Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5502G1 Multi-Conductor - Water-Blocked for Indoor/Outdoor Use
For more Information
please call
1-800-Belden1
General Description:
Rated-CM, 1-22 AWG tinned copper pair with PVC insulation and a Beldfoil shield, 2-22 AWG tinned
copper conductors with PVC insulation, Overall water resistant tape and PVC jacket with ripcord
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors # Pairs AWG Stranding Conductor Material
1
2
22
22
7x30
7x30
TC - Tinned Copper
TC - Tinned Copper
4
Total Number of Conductors:
Insulation
Insulation Material:
Insulation Material
Wall Thickness (in.)
PVC - Polyvinyl Chloride .010
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material
Beldfoil®
Coverage (%)
Tape Aluminum Foil-Polyester Tape 100
Inner Shield Drain Wire AWG:
AWG Stranding Conductor Material
24
7x32
TC - Tinned Copper
Non-woven
Inner Shield Waterblocking Tape:
Outer Shield
Outer Shield Material:
Outer Shield Material
Unshielded
Outer Shield Waterblocking Tape:
Yes
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
Nom. Wall Thickness (in.)
PVC - Polyvinyl Chloride .025
Outer Jacket Ripcord:
Yes
Overall Cable
Overall Cabling Color Code Chart:
Number Color
1
2
3
White
Green
Group/Cond. Color
Conductor
Conductor
0.234 in.
Black and Red Shielded Pair
Overall Nominal Diameter:
Pair
Pair Lay Length & Direction:
Lay Length (in.)
1.500
Mechanical Characteristics (Overall)
Operating Temperature Range:
Bulk Cable Weight:
Max. Recommended Pulling Tension:
Min. Bend Radius/Minor Axis:
-20°C To +105°C
24.400 lbs/1000 ft.
36.400 lbs.
2.375 in.
Page 1 of 3
09-11-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5502G1 Multi-Conductor - Water-Blocked for Indoor/Outdoor Use
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification:
CEC/C(UL) Specification:
EU Directive 2011/65/EU (ROHS II):
EU CE Mark:
EU Directive 2000/53/EC (ELV):
EU Directive 2002/95/EC (RoHS):
EU RoHS Compliance Date (mm/dd/yyyy):
EU Directive 2002/96/EC (WEEE):
EU Directive 2003/11/EC (BFR):
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
CM
CM
Yes
Yes
Yes
Yes
10/01/2005
Yes
Yes
Yes
Yes
Flame Test
UL Flame Test:
C(UL) Flame Test:
UL1685 UL Loading
FT1
Plenum/Non-Plenum
Plenum (Y/N):
No
Electrical Characteristics (Overall)
Nom. Inductance:
Inductance (µH/ft)
.18
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/ft)
44.500
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/ft)
80.100
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/1000 ft)
16.4
Maximum Conductor DC Resistance:
DCR @ 20°C (Ohm/100 m)
16.4
Max. Operating Voltage - UL:
Voltage
300 V RMS
Max. Recommended Current:
Current
2.2 Amps per conductor @ 25°C
Put Ups and Colors:
Item #
5502G1 0081000
5502G1 008500
Notes:
C = CRATE REEL PUT-UP.
Putup
1,000 FT
500 FT
Ship Weight
29.000 LB
14.000 LB
Color
GRAY
GRAY
Notes
C
Item Desc
1 FS PR + 2 #22 S-R PVC PVC
1 FS PR + 2 #22 S-R PVC PVC
Revision Number: 2
© 2017 Belden, Inc
All Rights Reserved.
Revision Date: 03-13-2013
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described herein are subject to error or omission and to
change without notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for
any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether
in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with EU RoHS (Directive 2002/95/EC, 27-Jan-2003). Material manufactured prior to the compliance date may be in stock at Belden facilities
and in our Distributor’s inventory. The information provided in this Product Disclosure, and the identification of materials listed as reportable or restricted within the Product Disclosure, is
correct to the best of Belden’s knowledge, information, and belief at the date of its publication. The information provided in this Product Disclosure is designed only as a general guide for the
Page 2 of 3
09-11-2017
Detailed Specifications & Technical Data
ENGLISH MEASUREMENT VERSION
5502G1 Multi-Conductor - Water-Blocked for Indoor/Outdoor Use
safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. This Product Disclosure is not to be considered a warranty or quality specification.
Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the
product.
Belden declares this product to be in compliance with EU LVD (Low Voltage Directive 2014/35/EU).
Page 3 of 3
09-11-2017