Up to 18000A²s for I²t and 1200Vp blocking voltage
Control voltages: 3-32 VDC, 20-275 VAC (24-190 VDC)
Design according to EN/IEC60947-4-2, EN/IEC60947-4-3,
EN/IEC62314, UL508, CSA 22-2 No. 14-13
•
Integrated voltage transient protection with varistor
•
100kA short circuit current rating according to UL508
1
This new range of solid state
contactors presents a unique
opportunity to maximize effi-
ciency in panel space and is an
evolution of solid state switch-
es for which Carlo Gavazzi is
very well known.
The nominal current ratings
are at 40˚C. The smallest
width is 17.5mm and is rated at
25 AAC.
Product Description
Ordering Key
Voltage transient protection is
standard across the output
with a varistor. Specifications
are stated at 25°C unless oth-
erwise noted.
Solid State Relay
Number of poles
Switching Mode
Rated Operational Voltage
Control voltage
Rated Operational current
Connection type for control
Connection type for power
Connection configuration
Option
RGC 1 A 60 A 40 K G U _
1. Germanischer Lloyd approval applicable only to models RGC...15KGU,
RGC...20KGU, RGC...25KGU and RGC...30KGU
Ordering Key
(Refer to page 2 for available part numbers)
1 Phase SSR
with heatsink
RGC1A: ZC
4
RGC1B: IO
4
Rated voltage,
Blocking voltage
Control voltage
D: 3 or 4-32VDC
A: 20 - 275VAC,
24-190 VDC
23: 230V +10% - 15%, 800Vp
60: 600V +10% -15%, 1200Vp
Rated
current at 40˚C
2
15: 20AAC, 525A²s
20: 23AAC, 525A²s
25: 25AAC, 1800A²s
30: 30AAC, 1800A²s
40: 40AAC, 3200A²s
42: 43AAC, 18000A²s
60: 60AAC, 3200A²s
62: 65AAC, 18000A²s
90: 85AAC, 6600A²s
Connection
control
K: Screw
G: Box clamp
Connection
power
G: Box clamp
Connection
configuration
U: SSR
Option
P: Overtemperature
protection
(OTP)
3
2. Refer to Derating Curves
3. Default control connection for RGC...P is box clamp. See Connections Specifications.
4. ZC = Zero cross switching, IO = Instant On switching
Specifications are subject to change without notice (22.05.2018)
1
RGC...U
Selection Guide
Rated voltage,
Blocking voltage,
Switching mode
230V, 800Vp
ZC
Control voltage
Connection
control/power
Rated operational current @ 40
o
C (I
2
t value)
Product width
20 AAC (525A²s)
23 AAC (525A²s)
17.5mm, low depth
17.5mm
25 AAC (1800A²s)
17.5mm, low depth
30 AAC (1800A²s)
22.5mm
3-32VDC
20-275VAC, 24-190VDC
Screw/Box
Screw/Box
RGC1A23D15KGU
RGC1A23A15KGU
20 AAC (525A²s)
17.5mm, low depth
RGC1A23D20KGU
RGC1A23A20KGU
23 AAC (525A²s)
17.5mm
RGC1A23D25KGU
RGC1A23A25KGU
25 AAC (1800A²s)
17.5mm, low depth
RGC1A23D30KGU
RGC1A23A30KGU
30 AAC (1800A²s)
22.5mm
600V,1200Vp
ZC
4-32VDC
20-275VAC, 24-190VDC
Screw/Box
Screw/Box
RGC1A60D15KGU
RGC1A60A15KGU
RGC1A60D20KGU
RGC1A60A20KGU
RGC1A60D25KGU
RGC1A60A25KGU
RGC1A60D30KGU
RGC1A60A30KGU
40 AAC (3200A²s)
35mm
43 AAC (18000A²s)
35mm
60 AAC (3200A²s)
70mm
65 AAC (18000A²s)
70mm
4-32VDC
20-275VAC, 24-190VDC
Screw/Box
Screw/Box
RGC1A60D40KGU
RGC1A60A40KGU
20 AAC (525A²s)
17.5mm, low depth
RGC1A60D42KGU
RGC1A60A42KGU
23 AAC (525A²s)
17.5mm
RGC1A60D60KGU
RGC1A60A60KGU
25 AAC (1800A²s)
