Technical Data 6001
Effective November 2016
Supersedes September 2016
R-Rated medium voltage fuses
for motor circuit protection
Features and benefits
•
Current-limiting R-Rated fuses will safely
interrupt all currents between their minimum
and maximum interrupting ratings and will melt
in a range of 15 to 35 seconds at a value of 100
times the “R” number per ANSI C37
.46.
R-Rated fuses are physically dimensioned for
easy installation in existing hardware.
Available in standard, AMPGARD Hookeye and
hermetically sealed, and bolt-on mounting styles
to meet application needs.
4.8kV Limitamp
®
bolt-on constructions available
in ratings from 2R to 24R.
2.4kV and 4.8kV AMPGARD hermetically sealed
constructions are suitable for Class I, Group D,
Div. 2 hazardous locations.
Open fuse indicator on all mounting styles
speeds troubleshooting.
Optional remote contact signaling microswitch
available.
Classified as backup fuses for current-limiting
protection of medium voltage motor controllers
(short-circuit performance only).
These fuses are in a self-contained, non-venting
package for installation indoors or outdoors in
an enclosure.
Medium voltage motors and controllers
•
•
•
•
•
•
Description:
•
•
Indoor/enclosure, R-Rated medium voltage,
current-limiting fuses for motor circuit
protection.
•
Typical applications:
•
Contents
Description
Page
Description
Page
2.4kV R-Rated fuses . . . . . . . . . . . . . . . . . . . . 2-7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Catalog numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4.8kV R-Rated fuses . . . . . . . . . . . . . . . . . . . 8-16
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Catalog numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-16
7.2kV R-Rated fuses . . . . . . . . . . . . . . . . . . 17-21
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Catalog numbers . . . . . . . . . . . . . . . . . . . . . . . . . 18
Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-21
Technical Data 6001
Effective November 2016
R-Rated medium voltage fuses
for motor circuit protection
Dimensions - in [mm]
Construction
Standard -
short
AMPGARD
Hookeye*
Bolt-on
Amp
range
25-230A
390-450A
70-230A
390-450A
25-230A
390-450A
Dimension
A
10.8 (274)
10.8 (274)
10.8 (274)
10.8 (274)
19.2 (488)
19.2 (488)
B
3 (76)
3 (76)
3 (76)
3 (76)
17 (455)
.9
17 (455)
.9
C
3 (76)
3 (76)
3 (76.
3 (76)
3 (76)
3 (76)
D
—
3.3 (84)
—
3.3 (84)
—
3.3 (84)
2.4kV R-Rated fuses
Catalog symbols:
Code-(amps)R
2CLS-25
2ACLS-25
JCK-_R
JCK-A-_R
2HCLS-_R
2BCLS-_R
Construction
Standard (25A only)
AMPGARD Hookeye (25A only)
Standard (2R-24R)
AMPGARD Hookeye* (2R-24R)
Hermetically sealed AMPGARD Hookeye* (25A/2R-24R)
Bolt-on (25A/2R-24R)
* Includes hermetically sealed versions.
* For use in 400 amp AMPGARD motor starters.
Ratings:
•
Volts
•
•
Standard and AMPGARD Hookeye
2.4kV (nominal)
2.54kV (max design)
D
C
B
A
Gripping tab
for Hookeye
constructions
•
•
Amps 25-450A
Interrupting ratings
•
•
Indicator
50kA Sym
80kA Asym
Agency information:
•
UL Recognized: Guide #MSSS2, File #E96676
Recommended fuse holders for standard constructions:
Amp range Description
Fuseclips
25-230A 3” Enclosed fuseclip*
25-450A
Fuse holders
Non-disconnect holder, porcelain
25-230A Non-disconnect holder, glass polyester
Single barrel Disconnect holder, porcelain
Disconnect holder, glass polyester
Non-disconnect holder, porcelain
390-450A Non-disconnect holder, glass polyester
Double barrel Disconnect holder, porcelain
Disconnect holder, glass polyester
* Single barrel only, not sold in pairs.
