Series OAC,(S)MOAC, X4OAC
AC Output Modules
• Status Indicating LED on
X4 Series and 4A Fuse
• UL, CSA, and CE
• Zero Cross Switching
Solid state I/O switching modules deliv-
er an electrically clean, photo-isolated,
noise-free "output" interface from
logic level control systems to external
loads such as motors, valves, solenoids,
etc. -- or an "input" interface from the
load or sensors to microprocessor or
computer-based logic level systems.
Designed for long, reliable service in
demanding industrial environments.
INPUT SPECIFICATIONS
OAC5
(S)MOAC5
X4OAC5
5
3.0 (4)
8.0 (7.5)
2.0
10
27
240
OAC15
(S)MOAC15
X4OAC15
15
8.5 (10)
18.5 (20)
2.0
10
20
900
OAC24
OAC5A
(S)MOAC24 (S)MOAC5A
X4OAC24
X4OAC5A
24
16.5 (18)
29.0 (30.5)
2.0
10
13.5
2.2K
5
3.0 (4)
8.0 (7.5)
2.0
10
27
240
OAC15A
OAC24A
(S)MOAC15A (S)MOAC24A
X4OAC15A X4OAC24A
15
8.5 (10)
18.5 (20)
2.0
10
20
900
2.2K
24
16.5 (18)
29.0 (30.5)
2.0
10
Nominal Input Voltage [Vdc]
Min. Input Voltage @ pin 3 [Vdc] (X4 Series)
Max. Input Voltage @ pin 3 [Vdc] (X4 Series)
Must Turn Off Voltage [Vdc]
T
Typical Input Current [mAdc]
Max. Input Current [mAdc]
Nominal Input Resistance [ohm]
OUTPUT SPECIFICATIONS
Nominal Line Voltage [Vrms]
Max. Line Voltage [Vrms]
Min. Line Voltage [Vrms]
Max. Peak Off-State V oltage [V peak]
Max. Off-State Leakage Current [mArms]
Static Off-State (dv/dt)[V/µs]
Max. On-State Current [Arms]
Min. On-State Current [mArms]
Max. One Cycle Surge [A peak]
Peak On-State Voltage [V peak]
Max. Turn-On Time [cycles]
Max Turn-Off Time [cycles]
Derating [mA per ˚ above 25˚ C]
Fuse Rating [fast-acting] (X4 Series Only)
120
140
12
400
2.5
200
3
50
100
1.6
1/2
1/2
33
4A
120
140
12
400
2.5
200
3
50
100
1.6
1/2
1/2
33
4A
120
140
12
400
2.5
200
3
50
100
1.6
1/2
1/2
33
4A
240
280
24
600
4.5
200
3
50
100
1.6
1/2
1/2
33
4A
240
280
24
600
4.5
200
3
50
100
1.6
1/2
1/2
33
4A
240
280
24
600
4.5
200
3
50
100
1.6
1/2
1/2
33
4A
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 304
SERIES OAC.
Rev. 071202
PAGE 1 OF 2
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506
Series OAC,
(
S
)
MOAC, X4OAC
AC Output Modules
GENERAL SPECIFICATIONS
Operating temperature range
Storage temperature range
Isolation
Capacitance input to output
Line frequency range
Package Color
-30 to +80˚C
-40 to +100˚C
4,000 Vrms
8 pF
47 to 63 Hz
Black
W IRING & M ECHANICAL DIAGRAM S
Standard Series, OAC
BOTTOM VIEW
Standard
and
M
ini
Pack
X4 Series
.30
(7.6)
.60
(15.2)
1
1
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
1.70
(43.1)
1.00
(25.4)
.100
(2.5)
Vac
Vac
2
+
1.25
(31.7)
Zero
Voltage
Circuit
2
+
3
Zero
Voltage
Circuit
3
LOGIC
LOGIC
-
4
.25
(6.3)
4
3
2
1
-
4
.030
(0.8)
.30
(7.6)
.040 (1.0) DIA.
(4 PLACES)
.70
(17.8)
1.20
(30.5)
1.40
(35.5)
X4 Series, X4OAC
M INI-PACK Series, (S)M OAC
SM Prefix
M Prefix
0.81
(20.6)
0.20
(5.1)
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
APPLICATION NOTES
• Do not install or remove modules in live
(electrically hot) circuits. High voltage
may be present.
• An externally located commutating diode
must be installed across inductive loads
.25
(6.35)
4
3+
2
1
.25
(6.35)
.30
(7.6)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.70
(43.1)
BOTTOM VIEW
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
1.70
(43.1)
1.00
(25.4)
1.70
(43.1)
1.78
(45.2)
1.00
(25.4)
1.00
(25.4)
4
3+
2
1
• I/O module boards also available
.30
(7.6)
.040 (1.0) DIA.
(4 PLACES)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.70
(43.1)
1.82
(46.2)
.040 (1.0) DIA.
(4 PLACES)
0.48
(12.2)
.040 (1.0) DIA.
(4 PLACES)
0.35
(8.9)
.40
(10.2)
.100
(2.5)
.100
(2.5)
.40
(10.2)
BOTTOM VIEW
0.55
(13.9)
0.20
(5.1)
1.3
(33.0)
1.70
(43.1)
All dimensions are in inches (millimeters)
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 304
SERIES OAC.
Rev. 071202
PAGE 2 OF 2
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506