
with
Heat Sink
G3NA-290B-UTU
G3NA-490B-UTU
100
90
80
0.3°C/W
with
Heat Sink
G3NA-D210B
20
10
Load current (A)
Load current (A)
Load current (A)
60
50
40
30
20
With
iron plate measuring
100 x 100 x t0.8 (W x H x t)
12
10
7
Without
heat sink
4A
20
−30−20
0
20
40
60 70
80
100
Using the Y92B-P250NF
70
60
50
40
35
30
With
20
100 xiron plate measuring t)
100 x t0.8 (W x H x
12
7
4A
Without
heat sink
20
0
20
40
60 70
80
100
−
30
−
20
Using the Y92B-P250NF
6
5
With
iron plate measuring
100 x 100 x t0.8 (W x H x t)
4
Without
heat sink
2
−
30
−
20
With
standard heat sink
(Y92B-A100 or Y92B-N50)
or aluminum plate measuring
150 mm x 150 mm x t3.2 mm
(W x H x t)
0
0
20
40
60
80
100
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
Note:
The ambient operating temperature of the Y92B-P250NF is
−30
to 70°C. Be sure the operating temperature is within this range.
5