D2E146-HT67-01
AC centrifugal fan
forward curved, dual inlet
with housing (flange)
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
info1@de.ebmpapst.com
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type
Motor
Phase
Nominal voltage
Frequency
Type of data definition
Valid for approval / standard
Speed
Power input
Current draw
Motor capacitor
Capacitor voltage
Capacitor standard
Min. back pressure
Max. ambient temperature
Starting current
Pa
°C
A
min
-1
W
A
µF
VDB
VAC
Hz
D2E146-HT67-01
M2E068-EC
1~
230
50
ml
CE
1850
355
1.55
8
450
P2 (CE)
0
55
1.8
1~
230
60
ml
CE
2100
400
1.75
8
450
P2 (CE)
200
50
1.9
ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unit
Subject to alterations
Data according to ErP directive
Actual
Request 2013
Request 2015
Installation category
Efficiency category
Variable speed drive
Specific ratio
*
*
A
Static
No
1.00
Overall efficiency η
es
Efficiency grade N
Power input P
e
Air flow q
v
Pressure increase p
fs
Speed n
kW
m³/h
Pa
min
-1
29
39
0.26
700
400
2435
27
37
34
44
Specific ratio = 1 + p
fs
/ 100 000 Pa
Data established at point of optimum efficiency
Item no. 10892-5-9980 · Revision 70969 · Release 2010-07-07 · Page 1 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D2E146-HT67-01
AC centrifugal fan
forward curved, dual inlet
with housing (flange)
Technical features
Mass
Size
Surface of rotor
Material of terminal box
Material of impeller
Housing material
Motor suspension
Direction of rotation
Type of protection
Insulation class
Humidity class
Max. permissible ambient motor
temp. (transp./ storage)
Min. permissible ambient motor
temp. (transp./storage)
Mounting position
Condensate discharge holes
Operation mode
Motor bearing
Speed steps
Touch current acc. IEC 60990
(measuring network Fig. 4, TN
system)
Electrical leads
Motor protection
Cable exit
Protection class
Product conforming to standard
Approval
3.44 kg
146 mm
Partially cast in aluminium
PP plastic, black
Sheet steel, hot-galvanised
PP plastic, black
Motor anti-vibration mounted on both sides
Counter-clockwise, seen on rotor
IP 20
"F"
F0
+ 80 °C
- 40 °C
Shaft horizontal or rotor on bottom; rotor on top on request
None, open rotor
S1
Calotte bearing
4
< 0.75 mA
With plug; Via terminal box, integrated capacitor connected via terminal box
Thermal overload protector (TOP) wired internally
Variable
I (if protective earth is connected by customer)
EN 60335-1; CE
GOST; CCC; VDE
Item no. 10892-5-9980 · Revision 70969 · Release 2010-07-07 · Page 2 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D2E146-HT67-01
AC centrifugal fan
forward curved, dual inlet
with housing (flange)
Product drawing
1
1.1
1.2
1.3
1.4
1.5
1.6
2
AMP Universal Mate-N-Lok coded plug system; connector shell: AMP 926 682-3; 6x plug pin: AMP 926 886-1
L = step 1
L = step 2
L = step 3
L = step 4
N
Protective earth
4 x sheet metal nut for thread EN ISO 1478-ST4.8 (min. screw length 14.5 mm plus thickness of mounting material)
Item no. 10892-5-9980 · Revision 70969 · Release 2010-07-07 · Page 3 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D2E146-HT67-01
AC centrifugal fan
forward curved, dual inlet
with housing (flange)
Connection screen
When changing speeds, switch must break the circuit
1
4
7
Step 1 (min.)
Step 4 (max.)
Speed increase
2
5
Step 2
N
3
6
Step 3
PE protective earth
Item no. 10892-5-9980 · Revision 70969 · Release 2010-07-07 · Page 4 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
D2E146-HT67-01
AC centrifugal fan
forward curved, dual inlet
with housing (flange)
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
0
500
480
460
440
420
400
380
360
340
320
300
280
p s[Pa]
f
100
200
300
qv[cfm]
400
500
600
700
800
2
4
8
3
12
7
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
p fs_E[IN H2O]
Measurement: LU-45713
Measurement: LU-45715
Measurement: LU-45717
Measurement: LU-45719
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
260
240
220
200
180
160
140
120
100
80
60
40
20
0
16
11
2
1
0,9
0,8
0,7
15
6
0,6
0,5
10
14
0
0,4
0,3
0,2
Step 2
Step 4
13
0
100
200
300
400
500
600
0
0,1
1.200
1.300
0
1.400
9
700
qv[m^3/h]
800
5
900
1.000
1
1.100
Measured values
Stage
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
4
4
4
4
3
3
3
3
2
2
2
2
1
1
1
1
U
V
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
f
Hz
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
n
min
-1
1850
2150
2435
2610
1550
1850
2235
2515
1195
1455
1890
2315
875
1055
1420
1965
P
e
W
355
318
268
227
286
261
222
179
233
222
196
158
195
191
179
151
I
A
1.55
1.38
1.16
0.99
1.27
1.18
1.03
0.87
1.06
1.02
0.94
0.81
0.89
0.88
0.84
0.76
qv
m
3
/h
1060
930
700
450
855
790
640
430
640
610
540
395
460
440
400
335
p
fs
Pa
0
200
400
460
0
145
337
418
0
88
239
360
0
45
132
255
U = Supply voltage · f = Frequency · n = Speed · P
e
= Power input · I = Current draw · qv = Air flow · p
fs
= Pressure increase
Item no. 10892-5-9980 · Revision 70969 · Release 2010-07-07 · Page 5 / 6
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com