Multifunction Counter
H7BX
DIN 72×72 mm Multifunction Counter with a Bright,
Easy-to-view, Negative Transmissive LCD.
•
Highly visible display with backlit transmissive LCD.
•
Selectable display color (red/green) enables checking output status at a
distance.
•
Easy operation with a key for each digit.
•
Perform all basic settings with a DIP switch.
•
Provides a total and preset counter, batch counter, dual counter, and
tachometer (See note.).
•
Wide range of inputs accepted for NPN/PNP inputs (multi-inputs) and 2-
wire DC sensors.
•
Complies with UL, CSA, and CE marking.
•
Degree of protection: IP54 equivalent (front section only).
Be sure to read
Safety Precautions
on page 25.
Note:
The functions that can be selected depend on the model.
Ordering Information
■
List of Models
External power supply
12 VDC
Output type
Contact and
NPN transistor output
Supply voltage
100 to 240 VAC
24 VAC/12 to 24 VDC
1-stage
H7BX-A
H7BX-AD1
2-stage
H7BX-AW
H7BX-AWD1
■
Accessories (Order Separately)
Name
Soft Cover
Hard Cover
Terminal Cover (See note.)
Note:
Supplied with the H7BX.
Model
Y92A-72F1
Y92A-72
Y92A-72T
Multifunction Counter
H7BX
1
Specifications
■
Ratings
Item
Type
Supported configurations
Power supply voltage
(See note 2.)
Ratings
Model
Preset counter
1-stage preset counter, total and preset counter (See note
1.) (selectable)
•
100 to 240 VAC (50/60 Hz)
•
24 VAC (50/60 Hz)/12 to 24 VDC (ripple 20% max.)
H7BX-A/AW: 9.6 VA max. (100 to 240 VAC)
H7BX-AD1/AWD1: 8 VA max. (24 VAC), 5.3 W max. (12 to 24 VDC)
Flush mounting
Screw terminals
IP54 (front section only)
CP1, CP2, reset 1, reset 2, key protection
30 Hz or 5 kHz (selectable, ON/OFF ratio 1:1), setting for both CP1 and CP2
Increment, decrement, command (UP/DOWN A), individual (UP/DOWN B), quadrature (UP/DOWN C)
N, F, C, R, K-1, P, Q, A, K-2, D, L
0.01 to 99.99 s
External reset (minimum reset input signal width: 1 ms or 20 ms selectable), manual reset, and automatic reset (internal
according to C, R, P, and Q mode operation)
---
---
---
---
---
---
---
---
Yes (0.001 to 99.999)
Yes (rightmost 3 digits)
290 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Response speed: Approx. 1 s
No-voltage NPN input (fixed)
Short-circuit (ON) impedance: 1 kΩ max. (Leakage current at 0
Ω:
Approx. 12 mA)
Short-circuit (ON) residual voltage: 3 V max.
Open (OFF) impedance: 100 kΩ min.
No-voltage NPN input or voltage PNP input (selectable)
No-voltage input
Short-circuit (ON) impedance: 1 kΩ max. (Leakage current at 0
Ω:
Approx. 12 mA)
Short-circuit (ON) residual voltage: 3 V max.
Open (OFF) impedance: 100 kΩ min.
Voltage input
High level: 4.5 to 30 VDC
Low level: 0 to 2 VDC
Input resistance: Approx. 4.7 kΩ
12 VDC (±10%), 100 mA (For details, refer to
External Power Supply
on page 26.)
Contact output: 3 A at 250 VDC/30 VDC, resistive load (cosφ = 1)
Minimum applied load: 10 mA at 5 VDC (Failure level: P, reference value)
Transistor output: 100 mA max. at 30 VDC max.
Residual voltage: 1.5 VDC max. (approx. 1 V)
Leakage current: 0.1 mA max.
Backlit 7-segment negative transmissive LCD
Character Heights
PV: 13.5 mm (red/green)
SV: 9 mm (green)
6 digits
−99,999
to 999,999 (5 digits negative and 6 digits positive)
6 digits
Counter:
−99,999
to 999,999 (5 digits negative and 6 digits
positive)
Tachometer: 0 to 999,999 (6 digits)
Periodic measurement (Sampling period: 200 ms)
30 Hz or 10 kHz (selectable)
30 Hz: 0.01 to 30.00 Hz
10 kHz: 0.01 Hz to 10 kHz
±0.1%
FS
±1
digit max. (at 23
±5°C)
Upper and lower limits, area, upper limit, lower limit
0.1 to 99.9 s
0.0 to 99.9 s
OFF/2/4/8 times
N, F, C, R, K-1, P, Q, A, K-2, D, L, H
H7BX-A/AD1
H7BX-AW/AWD1
Preset counter/tachometer
1-stage preset counter, 2-stage preset counter, total and
preset counter (See note 1.), batch counter, dual counter,
tachometer (selectable)
Operating voltage range
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Power consumption
Mounting method
External connections
Degree of protection
Input signals
Max. counting speed
Input modes
Counter
Output modes
One-shot output time
Reset input
Pulse measurement
method
Max. counting speed
Measuring ranges
Tachom-
eter
Measuring accuracy
Output modes
Auto-zero time
Startup time
Average processing
Prescaling function
Decimal point adjustment
Sensor waiting time
Key protection input
Input method
(except key protection input)
External power supply
Control output
Display (See note 3.)
