CAR4000 Series
4000 Watt 24 / 48V Front End
Features:
∎
∎
∎
∎
∎
∎
∎
Hot-swap N+1 Redundancy
Single phase or Three phase Input
Power Factor Correction
Over Voltage, Over Current and Thermal Protection
Visual LED Indicators
19” 3U High / 3-Bay Power Shelf
International Safety Approvals
FEATURES
No minimum load requirements
Modular design
Single phase or three phase inputs
Constant current characteristics
SPECIFICATIONS
Input Voltage Range
Input Current
Inrush Current
Input Fuse
Power Factor
Efficiency
Output Voltage & Current
Adjust Range (Trim Pot)
Over Voltage Protection
OVP Protection Type
Standby Voltage
Line Regulation
Load Regulation
Output Ripple & Noise
Transient Response
Start-up Time
Hold-up Time
Overshoot / Undershoot
Temperature Coefficient
Remote ON/OFF
Power Fail Signal
Over Current Protection
Over Temperature Protection
MTBF
Output Power Good
LED Indicators
Operating Temperature
Cooling
EMI/EMC
Dimensions
Weight
Safety Approvals
rev 100506
Lineage Power
3000 Skyline Dr.
Mesquite, TX 75149
Phone: (972) 284-2000
BENEFITS
Eliminates the need for preload on system backplace
Easy insertion and extraction during hot swap
One stop shopping, breadth of line
Ideal for Network Bus Applications
CAR4010K1
CAR4010L1
Single Phase Input / 180-264 VAC / 47-63 Hz
25.5Amax
50Amax
Single Fuse 30A 3AG
0.99
90% Typical @ 230 VAC
+24 VDC @ 167A
+48 VDC @ 83.3A
21.6~26.4
43.2~52.8
29.5~30.5 VDC
58.5~59.5 VDC
Recycle AC Input to Reset
KEY MARKET SEGMENTS & APPLICATIONS
∎
Distributed Power
∎
Mid-end servers
∎
Network Storage
∎
Storage Area Networks
∎
Blade Servers
∎
Network Equipment
∎
Test Equipment
CAR4030K1
CAR4030L1
Three Phase Input / 180-264 VAC / 47-63 Hz
15A per phase max.
50A max (per phase)
Single Fuse per Phase 20A 3AG
0.95
90% Typical @ 230 VAC
+24 VDC @ 167A
+48 VDC @ 83.3A
21.6~26.4
43.2~52.8
29.5~30.5 VDC
58.5~59.5 VDC
5VSB @ 500mA
0.5% using remote sense (5% on Stand-by Voltage)
0.5% using remote sense (5% on Stand-by Voltage)
<1% (pk-pk)
3% max deviation 0.50ms recovery time for a 25% load change
2 seconds
>20ms at low line
1% at turn ON/OFF
0.02% per °C
Logic 1 (TTL High) or open enables unit (ON), Logic 0 (TTL Low) or short shuts unit down (OFF)
Signal goes low (TTL Low) 2ms before loss output regulation
110-140% V1, 5VSB < 2.5A. Automatic recovery.
