Product Data Sheet
Part Number: C4412ST
4C 22 7/.0096 BC PVC NS PVC
Revision Level:
1
Date:
Sound, Alarm & Security Cable
11/5/2007
A. CONSTRUCTION
Conductor:
Insulation:
Cable:
Jacket:
Print Legend:
DIAMETERS
#22 AWG 7/.0096 Stranded Bare Copper
0.029” nom.
0.007” Wall Polyvinyl Chloride
0.043” nom.
4C @ 4.00" LHL
0.105" nom.
0.015” Wall Polyvinyl Chloride – Beige
0.135" +/- 0.007"
CAROL A (R) CMX OUTDOOR – CMR (UL) C(UL) - - - SW - - - 22 AWG E111240-8 - - (DATE
CODE & SEQUENTIAL FOOTAGE)
B. INDUSTRY APPROVALS
National Electrical Code
UL Standard 444
Article 800
Type CMX/CMR
C. ELECTRICAL PROPERTIES
TEMPERATURE:
SUGGESTED WORKING VOLTAGE (Vrms):
CONDUCTOR D.C. RESISTANCE:
MUTUAL CAPACITANCE:
CHARACTERISTIC IMPEDANCE:
60C
300V
16.7 Ohms/1000 ft nom
39.12 pF/ft @ 1kHz nom
57.9 Ohms @ 1MHz nom
D. COLOR CODE
1
2
3
4
Red
Green
Yellow
Black
(Listed as Individual Conductors or Pairs of Conductors)