Digits
Memory backup
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Case color
Accessories
EEPROM (Overwrites: 100,000 min.), Data storage: 10 years min.
−10
to 55°C (with no icing)
−25
to 65°C (with no icing)
25 to 85°C (with no condensation)
Black (N1.5)
Two flush-mounting adapters, terminal cover
Two flush-mounting adapters, terminal cover, DIP switch
setting stickers
Note 1.
The total and preset counter functions as a 1-stage preset counter and total counter.
2.
Do not use an inverter output for the power supply.
3.
Displayed only when the power is ON. Not displayed when the power is OFF.
2
Multifunction Counter
H7BX
■
Characteristics
Insulation resis-
100 MΩ min. (at 500 VDC) between current-carrying terminal and exposed non-
tance
current-carrying metal parts, and between non-continuous contacts
Between current-carrying metal parts and non-current-carrying metal parts:
2,000 VAC, 50/60 Hz for 1 min
Between power supply and input circuit: 2,000 VAC, 50/60 Hz for 1 min (for models
other than the H7BX-A@D1)
1,000 VAC, 50/60 Hz for 1 min (H7BX-A@D1)
Between control output, power supply, and input circuit: 2,000 VAC, 50/60 Hz for 1 min
Between non-continuous contacts: 1,000 VAC, 50/60 Hz for 1 min
Between power terminals: 3.0 kV (1.0 kV for 24 VAC/12 to 24 VDC models)
Between current-carrying terminal and exposed non-current-carrying metal parts:
4.5 kV (1.5 kV for 24 VAC/12 to 24 VDC models)
Between power terminals:
±1.5
kV
Between input terminals:
±600
V
Square-wave noise by noise simulator (Pulse width: 100 ns/1
µs,
1-ns rise)
Malfunction: 8 kV
Destruction: 15 kV
Destruction: 10 to 55 Hz, 0.75-mm single amplitude for 4 cycles each in 3 directions (8
min/cycle)
Malfunction: 10 to 55 Hz, 0.50-mm single amplitude for 4 cycles each in 3 directions (8
min/cycle)
Destruction: 294 m/s
2
3 times each in 6 directions
Malfunction: 98 m/s
2
3 times each in 6 directions
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min. (3 A at 250 VAC/30 VDC, resistive load) (See
note.)
Approx. 250 g
●
Electrical Life Expectancy
(Reference Values)
Resistive Load
No. of operations (×10
3
)
1,000
700
500
Dielectric
strength
300
30 VDC (cosφ=1)
Impulse with-
stand voltage
Noise immunity
100
70
50
0
250 VAC (cosφ=1)
Static immunity
1
2
3
4
Vibration resis-
tance
Shock resis-
tance
Life expectancy
Weight
Load current (A)
Inductive Load
No. of operations (×10
3
)
1,000
700
500
300
30 VDC (L/R=7 ms)
Note:
Check the electrical life expectancy curve.
■
Applicable Standards
Approved
cURus: UL 508, CSA C22.2 No. 14
EN 61010-1 (IEC 61010-1): Pollution degree 2/overvoltage category II;
safety
standards
EN 61326; VDE 0106 Part 100
EN 61326
EN 55011 Group 1 class A
EN 55011 Group 1 class A
EN 61326
EN 61000-4-2: 4 kV contact discharge;
8 kV air discharge
Immunity RF-interference:
EN 61000-4-3:10 V/m (Amplitude-modulated,
80 MHz to 1 GHz);
10 V/m (Pulse-modulated,
900 MHz
±5
MHz)
Immunity Conducted Disturbance: EN 61000-4-6: 3 V (0.15 to 80 MHz)
Immunity Burst:
EN 61000-4-4: 2 kV power-line;
1 kV I/O signal-line
Immunity Surge:
EN 61000-4-5: 1 kV line to lines (power and output lines
(relay outputs));
2 kV line to ground (power and output lines
(relay outputs))
Immunity Voltage Dip/Interruption: EN 61000-4-11: 0.5 cycle, 100% (rated voltage)
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
100
70
50
0
250 VAC (cosφ=0.4)
1
2
3
4
Load current (A)
A current of 0.15 A max. can be switched at
125 VDC (cosφ = 1) and current of 0.1 A max. can
be switched with L/R = 7 m/s. In both cases, a life of
100,000 operations can be expected.