2CLE-PNM-D
2CLE-GNM-D
2CLE-PDM-D
2CLE-GDM-E
2CLE-PNM-E
2CLE-GNM-E
2CLE-PDM-E
2CLE-GDM-E
3” Open fuseclip
3” Spring loaded open fuseclip
A3354730
1A0065
9078A67G04
Cat. No.
Bolt-on
E = 3 [76.2]
F = 2.5 [63.5]
G = 2.04 [51.81
H = 0.96 [24.4]
I= 0.5 [12.7]
EFGHI
R 0.23 [5.81] Typ.
D
C
Indicator
2.12
[53.8]
3.0
[76.2]
3.0
[76.2]
B
A
2
Eaton.com/bussmannseries
R-Rated medium voltage fuses
for motor circuit protection
2.4kV R-Rated fuse catalog numbers
Mounting style (minimum interrupting rating in amps)
Amp rating
25
70
100
130
150
170
200
230
390
450
“R”
Designation
—
2R
3R
4R
5R
6R
9R
12R
18R
24R
AMPGARD Hookeye
Standard
2CLS-25* (90)
JCK-2R (165)
JCK-3R (220)
JCK-4R (320)
JCK-5R (410)
JCK-6R (480)
JCK-9R (720)
JCK-12R (970)
JCK-18R** (1430)
JCK-24R** (1880)
Regular
2ACLS-25* (90)
JCK-A-2R (165)
JCK-A-3R (220)
JCK-A-4R (320)
JCK-A-5R (410)
JCK-A-6R (480)
JCK-A-9R (720)
JCK-A-12R (970)
JCK-A-18R** (1430)
JCK-A-24R** (1880)
Hermetically sealed
2HCLS-25* (90)
2HCLS-2R (170)
2HCLS-3R (245)
2HCLS-4R (340)
2HCLS-5R (430)
2HCLS-6R (500)
2HCLS-200* (1000)
2HCLS-230* (1250)
2HCLS-390* (1700)
2HCLS-24R (2100)
Technical Data 6001
Effective November 2016
Number
Bolt-on of barrels
2BCLS-25* (90) 1
2BCLS-2R (170) 1
2BCLS-3R (245) 1
2BCLS-4R (340) 1
2BCLS-5R (430) 1
2BCLS-6R (500) 1
2BCLS-9R (1000) 1
2BCLS-12R (1250) 1
2BCLS-18R (1700) 2
2BCLS-24R (2100) 2
* Does not comply with ANSI C37 for “R” rating.
.46
** Not UL Recognized
JCK and 2HCLS Type mountings -in (mm)
Catalog
number
Hole centers
A
B
6 (152.4)
6 (152.4)
6 (152.4)
6 (152.4)
6 (152.4)
6 (152.4)
C
18 (457
.2)
18 (457
.2)
18 (457
.2)
18 (457
.2)
18 (457
.2)
18 (457
.2)
18 (457
.2)
18 (457
.2)
Overall
length
D
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
0.62 (15.7)
Hole Inset
Hole centers
E
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
1.75 (44.4)
F
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
4.5 (114.3)
Contact
height
G
11.72 (297
.7)
11.72 (297
.7)
15.28 (388.1)
15.28 (388.1)
8.79 (223.3)
8.79 (223.3)
12.48 (317
.0)
12.48 (317
.0)
Overall
height
BIL rating
(kV)
60
60
60
60
60
60
60
60
Disconnect single barrel
†
2CLE-GDM-D 8.24 (209.3)
2CLE-PDM-D 8.24 (209.3)
Disconnect double barrel
†
2CLE-GDM-E 8.24 (209.3)
2CLE-PDM-E
8.24 (209.3)
Non-disconnect single barrel
2CLE-GNM-D 8.24 (209.3)
2CLE-PNM-D 8.24 (209.3)
Non-disconnect double barrel
2CLE-GNM-E 8.24 (209.3)
6 (152.4)
2CLE-PNM-E
8.24 (209.3)
6 (152.4)
2.4kV disconnect mounting
†
G
D
F
2.4kV non-disconnect mounting
G
D
F
E
E
A
C
A
C
E
E
D
B
D
B
† Disconnect mountings provide a means for fuse extraction only. Do not use a
disconnect mounting for load switching or fuse removal while energized.
Eaton.com/bussmannseries
3