MACX MCR-EX-T-UIREL-UP...
Temperature transducers with intrinsically safe
input for temperature sensors, voltage signals,
resistance-type sensors and potentiometers
Data sheet
104602_en_06
1
Description
© PHOENIX CONTACT 2014-07-10
The configurable and programmable
MACX MCR-EX-T-UIREL-UP...
temperature transducer is
used for the intrinsically safe (Ex i) operation of all standard
temperature sensors (RTDs and thermocouples), voltage
signals, remote resistance-type sensors and potentiome-
ters. The temperature input signals are output in a linearized
format at the output. In addition to an analog current and
voltage output, the module also has three switching outputs.
If you use the device in safety-related applications, relay 2
and 3 are connected to create a safety-related switching
output. The power supply has been designed as a wide
range power supply.
The devices can be installed in zone 2 in the protection type
"n" (EN 60079-15).
Features such as sensor type, connection method, measur-
ing range, measuring unit, filter, alarm signal and output
range can be configured using the ANALOG-CONF soft-
ware and a device-specific DTM (Device Type Manager).
Features
–
Input for all standard temperature sensors (RTDs and
thermocouples), voltage signals, remote resistance-
type sensors and potentiometers.
With intrinsically safe inputs [Ex ia] IIC
Current and voltage output
Switching output (3 PDT relay)
Switching output SIL: 1 relay
Configuration via software (FDT/DTM, ANALOG-
CONF) or operator interface (IFS-OP-UNIT)
Up to SIL 2 according to EN 61508 on output 4 ... 20 mA
3-way electrical isolation
Installation in zone 2 permitted
Wide range power supply 19.2 ... 253 V AC/DC
With screw or spring-cage connection
(push-in techno-
logy)
–
–
–
–
–
–
–
–
–
–
WARNING: Explosion hazard
The device is an item of associated electrical equipment for intrinsically safe circuits. It is designed for
use in zone 2, if specific conditions are observed.
When installing and operating the device, the applicable safety directives (including national safety directives), ac-
cident prevention regulations, as well as general technical regulations must be observed.
WARNING: Explosion hazard
Please observe the safety regulations and installation notes on page 8.
Make sure you always use the latest documentation.
It can be downloaded at
phoenixcontact.net/products.
This data sheet is valid for the products listed in section 3 “Ordering data” .
MACX MCR-EX-T-UIREL-UP...
2
1
2
3
4
5
Table of contents
Description..................................................................................................................................
1
Table of contents ........................................................................................................................
2
Ordering data..............................................................................................................................
5
Technical data ............................................................................................................................
6
Safety regulations and installation notes.....................................................................................
8
5.1
5.2
5.3
5.4
5.5
5.6
Installation notes
............................................................................................................................................... 8
Intrinsic safety
.................................................................................................................................................... 8
Installation in Zone 2
........................................................................................................................................ 8
Potentially dust-explosive areas
..................................................................................................................... 8
UL notes
............................................................................................................................................................. 8
Use in safety-related applications (SIL 2)
...................................................................................................... 8
6
Sensor types ..............................................................................................................................
9
6.1
6.2
6.3
6.4
6.5
6.6
Thermocouple (TC) with internal cold junction compensation
................................................................. 10
Thermocouple (TC) with external or without cold junction compensation
.............................................. 10
Voltage input
.................................................................................................................................................... 10
Potentiometer
.................................................................................................................................................. 10
Resistance thermometer (RTD) ........................................................................................................
10
Measuring resistances
................................................................................................................................... 10
7
Minimum span and measuring accuracies
.................................................................................................. 11
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
7.9
Pt and Ni-RTD inputs
...................................................................................................................................... 11
Cu-RTD inputs
................................................................................................................................................. 11
NI1000 input (Landis & Gyr), KTY 81-110, KTY 84-130 (Philips)
............................................................ 11
Thermocouple input
........................................................................................................................................ 11
Cold junction error.............................................................................................................................
11
Voltage signal input
........................................................................................................................................ 11
R transducers and resistors
.......................................................................................................................... 11
Potentiometer
.................................................................................................................................................. 12
Output signals
................................................................................................................................................. 12
8
Installation .................................................................................................................................
13
8.1
8.2
8.3
8.4
8.5
8.6
Basic circuit diagrams
................................................................................................................................... 13
Structure
........................................................................................................................................................... 14
Dimensions
...................................................................................................................................................... 14
Mounting
.......................................................................................................................................................... 14
Connecting the cables
................................................................................................................................... 15
Power supply ....................................................................................................................................
15
104602_en_06
PHOENIX CONTACT
2
MACX MCR-EX-T-UIREL-UP...
