Corcom Facility EMI Filters Product Guide
CDSUA Series
Catalog: 1654986
Issue Date: 02.2010
Revision 02.2010
CDSUA Series
Features
• All four current ratings utilize a single housing
(single-wire 30, 60, 100A and two-wire 30A)
• Sealed using 18 AWG steel suitably plated housing
• Removable input cover provides quick access to
terminals
• Three knockouts on the input side
• Discharge bleeder resistor provided to reduce shock
hazard
• Surge protector provided upon request
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Current Rating:
Singe-wire 30, 60 and 100A, two-wire 30A
R.F. Radiation:
100 dB minimum shielding effectiveness
Insertion Loss:
100 dB from 100 kHz - 10 GHz per MIL-STD-220A
Operating Frequency:
50/60Hz
Operating Voltage:
Line to Ground:
Line to Line:
277 VAC (max)
480 VAC (max)
How to Order:
CDSUA 2 030 - C - S
Surge Arrestors (optional)
Conduit Fitting (supplied)
Current Rating
# of Filters
Series
Examples: CDSUA1030-C, CDSUA2030-C-S
20
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
www.tycoelectronics.com
www.corcom.com
Corcom Facility EMI Filters Product Guide
CDSUA Series
(continued)
23.0
564.2
Catalog: 1654986
Issue Date: 02.2010
Revision 02.2010
.437 x .812
11.1 x 20.6
(2)
6.0
8.0
203.2 152.4
Label
Knockouts for
0.75 (19.05) & 1.0 (25.4)
Conduit
3 Places
5.0
127.0
2.5
63.5
2
Corcom Facility EMI Filters — Stand-Alone Filters
6.0
152.4
2.0
50.8
36.0 ± 1.0
914.4 ± 25.4
Ground Stud
& Lug
1.0 (25.4) NPT Supplied
with RF Gasket,
Flange Nut and
Insulating Bushing
Insulated wire
Type THHN
Part Nos.
CDSUA1030-C
CDSUA1060-C
CDSUA1100-C
CDSUA2030-C
Current
(Amps)
30
60
100
2 x 30
Wire Gauge
(AWG)
6
6
1
6
# of
Wires
1
1
1
2
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
USA Cust. Svc.:
Corcom Prods:
1-800-468-2023
1-847-680-7400
21
www.tycoelectronics.com
www.corcom.com