Solid-state Twin Timers
H3CR-F
CSM_H3CR-F_DS_E_1_2
DIN 48
×
48-mm Twin Timers
• Wide power supply ranges of 100 to 240 VAC and 48 to
125 VDC respectively.
• ON- and OFF-times can be set independently and so
combinations of long ON- or OFF-time and short OFF- or ON-
time settings are possible.
• Fourteen time ranges from 0.05 s to 30 h or from 1.2 s to 300 h
depending on the model to be used.
• Models with a flicker ON start or flicker OFF start are available.
• Easy sequence checks through instantaneous outputs for a
zero set value at any time range.
• Length, when panel-mounted with a Socket, of 80 mm or less.
• 11-pin and 8-pin models are available.
Model Number Structure
■
Model Number Legend
H3CR - F
@ @
-
@ @
1 2
3
4
5
1. Classification
F:
Twin timers
2. Configuration
None:
11-pin socket
8:
8-pin
socket
3. Twin Timer Mode
None:
Flicker OFF start
N:
Flicker ON start
4. Time Range
None:
0.05 s to 30 h models
300: 1.2 s to 300 h models
5. Supply Voltage
100-240AC: 100 to 240
VAC
24AC/DC: 24
VAC/VDC
12DC:
12
VDC
48-125DC: 48 to 125
VDC
Ordering Information
■
List of Models
Operating
modes
Flicker OFF
start
Supply
voltage
100 to 240 VAC
24 VAC/DC
12 VDC
48 to 125 VDC
Flicker ON start 100 to 240 VAC
24 VAC/DC
12 VDC
48 to 125 VDC
0.05 s to 30 h models
11-pin models
H3CR-F 100-240AC
H3CR-F 24AC/DC
H3CR-F 12DC
H3CR-F 48-125DC
H3CR-FN 100-240AC
H3CR-FN 24AC/DC
H3CR-FN 12DC
H3CR-FN 48-125DC
8-pin models
H3CR-F8 100-240AC
H3CR-F8 24AC/DC
H3CR-F8 12DC
H3CR-F8 48-125DC
H3CR-F8N 100-240AC
H3CR-F8N 24AC/DC
H3CR-F8N 12DC
H3CR-F8N 48-125DC
1.2 s to 300 h models
11-pin models
H3CR-F-300 100-240AC
H3CR-F-300 24AC/DC
H3CR-F-300 12DC
H3CR-F-300 48-125DC
H3CR-FN-300 100-240AC
H3CR-FN-300 24AC/DC
H3CR-FN-300 12DC
H3CR-FN-300 48-125DC
8-pin models
H3CR-F8-300 100-240AC
H3CR-F8-300 24AC/DC
H3CR-F8-300 12DC
H3CR-F8-300 48-125DC
H3CR-F8N-300 100-240AC
H3CR-F8N-300 24AC/DC
H3CR-F8N-300 12DC
H3CR-F8N-300 48-125DC
Note:
Specify both the model number and supply voltage when ordering.
Example: H3CR-F 100-240AC
Supply voltage
1
H3CR-F
■
Accessories (Order Separately)
Name/specifications
Flush Mounting Adapter
Y92F-30
Y92F-73
Y92F-74
Mounting Track
50 cm (l)
×
7.3 mm (t)
1 m (l)
×
7.3 mm (t)
1 m (l)
×
16 mm (t)
End Plate
Spacer
Protective Cover
Track Mounting/
Front Connecting Socket
8-pin
8-pin, finger safe type
11-pin
11-pin, finger safe type
Back Connecting Socket
8-pin
8-pin, finger safe type
11-pin
11-pin, finger safe type
Hold-down Clip (See note 2)
For PL08 and PL11 Sockets
For PF085A Socket
PFP-50N
PFP-100N
PFP-100N2
PFP-M
PFP-S
Y92A-48B
P2CF-08
P2CF-08-E
P2CF-11
P2CF-11-E
P3G-08
P3G-08 with Y92A-48G (See note 1)
P3GA-11
P3GA-11 with Y92A-48G (See note 1)
Y92H-7
Y92H-8
Models
Note: 1.
Y92A-48G is a finger safe terminal cover which is attached to the P3G-08 or P3GA-11 Socket.
2.
Hold-down Clips are sold in sets of two.