17.5mm, low depth
RGC1A60D62KGU
RGC1A60A62KGU
30 AAC (1800A²s)
22.5mm
600V, 1200Vp
IO
4-32VDC
Screw/Box
RGC1B60D15KGU
RGC1B60D20KGU
RGC1B60D25KGU
RGC1B60D30KGU
40 AAC (3200A²s)
35mm
43 AAC (18000A²s)
35mm
60 AAC (3200A²s)
70mm
65 AAC (18000A²s)
70mm
4-32VDC
Screw/Box
RGC1B60D40KGU
RGC1B60D42KGU
RGC1B60D60KGU
RGC1B60D62KGU
Selection Guide - RGC..P
Rated voltage,
Blocking voltage,
Switching mode
Control voltage
(Integrated Overtemperature Protection)
Rated operational current @ 40
o
C (I
2
t value)
Product width
40 AAC (3200A²s)
35mm
Connection
control/power
60 AAC (3200A²s)
70mm
85 AAC (6600A²s)
70mm + fan
600V, 1200Vp
ZC
5-32VDC
20-275VAC, 24-190VDC
Box/Box
Box/Box
RGC1A60A40GGUP
85AAC (6600A²s)
70mm + fan
RGC1A60D40GGUP
RGC1A60A60GGUP
RGC1A60D60GGUP
RGC1A60A90GGUP
RGC1A60D90GGUP
600V, 1200Vp
IO
5-32VDC
Box/Box
RGC1B60D90GGUP
2
Specifications are subject to change without notice (22.05.2018)
RGC...U
Output Voltage Specifications
Operational voltage range
Blocking voltage
Internal varistor
24-240 VAC,
+10%, -15% on max
800Vp
275V
RGC..23..
RGC..60..
42-600 VAC,
+10% -15% on max
1200 Vp
625V
General Specifications
Latching voltage
(across L1-T1)
Operational frequency
range
Power factor
Touch Protection
Control input status
20V
Rated impulse withstand
Over-voltage category
Isolation
Input to Output
Pollution degree
45 to 65Hz
> 0.5 @ Vrated
IP20
continuously ON Green LED,
when control input is applied
2
(non-conductive pollution with
possibilities of condensation)
6 kV (1.2/50μs) for voltage,
Uimp
III
(fixed installations)
RGC... 4000 Vrms
RGC...D..P 2500 Vrms
RGC...A..P 4000 Vrms
Input and Output RGC... 4000 Vrms
to case
RGC...D..P 4000 Vrms
RGC...A..P 4000 Vrms
Input to Fan/ Alarm Output
RGC...A..P 2500 Vrms
Specifications are subject to change without notice (22.05.2018)
3
RGC...U
Output Specifications
Rated operational current
6
AC-51 rating @ Ta=25°C
AC-51 rating @ Ta=40°C
AC-53a rating @ Ta=40°C
Number of motor starts per hour
(x:6, Tx:6s, F:50%) at 40˚C
5
Min. operational current
Rep. overload current -
(Motor Rating) PF = 0.4 - 0.5
UL508: T
AMB
=40°C, t
ON
=1s, t
OFF
=9s,
50cycles
RGC..15..
20 AAC
20 AAC
5 AAC
RGC..20..
25.5 AAC
23 AAC
5 AAC
30 AAC
25 AAC
5 AAC
RGC..25..
30 AAC
30 AAC
8 AAC
RGC..30..
30
150 mAAC
30
150 mAAC
60 AAC
325 Ap
30
250 mAAC
51 AAC
600 Ap
30
250 mAAC
84 AAC
600Ap
51 AAC
Maximum transient surge current (I
TSM
), t=10ms
325 Ap
Maximum off-state leakage current
at rated voltage
3 mAAC
I²t for fusing (
t=10ms
), minimum
525 A²s
Crititcal dv/dt (@ Tj init = 40°C)
1000 V/μs
RGC..40..
3 mAAC
525 A²s
1000 V/μs
3 mAAC
1800 A²s
1000 V/μs
RGC..62..
75 AAC
65 AAC
20 AAC
3 mAAC
1800 A²s
1000 V/μs
RGC..90..
85 AAC
85 AAC
18 AAC
Rated operational current
6
AC-51 rating @ Ta=25°C
AC-51 rating @ Ta=40°C
AC-53a rating @ Ta=40°C
Number of motor starts per hour
(x:6, Tx:6s, F:50%) at 40˚C
5
Min. operational current
Rep. overload current -
(Motor Rating) PF = 0.4 - 0.5
UL508: T
AMB
=40°C, t
ON
=1s, t
OFF
=9s,
50cycles
47 AAC
40 AAC
13 AAC
RGC..42..
