Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
106.7K hrs min. MIL-HDBK-217F (25
278*177.8*63.5mm (L*W*H)
3.3Kg; 4pcs/14.2Kg/1.89CUFT
)
OTHERS
NOTE
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
File Name:RSP-2400-SPEC 2010-10-18
2400W Single Output Power Supply
Mechanical Specification
278
236.3
RSP-2400
Case No.982B
27
12.5
series
Unit:mm
40
63.5
38
CN1 CN2
8 64 2
7 53 1
CN3
8 6 4 2 10 8 6 4 2
7 5 31 9 75 31
8-M4(Both Sides) L=5mm
236.3
7.9
27
OUTPUT
4-M4 L=5mm
4
-V
CN1 CN2
CN3
20
+V
LED
SVR
8 642
7 531
8 6 4 2 10 8 6 4 2
7 5 31 97 5 31
Air flow
direction
INPUT
10
177.8
162
+
13
16max.
AC Input Terminal Pin No. Assignment
Pin No.
1
2
3
Assignment
AC/L
AC/N
FG
Control Pin No. Assignment(CN1,CN2) : HRS DF11-8DP-2DS or equivalent
Pin No.
1
2
3
4
Assignment
RCG
RC
PV
PS
Pin No.
5,7
6
8
Terminal
Assignment Mating Housing
-S
CS(Current Share) HRS DF11-8DS HRS DF11-**SC
or equivalent or equivalent
+S
-S : -Remote Sensing
CS: Load Share
+S: +Remote Sensing
RCG: Remote ON/OFF Ground
RC : Remote ON/OFF
PV :Output Voltage External Control
PS : Reference Voltage Terminal
Control Pin No. Assignment(CN3) : HRS DF11-10DP-2DS or equivalent
Pin No.
1
2
3
Assignment
P OK GND
P OK
P OK GND2
Pin No.
4
5
6
Assignment
P OK2
RCG
RC
Pin No.
7
8
9
Assignment
AUXG
AUX
OLP
Pin No.
10
Assignment
OL-SD
Mating Housing
Terminal
HRS DF11-10DS HRS DF11-**SC
or equivalent
or equivalent
P OK GND: Power OK Ground
P OK: Power OK Signal (Relay Contact)
P OK2: Power OK Signal (TTL Signal)
RCG: Remote ON/OFF Ground
RC: Remote ON/OFF
AUXG: Auxiliary Ground
AUX: Auxiliary Output
OLP: OLP mode select
OL-SD: OLP mode select
Block Diagram
I/P
EMI
FILTER
ACTIVE
INRUSH
CURRENT
LIMITING
PFC fosc : 88KHz
PWM fosc : 100KHz
+S
+V
-V
-S
RECTIFIERS
&
PFC
PFC
CONTROL
O.T.P.
POWER
SWITCHING
RECTIFIERS
&
FILTER
O.V.P.
O.L.P.
PWM
CONTROL
LOAD
SHARING
DETECTION
CIRCUIT
REMOTE
CONTROL
FAN
P OK
RC
CS
RECTIFIERS
&
FILTER
AUX POWER
(12V/0.1A)
AUX
POWER
File Name:RSP-2400-SPEC 2010-10-18
TB1
1
2
3
2400W Single Output Power Supply
Derating Curve
RSP-2400
Static Characteristics
Ta=25
series
100
80
100
90
60
LOAD (%)
LOAD (%)
0
10
20
30
40
50
60
70 (HORIZONTAL)
50
40
80
70
60
20
-20
180
185
190
195
200
210
220
230
240
250
264
AMBIENT TEMPERATURE ( )
INPUT VOLTAGE (V) 60Hz
Function Manual
1.Remote ON/OFF
(1)Remote ON/OFF control becomes available by applying voltage in CN1 & CN2 & CN3.
(2)Table 1.1 shows the specification of Remote ON/OFF function.
(3)Fig.1.2 shows the example to connect Remote ON/OFF control function.
Table 1.1 Specification of Remote ON/OFF
Connection Method
Fig. 1.2(A)
Output on
SW Open
SW Logic
Output off
SW Close
Fig. 1.2(B)
SW Open
SW Close
Fig. 1.2(C)
SW Close
SW Open
Fig.1.2 Examples of connecting remote ON/OFF
(A)Using external voltage source
(B)Using internal 12V auxiliary output
AUX
AUX
12V
RC
SW
RCG
12V typ.
