TA35-C387L150C0-CZM21

Description
Thermal Circuit Breaker, 2 Pole(s), 15A, 240VAC, 60VDC, Panel Mount,
CategoryCircuit protection    Circuit protection   
File Size3MB,8 Pages
ManufacturerSCHURTER
Websitehttp://www.schurterinc.com/
Environmental Compliance
Download Datasheet Parametric View All

TA35-C387L150C0-CZM21 Overview

Thermal Circuit Breaker, 2 Pole(s), 15A, 240VAC, 60VDC, Panel Mount,

TA35-C387L150C0-CZM21 Parametric

Parameter NameAttribute value
Is it Rohs certified?conform to
MakerSCHURTER
Reach Compliance Codenot_compliant
Actuator typeROCKER
body width26 mm
body height43.9 mm
Body length or diameter39 mm
circuit functionTRIP FREE
Circuit protection typeTHERMAL CIRCUIT BREAKER
Environmental characteristicsIP40; IP00
Installation featuresPANEL MOUNT
Number of poles2
Maximum operating temperature60 °C
Minimum operating temperature-30 °C
physical size39mm x 26mm x 43.9mm
Rated current15 A
Rated voltage (AC)240 V
Rated voltage (DC)60 V
GuidelineCSA; CUL; IEC; UL; VDE
surface mountNO
Terminal shapeQUICK CONNECT
circuit breakers
Thermal Circuit Breaker, rocker actuated, 1-, 2- or 3-pole
TA35 1-pole
TA35 2-pole with CZM23 cover
TA35 3-pole
(pending)
Description
Thermal circuit breaker 1-, 2- or 3-pole
Supplementary protector for general industrial use
Positively trip-free release
Snap-in mounting
Version with illuminated rocker
Different rocker colours
Protection cover for IP65
«Dead-Man»-version (Momentary switch)
Applications
Power tools
Industrial equipment
Equipment for building construction
Medical equipment
Cleaning equipment
Power generators
Commercial and household kitchen appliances
Standards
– IEC 60934
– UL 1077
– CSA C22.2 235
– GB 17701 (pending)
Weblinks
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
TeChniCAl DATA
Rated voltage U
e
1-pole
2-pole
3-pole
Rated current I
n
1- / 2-pole
3-pole
1- / 2-pole, AC 240 V
3-pole, AC 415 V
Accessible range
Terminal side
50 Hz
Impulse 1.2/50 µs
DC 500 V
AC 240 V / 50/60 Hz
DC 32 V
AC 240 V / 50/60 Hz
DC 60 V
AC 415 Y/240 V / 50/60 Hz
0.05 – 20 A
0.05 – 12 A
0.05…20 A: 2000 A, SC (C1)
0.05…12 A: 2000 A
Shock resistance
Degree of protection
IP 40
IP 00
> 2500 V
> 4000 V
> 100 MOhm
Max. switching capacity 1-, 2-pole
for switch only types
3-pole
(without bimetal)
20 A
12 A
Type of tripping
Weight
1-pole
2-pole
3-pole
Overload
IEC 60934
UL 1077
min. 40 cycles @ 6 x I
n
,
cos phi 0.6
min. 50 cycles @ 1.5 x I
n
,
cos phi 0.75 (OLØ)
–30 °C to +60 °C
Admissible ambient
air temperature
Resistance to vibration
IEC 60068-2-6, Test Tc
Conditional short
circuit I
nc
10…60 Hz: ±0.75 mm
60…500 Hz: 10 G
IEC 60068-2-27, Test Ea 30 G / 18 ms
Thermal positively trip free
19 g
32 g
45 g
Dielectric strength
Insulation resistance
Endurance (typical)
Mechanical
50’000 cycles
AC: 1 x I
n
, cos phi 0.6
50’000 cycles
DC: 1 x I
n
, L/R = 2…3ms 50’000 cycles
2
circuit breakers

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号