Delay On Make (Operate)
HRDM Power-Time
Time Delay Relay
Description
The HRDM Series combines an electromechanical relay output with microcontroller timing circuitry. It offers 12
to 230 V operation in five ranges and factory fixed, external, or onboard adjustable time delays with a repeat
accuracy of +/-0.5%. The output contact rating allows for direct operation of heavy loads such as compressors,
pumps, blower motors, heaters, etc. This series is ideal for OEM applications where cost is a factor.
Operation
Upon application of input voltage, the time delay
begins. The output is de-energized before and during
the time delay. At the end of the time delay, the output
relay energizes and remains energized until input
voltage is removed.
Reset:
Removing input voltage resets the time delay
and output.
Function
Delay On Make
30 A SPDT N.O. Output
Contact
12 ... 230 V Operation in
5 Ranges
Encapsulated Circuitry
Delays from 100 ms ...100 m
in 5 Ranges
+/-0.5% Repeat Accuracy
Fixed, External, or Onboard
Adjustment
Approvals:
V = Voltage
L = Load
R = Reset
= Undefined time
TD = Time Delay
Connection
Accessories
B
A
External adjust
potentiometer
P/Ns:
P1004-95
(fig A)
P1004-95-X
(fig B)
NC
NO
C
Mounting bracket
P/N:
P1023-6
Female quick
connect P/Ns:
P1015-64
(AWG 14/16)
P1015-13
(AWG 10/12)
NO = Normally Open L = Load
C = Common, Transfer Contact
Quick connect to
screw adaptor
P/N:
P1015-18
Versa-knob
P/N:
P0700-7
NOTE: A knob, or terminals 4 & 5 are only included
on adjustable units. R
T
is used when external
adjustment is ordered. Relay contacts are not
isolated. Dashed lines are internal connections.
Ordering Table
HRDM
Series
DIN rail P/Ns:
017322005
(Steel)
C103PM
(Al)
See accessory pages for
specifications.
5.8
Example P/N:
HRDM421
Fixed –
HRDM41A0.5S
* If Fixed Delay is selected, insert
delay [0.1
… 1000]
followed by
(S) sec. or [0.1
... 100]
(M) min.
Low Voltage Products & Systems
HRDMGen
DIN rail adaptor
P/N:
P1023-20
→
10.03.05
←
X
Input
–1 -
12 V DC
–2 -
24 V AC
–3 -
24 V DC
–4 -
120 V AC
–6 -
230 V AC
X
Adjustment
–1 -
Fixed
–2 -
Onboard
Knob
–3 -
External
Adjust
X
Time Tolerance
–A
- +/-1%
Blank - +/-5%
X
Time Delay *
–0 - 0.1 ...
10 s
–1 - 1 ... 100 s
–2
- 10 ... 1000 s
–3 - 0.1 ... 10 m
–4 - 1 ... 100 m
Delay On Make (Operate)
HRDM Power-Time
Time Delay Relay
Technical Data
Time Delay
Type
Range
Repeat Accuracy
Tolerance (Factory Calibration)
Reset Time
Time Delay vs. Temperature & Voltage
Input
Voltage
Tolerance
12 V DC & 24 V DC
24 ... 230 V AC
Line Frequency
Power Consumption
Output
Type
Form
Ratings:
General Purpose
Resistive
Motor Load
Microcontroller circuitry
100 ms ... 100 m in 5 adjustable ranges or fixed
+/-0.5% or 20 ms, whichever is greater
+/-1%, +/-5%
≤
150 ms
+/-2%
12 or 24 V DC; 24, 120, or 230 V AC
-15% ... +20%
-20% ... +10%
50 ... 60 Hz
AC
≤
4 VA; DC
≤
2 W
Electromechanical relay
SPDT, non-isolated
SPDT-N.O.
SPDT-N.C.
30 A
15 A
30 A
15 A
20 A
10 A
1 hp*
1/4 hp**
2 hp**
1 hp**
Mechanical -- 1 x 10
6
; Electrical -- 1 x 10
5
, *3 x 10
4
, **6,000
IEEE C62.41-1991 Level A
Encapsulated
≥
2000 V RMS terminals to mounting surface
≥
100 MΩ
DC units are reverse polarity protected
Surface mount with one #10 (M5 x 0.8) screw
3 x 2 x 1.5 in. (76.7 x 51.3 x 38.1mm)
0.25 in. (6.35 mm) male quick connect terminals
-40°C ... +60°C / -40°C ... +85°C
95% relative, non-condensing
≅
3.9 oz (111 g)
125/240 V AC
125/240 V AC
28 V DC
125 V AC
240 V AC
Life
Protection
Surge
Circuitry
Dielectric Breakdown
Insulation Resistance
Polarity
Mechanical
Mounting
Package
Termination
Environmental
Operating / Storage Temperature
Humidity
Weight
External Resistance vs Time Delay
Mechanical View
Onboard Adjust Detail Replaces
Terminals if Ordered
Inches (Millimeters)
HRDMGen
10.03.05
Low Voltage Products & Systems
5.9