Specifications
■
General
Item
Operating mode
Pin type
Operating/Reset method
Output type
Mounting method
Approved standards
11-pin
Relay output (DPDT)
DIN track mounting, surface mounting, and flush mounting
UL508, CSA C22.2 No.14, NK, Lloyds
Conforms to EN61812-1 and IEC60664-1 (VDE0110) 4kV/2.
Output category according to EN60947-5-1.
H3CR-F
Flicker OFF start
8-pin
Time-limit operation/Time-limit reset or self-reset
H3CR-F8
11-pin
H3CR-FN
Flicker ON start
8-pin
H3CR-F8N
■
Time Ranges
0.05 s to 30 h Models
Time unit
Setting
1.2
3
12
30
0.05 to 1.2
0.3 to 3
1.2 to 12
3 to 30
s (sec)
×10
s (10 sec)
1.2 to 12
3 to 30
12 to 120
30 to 300
0.3 to 3
1.2 to 12
3 to 30
min (min)
0.12 to 1.2
h (hrs)
Note:
Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.
1.2 s to 300 h Models
Time unit
Setting
1.2
3
12
30
×10
s (10 sec)
1.2 to 12
3 to 30
12 to 120
30 to 300
×10
min (10 min)
1.2 to 12
3 to 30
12 to 120
30 to 300
0.3 to 3
1.2 to 12
3 to 30
h (hrs)
0.12 to 1.2
×10
h (10 hrs)
1.2 to 12
3 to 30
12 to 120
30 to 300
Note:
Instantaneous output is available at any time range. To obtain instantaneous output, set to below 0.
2
H3CR-F
■
Ratings
Rated supply voltage (See notes 1, 2, and 3.)
100 to 240 VAC (50/60 Hz),12 VDC, 24 VAC/DC (50/60 Hz), 48 to 125 VDC
Operating voltage range
Power reset
Power consumption
85% to 110% of rated supply voltage; 90% to 110% with 12-VDC models
Minimum power-opening time: 0.1 s
100 to 240 VAC: approx. 10 VA (2.1 W) at 240 VAC
24 VAC/VDC:
approx. 2 VA (1.7 W) at 24 VAC
approx. 1 W at 24 VDC
48 to 125 VDC: approx. 1.5 W at 125 VDC
12 VDC:
approx. 1 W at 12 VDC
Contact output: 5 A at 250 VAC/30 VDC, resistive load (cosφ = 1)
Control outputs
Note: 1.
A power supply with a ripple of 20% max. (single-phase power supply with full-wave rectification) can be used with each DC Model.
2.
Do not use an inverter output as the power supply. Refer to
Safety Precautions for All Timers
for details.
3.
Refer to
Safety Precautions for All Timers
when using the Timer together with a 2-wire AC proximity sensor.
■
Characteristics
Accuracy of operating
time
Setting error
Reset time
Reset voltage
Influence of voltage
Insulation resistance
Dielectric strength
±0.2%
FS max. (±0.2% FS
±10
ms max. in ranges of 1.2 and 3 s)
±5%
FS
±50
ms max.
0.1 s max.
