POWER ENTRY MODULES /
GERÄTESTECKER-KOMBIELEMENTE
Power entry module Type 6145
– Panel mount: screw-on, front-side
– Appliance inlet, circuit breaker type TA 45
– Version with line filter/shield see page 126
6145
50
75
100
Characteristics
• Circuit breaker with line switch, 2-pole,
non-illuminated or illuminated
• Combined with thermal overload protection
• Optional with undervoltage release or remote trip release
• All single elements wired
Unwired versions available on request
Technical data
Rated voltage
Rated currents I
n
125/250 VAC
0,1 up to 10 A; SEV, VDE, Semko,
0,1 up to 15 A; UL, CSA
See table 1
> 1,5 kV between L/N-PE
Dielectric strength
(50 Hz, 1 Min.)
Allowable ambient air
temperatures T
a
–10 °C to +55 °C
Degree of protection (front-side) IP40 acc. to IEC 60529
suitable for equipment with prot. cl. I, acc.
Protection class
to IEC 61140
Terminals
quick-connect 6,3 x 0,8 mm
Panel thickness s
max. 6 mm
Materials: Housing
Thermoplastic, black, UL94 V-0
Appliance-inlet
acc. to IEC/EN 60320-1/C14, Protection
class I, pin-temperature 70 °C
(cold condition)
acc. to IEC/EN 60934, UL 1077,
CSA 22.2 no 235.
2-pole rocker switch, illuminated or
non-illuminated.
Optional with undervoltage- or
remote trip release
Short circuit capacity Icn:
at In < 3A/240 VAC : 10 x In
at In
≥
3A/240 VAC : 300 A
Circuit breaker
type TA 45
Accessories see page 171
70
www.schurter.com
POWER ENTRY MODULES /
GERÄTESTECKER-KOMBIELEMENTE
Technical data (continued)
Circuit breaker
Tripping characteristics
In < 3 A
[ min ] [ sec ]
10’000
Type /
Typ
Rated current /
Nennstrom
TA45
In < 3 A
1-pole protected
2-pole protected
Ambient temp.
Umgebungstemp.
6145
Effect of ambient temperature
The unit is calibrated for an ambient
temperature of +23 °C. To determine the
rated current for a lower or higher
ambient temperature, use a correction
factor from the table below.
Tripping characteristics
In
≥
3…≤ 15 A
[ min ] [ sec ]
10’000
Type /
Typ
Rated current /
Nennstrom
TA45
I n
≥
3...
≤
15 A
1-pole protected
2-pole protected
Ambient temp.
Umgebungstemp.
60
30
20
10
5
200
100
1
50
2000
1000
500
60
30
20
2’000
1’000
500
+23
°C
10
5
+23
°C
200
100
1
50
20
10
5
2
1
0,5
Tripping time
20
10
5
2
1
0,5
Tripping time
Ambient temperature /
Umgebungs-
[°C]
–10
–5
0
+23
+30
+40
+55
Example
Rated current at +23 °C
Nennstrom bei +23 °C
Ambient temperature
Umgebungstemperatur
Correction
factor
0,89
0,91
0,92
1,00
1,03
1,08
1,16
0,3
0,2
0,1
1,05 1,32
2
3
[xI
4
5
8
10
n]
0,3
0,2
0,1
1,05 1,32
2
3
4
5
8
10
6,0 A
+40 °C
Multiple of rated current
Multiple of rated current
[ x In ]
Correction factor /
Korrekturfaktor 1,08
Chosen rated current at
+ 40 °C ambient temperature
6 A x 1,08 = 6,5 A
Dimensions
Panel cut-out
36
43
Detail a
2
1
29
+0,2
0
Diagram
Line
ø6
R3
0
-0,5
TA45
Load
6,3 x 0,8 mm
91,5
3,25
6,3 x 0,8 mm
24,2
M3 / ø 3,6
13,5
Mounting screw torque 0,5 Nm
67,5*
*
Version TA45 with undervoltage release
Order code (Order example)
Type
Order code TA 45
(2-pole rocker-switch without
accessories)
Wiring
0
Without
1
With
2
Special (on request)
0
0
6145
.
A B T W F 1 5 0 C 0
see table 1
Please note that Schurter will establish an internal part number for logistical use in addition to the order code.
The format of this internal part number is, for example 6145.0031.001
Without line filter
Without line filter
.
0 0 1
72
0
80
±0,1
80
+0,1
www.schurter.com
71
POWER ENTRY MODULES /
GERÄTESTECKER-KOMBIELEMENTE
Table 1 Selection for type TA45
Order example
• Line switch
• 2-pole, rocker actuated
• Quick connect terminal
Other types on request
Diagram
Thermal overload protection
without /
ohne
P2
P1
6145
W
F
150
C0
ABT
5
3
P1
a
with
1-pole
P2
P1
with
2-pole
P2
P1
Without illumination
With illumination /
Mit Beleuchtung
220…240 V
110…120 V
6
5
6
3
4
3
ABC
A02
A04
ABT
A12
A14
ABD
A32
A34
}
Colours
Switch front /
Rocker
W
B
6
black
/ schwarz
black
/ schwarz
black
/ schwarz
white
/ weiss
black
/ schwarz
–
–
–
orange transp.
Rocker legend
Surface /
Illustration / Colour of print
Surface /
Illustration / Colour of print
O
F
H
K
L
embossed
printed
/ bedruckt
printed
/ bedruckt
printed
/ bedruckt
M
white
black
white
P
R
printed
/ bedruckt
printed
/ bedruckt
printed
/ bedruckt
O
l
l
black
white
black
OFF OFF
ON
I
I
O
O
ON
l
Position of the rocker legend
e.g F
O
Rated current
:
• Without thermal overload protection: code C00
}
I
n
= 16 A
• With thermal overload protection: rated current In (A)
In
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1,0
1,1
1,2
Code
J01
J02
J03
J04
J05
J06
J07
J08
J09
J10
J11
J12
In
1,3
1,4
1,5
1,6
1,7
1,8
1,9
2,0
2,1
2,2
2,3
2,5
Code
J13
J14
J15
J16
J17
J18
J19
J20
J21
J22
J23
J25
In
2,8
3,0
3,5
4,0
4,5
5,0
6,0
6,5
7,0
7,5
8,0
9,0
Code
J28
030
035
040
045
050
060
065
070
075
080
090
In
10,0
11,0
12,0
13,0
14,0
15,0
Code
100
110
120
130
140
150
Without release: code C0
Undervoltage release
P2
U<
P1
P2
b
U<
P1
P2
ba
U<
P1
Remote trip release
P2
c P1
Rated voltage Un
U
E
Z
A
Code
2
3
4
240 V AC
230 V AC
120 V AC
•
•
•
•
•
•
•
•
•
•
•
•
72
www.schurter.com