50 AAC
43 AAC
16 AAC
RGC..60..
70 AAC
60 AAC
14.8 AAC
30
400 mAAC
30
500 mAAC
126 AAC
1900 Ap
30
400 mAAC
126 AAC
800 Ap
30
500 mAAC
168 AAC
1900 Ap
30
400 mAAC
168 ACC
1150 Ap
126 AAC
Maximum transient surge current (I
TSM
), t=10ms
800 Ap
Maximum off-state leakage current
at rated voltage
3 mAAC
I²t for fusing (
t=10ms
), minimum
3200 A²s
Crititcal dv/dt (@ Tj init = 40°C)
1000 V/μs
3 mAAC
18000 A²s
1000 V/μs
3 mAAC
3200 A²s
1000 V/μs
3 mAAC
18000 A²s
1000 V/μs
3 mAAC
6600 A²s
1000 V/μs
5. Overload profile for AC-53a;
Ie: AC-53a: x-Tx: F-S, where Ie = nominal current (AC-53a AAC), x = overload current factor, Tx = duration of overload current (s), F = duty cycle (%), S = number of
starts per hour. Example; 5A: AC-53a: 6 - 6 : 50 - 30 = max. 30 starts for the RGC..15 with an overload profile of 30A for 6 seconds with a duty cycle of 50%
6. Refer to Derating Curves
Overtemperature Alarm Specifications for RGC...P
Output type
Normal state
Maximum current rating
Rated voltage (EN61131-2: 2003)
Rated voltage, Us
Fan rating, U
f
Alarm voltage drop
Visual Indication
Reverse polarity protection
7, 8
, Ua
RGC..D..P
PNP open collector_
Closed
50 mADC
24VDC -15%, +20%
RGC...D90GGUP 24VDC ± 10%
RGC...A90GGUP N/A
Typical
2.8VDC
Maximum
4VDC
Continous Red LED
24VDC
RGC..A..P
Potential Free
Closed
50 mADC
24VDC -15%, +20%
N/A
24VDC ±10%, 50mA nominal
1.8VDC
3.5VDC
Continous Red LED
24VDC
7. DC supply for alarm signal should be supplied from a Class 2 power source
8. Maximum voltage to be applied between 11+ and 12- (Ua) terminals should be 35VDC maximum with reference to A2-
4
Specifications are subject to change without notice (22.05.2018)
RGC...U
Input Specifications
Control voltage range
9, 10
RGC..23..
RGC..D..
3 - 32 VDC
RGC..A..
20 - 275 VAC,
24 (-10%) - 190 VDC
20-275 VAC,
24 (-10%) - 190 VDC
20-275 VAC,
24 (-10%) - 190 VDC
20 VAC/DC
20 VAC/ 24VDC
5 VAC/DC
-
RGC..60..
Pick-up voltage
Drop-out voltage
Maximum Reverse voltage
Response time pick-up (RGC1A..)
Response time pick-up (RGC1B..)
Response time drop-out
Input current @ 40°C
RGC...P (Uc)
RGC..23..
RGC..60..
RGC...P
4 - 32 VDC
3.0 VDC
3.8 VDC
5 VDC
1 VDC
32 VDC
5 - 32 VDC
0.5 cycle + 500µs @ 24VDC
9. DC control to be supplied by class 2 power source according to UL1310
350µs @ 24 VDC
0.5 cycle
+ 500µs @ 24VDC
See diagrams below
2 cycles
@ 230VAC/110VDC
0.5 cycle + 40ms @ 230VAC/ 110VDC
N/A
See diagrams below
10. For GL approved models control range for RGC1.23... is 4-32VDC and for RGC1.60... 5-32VDC
RG..A..
40mA
35mA
30mA
25mA
20mA
15mA
10mA
5mA
0mA
0VAC
RGC1 .. A : input current vs input voltage
RGC .. A
RGC..A..P
(Normal Operation)
RGC..A..P
(Active Protection)
50VAC
100VAC
150VAC
200VAC
250VAC
300VAC
RGC1 .. A : input current vs input voltage
40mA
35mA
30mA
25mA
20mA
15mA
10mA
5mA
0mA
0VDC
RGC..A..P
(Normal Operation)
RGC..A..P
(Active Protection)
RGC .. A
50VDC
100VDC
150VDC
200VDC
250VDC
Specifications are subject to change without notice (22.05.2018)