10% max. of rated voltage
±0.2%
FS max. (±0.2% FS
±10
ms max. in ranges of 1.2 and 3 s)
100 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying metal parts and exposed non-current-carrying metal parts)
2,000 VAC, 50/60 Hz for 1 min (between control output terminals and operating circuit)
2,000 VAC, 50/60 Hz for 1 min (between contacts of different polarities)
1,000 VAC, 50/60 Hz for 1 min (between contacts not located next to each other)
3 kV (between power terminals) for 100 to 240 VAC, 48 to 125 VDC
1 kV for 12 VDC, 24 VAC/DC
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts) for 100 to 240 VAC, 48 to
125 VDC
1.5 kV for 12 VDC, 24 VAC/DC
±1.5
kV (between power terminals), square-wave noise by noise simulator (pulse width: 100 ns/1
µs,
1-ns rise)
±400
V for 12 VDC
Malfunction: 8 kV
Destruction: 15 kV
Destruction: 10 to 55 Hz with 0.75-mm single amplitude for 2 hrs each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude for 10 min each in three directions
Destruction: 980 m/s
2
three times each in six directions
Malfunction: 98 m/s
2
three times each in six directions
Operating:
Storage:
Operating:
−10°C
to 55°C (with no icing)
−25°C
to 65°C (with no icing)
35% to 85%
Influence of temperature
±1%
FS max. (±1% FS
±10
ms max. in ranges of 1.2 and 3s)
Impulse withstand
voltage
Noise immunity
Static immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
EMC
Mechanical: 20 million operations min. (under no load at 1,800 operations/h)
Electrical:
100,000 operations min. (5 A at 250 VAC, resistive load at 1,800 operations/h) (See note)
(EMI)
Emission Enclosure:
Emission AC Mains:
(EMS)
Immunity ESD:
EN61812-1
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61812-1
IEC61000-4-2:
6 kV contact discharge (level 3)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves:
IEC61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)
Immunity RF-interference from Pulse-modulated Radio Waves: IEC61000-4-3: 10 V/m (900±5 MHz) (level 3)
Immunity Conducted Disturbance: IEC61000-4-6:
10 V (0.15 to 80 MHz) (level 3)
Immunity Burst:
IEC61000-4-4:
2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity Surge:
IEC61000-4-5:
1 kV line to line (level 3)
2 kV line to ground (level 3)
Case color
Degree of protection
Weight
Light Gray (Munsell 5Y7/1)
IP40 (panel surface)
Approx. 100 g
Note:
Refer to the
Life-test Curve.
3
H3CR-F
■
Life-test Curve
10,000
Switching operations (x 10
3
)
5,000
1,000
500
30 VDC L/R = 7 ms
250 VAC/30 VDC
(cosφ = 1)
Reference: A maximum current of 0.15 A can be switched at 125 VDC (cosφ = 1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms. In
both cases, a life of 100,000 operations can be expected.
The minimum applicable load is 10 mA at 5 VDC (failure level: P).
100
250 VAC (cosφ = 0.4)
Load current (A)
Connections
■
Block Diagrams
Zero setting
detection
circuit
ON indicator
OFF indicator
Indicator
circuit
ROM
RAM
Clock
Output
circuit
AC (DC) input
Power supply
circuit
One-chip microcomputer
Time range/unit
selectors
■
I/O Functions
Inputs
Outputs
Control output
---
Outputs are turned ON/OFF according to the time set by the ON- and OFF-time setting knob.
■
Terminal Arrangement
H3CR-F8
H3CR-F8
NH3CR-F8-300
H3CR-F8N-300
H3CR-F
H3CR-FN
H3CR-F-300
H3CR-FN-300
(+)(~)
Power supply
Power supply
Note:
Leave terminals 5, 6, and 7 open.
Do not use them as relay terminals.
4
H3CR-F
Operation
■
Timing Chart
t
ON
: ON set time
t
OFF
: OFF set time
Operating mode
Flicker OFF start
Power
ON
OFF
Timing chart
0.1 s min.
t
OFF
t
ON
t
OFF
t
ON
t
OFF
t
OFF
Lit
ON
indicator Not lit
Lit
OFF
indicator Not lit
Output
NO
ON
OFF
ON
OFF
0.1 s min.
Output
NC
Flicker ON start
Power
ON
OFF
t
ON
t
OFF
t
ON
t
OFF
t
ON
t
OFF
Lit
ON
indicator Not lit
Lit
OFF
indicator Not lit
Output
NO
ON
OFF
ON
OFF
Output
NC
Note: 1.
The reset time requires a minimum of 0.1 s.
2.
When power is supplied in flicker ON start mode, the OFF indicator lights momentarily. This, however, has no effect on the performance
of the Timer.
Nomenclature
OFF indicator (green)
Lit when the output is OFF.
ON indicator (orange)
Lit when the output is ON.
OFF-time unit display window
OFF-time unit selector (select one from sec.
10 s, min., and hrs, or from 10 s, 10 min, hrs,
and 10 h)
Scale range display
windows
ON-time setting knob (with orange pointer)
For ON-time setting
OFF-time setting knob (with green pointer)
For OFF-time setting
Time range selector (select one
from 1.2, 3, 12, and 30 at full
scale)
For both ON-time and OFF-time.
ON-time unit display window
ON-time unit selector (select one
from sec, 10 s, min, and hrs, or from
10 s, 10 min, hrs, and 10 h)
5