Automatic shutdown with auto recovery. Thermal shutdown point @ 95°C
300,000 hrs per Bellcore standard
TTL High = Power Good, TTL Low = Output out of limits
DC Good: Green LED; Temperature OK: Green LED and AC Good: Amber LED
0°C to 50°C at rated output power. Supply derates linearly from 50°C to 65°C at 2.2% per °C
Self contained ball bearing fan
Meets EN61000-3-2, -3 CISPR22 and FCC Part 15 Class A, Bellcore GR-1089-CORE
14.12 x 5.00 x 5.00” / 333.2 x 127 x 127mm (handle extends additional 1.00” / 25.4mm from faceplate)
11.5 pounds / 5.23 kg
UL1950, CSA 22.2 No. 650, TUV EN0950 & CE Mark
www.lineagepower.com/oem
Lineage Power
2841 Dow Avenue
Tustin, CA 92780 USA
Phone: (714) 544-6665
Lineage Power (China)
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910
CAR4000 Series
4000 Watt 24 / 48V Front End
OUTLINE DRAWING:
14.12
Side & Bottom Views are of
Bus Bar Output Connector Versions
5.00
SIDE VIEW
1.04
1 .02
1.00
15.12
AIRFLOW
5.00
BOTTOM VIEW
3.20
Latch
3 2 1
LEDs
0.16
8.00
1.79
0.25
0.822
REAR PANEL CONNECTIONS:
Single Phase Input with Bus Bar
V1 Rtn
1.25
1.20
V1
1.56
CAR4010x1
Three Phase Input with Bus Bar
0.641
V1 RTN
1.25
V1
1.56
CAR4030x1
Single Phase Input with Positronic
CAR4010x1H
Three Phase Input with Positronic
CAR4030x1H
3.00
0.84
0.65
2.44
2.99
0.59
0.98
3.095
15-PIN D-SUB CONNECTOR1 1
Positronic Output Connector
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
5 VSB
5VSB RTN
MODULE PRESENT
POWER GOOD
ON/OFF
I SHARE
MOD-ENABLE
OVP TEST POINT
AC FAIL
V PROGRAM
+ REMOTE SENSE
CURRENT MONITOR
TEMPERATURE OK
- REMOTE SENSE
NO CONNECTION
THREE PHASE AC INPUT4 4
1
2
3
4
LINE 1
LINE 2
LINE 3
GROUND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
V1
V1
V1
V1
V1 RETURN
V1 RETURN
V1 RETURN
V1 RETURN
V1
5VSB RTN
MODULE PRESENT
MODULE ENABLE
CURRENT SHARE
ON/OFF
OVP
V1 RETURN
5VSB
POWER GOOD
AC FAIL
MARGIN 1
+ SENSE
TEMP OK
MARGIN 2
- SENSE
Lineage Power
2841 Dow Avenue
Tustin, CA 92780 USA
Phone: (714) 544-6665
SINGLE PHASE AC INPUT 3
1
2
3
4
5
6
GROUND
LINE
NEUTRAL
GROUND
LINE
NEUTRAL
CAR 40 xx xx x xx - 1A
CAR 40 xx xx x x
Rev.
xx - 1A
x
Series
Blank=Non-Compliant
40=4000W
Series
Rev.
Y0=5 of 6 Compliant
Power
Blank=Non-Compliant
40=4000W
Z0=6 of 6 Compliant
10 =
Y0=5
Power
1Ø
RoHS Compliance
of 6 Compliant
30 = 3Ø
Z0=6 of 6 Compliant
10 = 1Ø
Blank = Bus Bar
Input Phase
RoHS Compliance
30 = 3Ø
K1=+24V H = Positornic
Blank = Bus Bar
Input Phase
L1= +48V
Output Connector
Positronic
(front-end only)
H=
K1=24V
Output V
Output Connector
L1=48V
Output V
Blank = Positive
Blank = Front End N = Negative
T = Rectifier
Polarity
Type
PART NUMBER DEFINITION GUIDE
MATING CONNECTORS
1) AMP 205205-2 Housing with
205090-1 Pins
2) Positronics PLC24F4BN0A1/AA
Housing with FC114N2 pins
3) Positronics PLB06F000 Housing
with FC114N2 pins
4) Positronics PLA04F8000 Housing
with FC114N2 pins
Output Bus Bars Mate with Elcon
Part Number 538-17-00100
Examples:
CAR4010L1-Z01A: 4000W / +48V Front End / Single Phase
AC Input / 6 of 6 RoHS Compliant
CAR4030L1H-Z01A: 4000W / +48V Front End / 3-Phase AC
Input / Positronic Connector / 6 of 6 RoHS Compliant
www.lineagepower.com/oem
rev 100506
Lineage Power
3000 Skyline Dr.
Mesquite, TX 75149
Phone: (972) 284-2000
Lineage Power (China)
1353 Chenqiao Road, Shanghai Sengpu Industrial Park
Shanghai, 201401 China
Phone: 021 6710 8910