8.7
8.8
8.9
Current output
................................................................................................................................................. 15
Voltage output
................................................................................................................................................. 15
Switching output
.............................................................................................................................................. 16
8.10.1
8.10.2
8.10.3
8.10.4
8.10.5
8.10.6
Switching behavior (2): Undertemperature limit (≤ SPH) .............................................................................. 17
(Switching behavior (3): Overtemperature limit (≥ SPH) ............................................................................... 17
Switching behavior (4): Undertemperature limit with hysteresis (≤ SPL) ...................................................... 18
Switching behavior (5): Overtemperature limit with hysteresis (≥ SPH) ........................................................ 18
Switching behavior (6): Temperature range limit (≤ SPL and
≥
SPH) ........................................................... 19
Switching behavior (7): Temperature range limit (≥ SPL and
≤
SPH) ........................................................... 19
8.10 Switching output behavior with manual acknowledgement (latching)
.................................................... 17
8.11 Connection of relay contacts
......................................................................................................................... 20
8.12 Monitoring function
......................................................................................................................................... 21
8.13 Operating modes
............................................................................................................................................ 21
8.13.1 SIL ON/SIL OFF ........................................................................................................................................... 21
8.13.2 Service mode ............................................................................................................................................... 21
9
Configuration .............................................................................................................................
21
9.1
9.2
9.3
9.4
9.5
9.6
9.7
9.8
9.9
Delivered state/standard configuration
........................................................................................................ 22
Zero adjust, adjustment via buttons S2 and S3 (only possible with SIL OFF)
....................................... 22
Span adjust, adjustment via buttons 2 and 4 (only possible with SIL OFF)
............................................ 22
Force output......................................................................................................................................
22
Cable compensation, 2-wire RTD or RTD 1 with 2 x RTD
........................................................................ 22
Cable compensation RTD 2 with 2 x RTD or TC with external cold junction compensation (TC + CJ
external)
........................................................................................................................................................... 22
Automatic potentiometer adjustment (teach-in)
......................................................................................... 23
Manual acknowledgement of switching outputs (latch function)
.............................................................. 23
LED status indicators ........................................................................................................................
23
10 Password...................................................................................................................................
24
11 Configuration with the service PC
................................................................................................................... 24
11.1 System requirements
..................................................................................................................................... 24
11.2 Configuring the user characteristic curve ..........................................................................................
25
12 Comparison of safety data
................................................................................................................................ 25
13 Connection examples ................................................................................................................
26
13.1 Current output
................................................................................................................................................. 26
13.2 Voltage output...................................................................................................................................
27
13.3 Switching output
.............................................................................................................................................. 27
14 Flow chart, operator interface
.......................................................................................................................... 28
14.1 Menu structure
................................................................................................................................................ 29
14.2 Key for start screen
......................................................................................................................................... 30
104602_en_06
PHOENIX CONTACT
3
MACX MCR-EX-T-UIREL-UP...
14.3 Key for MENU
.................................................................................................................................................. 30
14.4 Key for SETTINGS - Configure
..................................................................................................................... 30
14.5 Key for SETTINGS - Service
......................................................................................................................... 30
14.6 Key for SETTINGS - Save
............................................................................................................................. 31
14.7 Key for input
..................................................................................................................................................... 32
14.7.1 Key for input configuration (analog input) ..................................................................................................... 32
14.8 Key for output
.................................................................................................................................................. 35
14.8.1 Key for output configuration (analog output)................................................................................................. 35
14.9 Key for error handling
..................................................................................................................................... 36
14.10 Key for switch
.................................................................................................................................................. 36
14.10.1Key for switch 1 ........................................................................................................................................... 36
14.10.2Key for switch 2 ........................................................................................................................................... 36
14.10.3Key for switch 3 (only configurable with SIL OFF)........................................................................................ 37
15 IFS-OP-UNIT operator interface error codes .............................................................................
37
Appendix
Safety-related applications (SIL 2)
............................................................................................................................. A-1
104602_en_06
PHOENIX CONTACT
4
MACX MCR-EX-T-UIREL-UP...
3
Ordering data
Type
MACX MCR-EX-T-UIREL-UP
MACX MCR-EX-T-UIREL-UP-SP
Temperature transducer, Ex i
Description
Standard configuration/in-stock article, with screw connection
Standard configuration/in-stock article, with spring-cage connection
Order No.
2865751
2924799
Pcs. / Pkt.
1
1
Accessories
Description
Operator interface for the configuration of compatible MACX modules.
Cradle unit, for snapping the operating and display unit onto the DIN rail
Programming adapter for MACX MCR... devices. With USB interface for pro-
gramming with the ANALOG-CONF software
Cold junction compensation connector for thermocouples
Type
IFS-OP-UNIT
IFS-OP-CRADLE
IFS-USB-PROG-ADAPTER
MACX MCR-EX-CJC
Order No.
2811899
2811886
2811271
2925002
Pcs. / Pkt.
1
1
1
1
For additional accessories, please refer to the Interface technology and switching devices catalog from Phoenix Contact.
104602_en_06
PHOENIX CONTACT