1K
12V typ.
1K
RC
RCG
SW
AUXG
AUXG
(C)Using internal 12V auxiliary output
AUX
1K
12V typ.
1K
RC
SW
RCG
AUXG
File Name:RSP-2400-SPEC 2010-10-18
2400W Single Output Power Supply
RSP-2400
series
2.Alarm Signal Output
(1)Alarm signal is sent out through "P OK" & "P OK GND" and P OK2 & P OK GND2 pins.
(2)An external voltage source is required for this function.
(3)Table 2.1 explains the alarm function built-in the power supply.
Function
Description
Output of alarm(P OK, Relay Contact) Output of alarm(P OK2, TTL Signal)
The signal is "Low" when the power supply is above
Low (0.5V max at 500mA)
Low (0.5V max at 10mA)
80% of the rated output voltage-Power OK
P OK
High or open
The signal turns to be "High" when the power supply High or open
is under 80% of the rated output voltage-Power Fail (External applied voltage, 500mA max.) (External applied voltage, 10mA max.)
Table 2.1 Explanation of alarm
P OK
P OK2
R
V
0.1uF
R
V
P OK GND
External voltage and R
(The max. sink is 500mA and 20V)
P OK GND2
External voltage and R
(The max. sink is 10mA and 30V)
Fig. 2.2 Internal circuit of P OK (Relay, total is 10W)
Fig. 2.3 Internal circuit of P OK2 (Open collector method)
3.Output Voltage TRIM
(1)Connecting an external DC source between PV and-S on CN1 or CN2 that is shown in Fig. 3.1.
(2)Adjustment of output voltage is possible between 20~110%(Typ.) of the rated output which is shown in Fig. 3.2. Reducing output current is required when the
output voltage is trimmed up.
Vout
OVP >120%
120
100
100
OUTPUT VOLTAGE (%)
80
60
40
20
OUTPUT CURRENT (%)
V
Non-Linear
80
60
40
20
V
PV
1~6V
-S
Fig. 3.1 Add on 1~6V external voltage
1
2
3
4
5
6
20
40
60
80
100
120
EXTERNAL VOLTAGE (DC)
OUTPUT VOLTAGE (%)
Fig. 3.2 Output voltage trimming
File Name:RSP-2400-SPEC 2010-10-18
2400W Single Output Power Supply
RSP-2400
series
4.Current Sharing
(1)Parallel operation is available by connecting the units shown as below
(+S,-S and CS are connected mutually in parallel):
(2)The voltage difference among each output should be minimized that less than 2% is required.
(3)The total output current must not exceed the value determined by the following equation.
(Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9
(4) In parallel operation 3 units is the maximum, please consult the manufacturer for other applications.
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
(6) Wires of remote sensing should be kept at least 10 cm from input wires.
No.1(Master)
+V
CN1
+S
-S
CS
+S
-S
CS
CN2
-V
AC/L AC/N
+S
-S
+V
-V
Load
No.2(Slave)
+V
CN1
+S
-S
CS
+S
-S
CS
CN2
-V
AC/L AC/N
No.3(Slave)
+V
CN1
+S
-S
CS
+S
-S
CS
CN2
-V
AC/L AC/N
(7) Under parallel operation, the "output voltage trim" function is not available.
(8) When in parallel operation, the minimum output load should be greater than 2% of total output load (Min. Load >2% rated current per unit number of unit)
5.Select O.L.P mode
(1)Remove the shorting connector on CN3 that is shown in Fig 5.1, the O.L.P. mode will be "continuous constant current limiting".
(2)Insert the shorting connector on CN3 that is shown in Fig 5.2, the O.L.P. mode will be "constant current limiting with delay shutdown after 5 seconds,
re-power on to recover".
OL-SD
OLP
OL-SD
OLP
Fig. 5.1 Remove the CN3
Fig. 5.2 Insert the CN3
OLP Mode : constant current limiting
OLP Mode : constant current limiting with delay shutdown after 5 seconds