Circuit Protection
Circuit Break ers
Thermal Magnetic Type
CB4201-10
CB4202-10
Single Pole
Ordering Data
Internal
Resistance per
Pole (ohms)
131.00
40.00
19.30
10.40
7.10
4.30
3.58
2.50
1.67
1.22
0.61
0.55
0.38
0.24
0.19
0.16
0.09
0.09
0.061
0.07
0.041
0.04
0.034
0.02
0.02
<0.02
<0.02
<0.02
<0.02
<0.02
<0.02
<0.02
Current
Ratings
(amps)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.0
1.2
1.5
1.8
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
Double Pole
Type:
Single Pole - CB4201-10
Part No.*
TS 32
9104173200
9104183200
9129813200
9124093200
9101003200
9124113200
9129563200
9101103200
9101203200
9101303200
9101403200
9124143200
9101503200
9101603200
9101703200
9124163200
9104353200
9101803200
9103813200
9104153200
9103003200
9104613200
9101903200
9107843200
9107853200
9102003200
9124213200
Part No.*
TS 35
9104173500
9104183500
9129813500
9124093500
9101003500
9124113500
9129563500
9101103500
9101203500
9101303500
9101403500
9124143500
9101503500
9101603500
9101703500
9124163500
9104353500
9124173500
9101803500
9107833500
9103813500
9120043500
9104153500
9103003500
9104613500
9101903500
9124183500
9107843500
9124193500
9107853500
9102003500
9124213500
Current
Ratings
(amps)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.0
1.2
1.5
1.8
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
Type:
Double Pole - CB4202-10
Part No.*
TS 32
9120353200
9124243200
9124263200
9124273200
9129583200
9124283200
9124293200
9129593200
9129613200
9129623200
9129633200
9124333200
9129643200
9129653200
9129663200
9124343200
9129713200
9129673200
9124363200
9124373200
9124383200
9124393200
9104673200
9124423200
9129683200
9124433200
9124443200
9124453200
9124463200
9129693200
9124473200
Part No.*
TS 35
9120353500
9124243500
9124263500
9124273500
9129583500
9124283500
9124293500
9129593500
9129613500
9129623500
9129633500
9124333500
9129643500
9129653500
9129663500
9124343500
9129713500
9129673500
9124373500
9124393500
9104673500
9124423500
9129683500
9124443500
9124463500
9129693500
9124473500
Circuit Break er – Trip Curv es
Thermal Magnetic Type
Typical time/current characteristics at 23ºC
4200 Series
* Ordering Options - Example
To order CB4201-10 Single Pole Circuit Breaker,
Part No. 9101203501
•
•
•
•
Current Rating of 1.0 amps
Internal Resistance per Pole of 1.67 ohms
For TS 35
Without Trip Button
M1+
10,000
0.05 to 7.5 A
10,000
M1+
8 to 16 A
–30°C
+23°C
+55°C
–30°C
+23°C
+55°C
1,000
1,000
9 1 0 1 2 0 3 5 0 1
"00" – Standard
Circuit Breaker
"01" – Without Trip Button†
100
100
Trip time in seconds
Trip time in seconds
10
10
1
1
0.1
0.1
"32" – TS 32 DIN-Rail Mountable
"35" – TS 35 DIN-Rail Mountable
Base Part No. (Determines 1 or 2 pole unit)
0.01
0.01
0.001
0.8 1
2
3
4
6
8 10
20 30
50 70 100
0.001
0.8 1
2
3
4
6
8 10
20 30
50 70 100
… times rated current
… times rated current
†T o manually trip breaker, a plastic or wooden
dowel (0.12 inch diameter) will be needed.
126
CB4201-10
Single Pole
Internal
Wiring
Diagram
Dimensions in mm
CB4202-10
Double Pole
Internal
Wiring
Diagram
Dimensions in mm
Technical Data
Rated voltage & current†
UL
CSA
VDE
Creepage resistance
Dielectric strength
Insulation resistance
Interrupting capacity
(VDE 0660, Part 101, P-2)
Voltage Ratings
AC 250 V, DC 80 V, 50/60 Hz
AC 250 V, DC 80 V, 50/60 Hz
AC 250 V, DC 65 V, 50/60 Hz
PTI 600 to IEC 112
4,000 VAC; IEC 664 & 664 A
Current Ratings
0.05…16 A
0.05…16 A
0.05…16 A
Interrupting capacity; 4201-10
(UL 1077/EN 60934 PC1)
Typical life at 2 x rated current
Shock
Torque
Vibration
Temperature range
Corrosion
Humidity
Weight
Wire size (UL)
Accessories
Jumpers
Daisy Chain 50*
Straight CQB**
Nm (lb. in.)
Angled CQB**
Adaptor foot
Marking Tags
1 2 3 4 5 6
Special print only
Consecutive horizontal
Consecutive vertical
BDC 50
CQB 2
CQB 3
CQB 4
CQB 10
CQB 2
CQB 3
CQB 4
CQB 10
AF/TS 32
WS 8/5 MC
DEK 5/5
DEK 5/5
9970290000
9970560000
9970570000
9970580000
9970590000
9970600000
9970610000
9970620000
9970630000
9102100000
1640750000***
0473460001
0473560001
Note: Part numbers are shown
for a single card of pre-printed
tags numbered 1-50.
†Note: Resistive and inductive loads
(0.05 - 16 A)
*BDC will accommodate 20 A per pin,
20 A total
**CQB will accommodate 18 A per pin,
18 A total; dedicated to
4201 Series
***Please specify horiz ontal or vertical
print when ordering. Standard
quantity = 144 tags per card.
127
RAIL MOUNTED TERMINAL
BLOCKS: SAK-SERIES
> 100 M (DC 500 V)
4201-10
maximum capacity
0.05…0.8 A
self-limiting
1…2 A
200 A
2.5…16 A
400 A
Rated current
Rated voltage
maximum capacity
0.05…4.5 A
AC 250 V
200 A
5…8 A
AC 250 V
1000 A
9…15 A
AC 125 V
1000 A
0.05…15 A
DC 65 V
200 A
5,000 operations
25 g (11 ms) to IEC 68-2-27, Test Ea
0.8 (7.1)
5 g (57 to 500 Hz / ±0.38 mm, 10 to 57 Hz) to IEC 68-2-6, Test Fc
-30°C…+55°C (-22°F…+131°F)
96 hours at 5% salt spray, to IEC 68-2-11, Test Ka
240 hours at 95% RH, to IEC 68-2-3, Test Ca
Approximately 60 g per pole
# 20…8 AWG
solid
# 20…10 AWG
standard
Type