EMC
Multifunction Counter
H7BX
3
■
I/O Functions
●
Using as a Counter (See note 1.)
(1) All Modes Except for Dual Counter Mode
•
Reads count signals.
•
Increment, decrement, up/down (command, individual, or quadrature) inputs
can be used.
(2) Dual Counter Mode
•
Reads CP1 count signals on CP1 input and CP2 count signals on CP2 input.
•
Increment signals can be used.
(1) All Modes Except for Dual Counter Mode
•
Resets present value and outputs (OUT2 when using the batch counter). (See
note 2.)
•
Counting cannot be performed while resetting or when reset 1 input is ON.
•
The reset indicator is lit while the reset input is ON.
(2) Dual Counter Mode
•
Resets the CP1 present value to 0.
•
Counting the CP1 input cannot be performed while the reset 1 input is ON.
•
The reset indicator is lit while the reset 1 input is ON.
The reset operation depends on the selected function. (See note 3.)
When the corresponding set value is reached, signals are output according to the
designated output mode.
●
Using as a Tachometer
CP1,
CP2
Inputs
Reset 1,
Reset 2
Reads counting signals.
(CP2 input is not
available.)
•
Holds the measurement
value and outputs.
(Reset 2 input is not
available.)
•
The reset indicator is lit
during hold.
CP1, CP2
Inputs
Reset or
Reset 1
Outputs signals according
to the specified output
Outputs OUT1, 2
mode when a set value is
reached.
Total Reset
or Reset 2
Outputs OUT1, 2
●
Using as a Counter or
Tachometer
Key protection
input
•
Prohibits using the keys
on the front panel.
•
Set the key protection
level in function selection
mode.
Note 1.
Refer to pages 14 to 17 for information on the operation of input and output functions.
2.
In increment mode or increment/decrement mode, the present value returns to 0; in decrement
mode, the present value returns to the set value with 1-stage models, and returns to set value 2 with
2-stage models.
3.
The reset indicator will not be lit when the total reset or reset 2 input is ON.
Function
Reset operation
•
Resets the total count value.
•
Holds the total count value at 0 while the total reset input is ON.
•
Resets the batch count value and batch output (OUT1).
•
Holds the batch count value at 0 while the reset 2 input is ON.
•
Resets the CP2 present value.
•
Counting for CP2 input is disabled while the reset 2 input is ON.
Note:
For details, refer to page 24.
1-stage/2-stage preset counter
Does not operate (Not used).
Total and preset counter
Batch counter
Dual counter
4
Multifunction Counter
H7BX
Connections
■
Terminal Arrangement
Confirm that the power supply meets specifications before using the H7BX.
H7BX-A
Output COM
Reset 1
Reset 2
CP2
CP1
12 VDC
H7BX-AW
Output COM
17
18
7
Unused.
Output COM
17
18
7
Reset 1
Reset 2
5
Reset 2
5
CP2
CP1
12 VDC
0V
8
9
0V
8
9
10 11 12 13 14
10 11 12 13 14
(−)
Unused. 15
External power supply
(+)
17 Unused.
Unused. 15
(−)
External power supply
(+)
OUT1
OUT2
Key
protection
OUT
16
OUT
1
2
3
4
5
Unused.
6
Unused.
7
Unused.
18
Key
protection
16
OUT2
1
2
3
4
OUT1
6
H7BX-AD1
Output COM
Reset 1
Reset 2
CP2
CP1
12 VDC
H7BX-AWD1
Reset 1
CP2
CP1
12 VDC
0V
8
9
0V
8
9
10 11 12 13 14
10 11 12 13 14
(−)
Unused. 15
External power supply
(+)
17 Unused.
Unused. 15
(−)
External power supply
(+)
OUT1
OUT2
Key
protection
OUT
16
OUT
1
2
3
4
5
Unused.
6
Unused.
7
Unused.
18
Key
protection
16
OUT2
1
2
3
4
OUT1
6
Unused.
(−)
(+)
(−)
(+)
Note:
Do not use the unused terminals for relay connections.
■
Block Diagram
(Basic insulation)
Output circuit
(Basic insulation)
Display circuit
Input circuit
Internal control
circuit
Key switch
circuit
Power supply
circuit
●
CP1, CP2, Reset/Reset 1, and Total Reset/Reset 2 Input
+14 V
1 kΩ
IN
Internal
circuit
■
Input Circuits
Note:
The circuit shown above is for
no-voltage input (NPN input).
Multifunction Counter
H7BX
5