46 Series - Miniature industrial relays 8 - 16 A
Features
1 & 2 Pole relay range
46.52 - 2 Pole 8 A
46.61 - 1 Pole 16 A
Socket mount or direct connection via Faston
connectors
•
AC coils & DC coils
•
Available with: lockable test button,
mechanical indicator & LED indicator
•
8 mm, 6 kV (1.2/50 µs) isolation, coil-contacts
•
Cadmium Free contacts
•
European Patent
•
SERIES
46.52
46.61
Plug-in / PCB Relays
2 Pole CO, 8 A
•
Plug-in/Solder terminals
•
1 Pole CO, 16 A
•
Plug-in/Faston 187
•
46.52
29
12.4
20
32.8
46.61
6.5
4.75
0.5
4.75
F
OR
UL
RATINGS SEE
:
“General technical information” page
V
Contact specification
Contact configuration
Rated current/Maximum peak current
Rated load AC1
Rated load AC15 (230 V AC)
Single phase motor rating (230 V AC)
Breaking capacity DC1: 30/110/220 V
Minimum switching load
Standard contact material
Coil specification
Nominal voltage (U
N
)
Rated power
Operating range
Holding voltage
Must drop-out voltage
Technical data
Mechanical life AC/DC
Electrical life at rated load AC1
Operate/release time
X-2013, www.findernet.com
2 CO (DPDT)
A
VA
VA
kW
A
8/15
250/440
2,000
350
0.37
6/0.5/0.15
300 (5/5)
AgNi
V AC (50/60 Hz)
V DC
VA/W
AC
DC
AC/DC
AC/DC
cycles
cycles
ms
1 CO (SPDT)
16/25 *
250/440
4,000
750
0.55
12/0.5/0.15
300 (5/5)
AgNi
* With the AgSnO
2
material
the maximum peak current is
80 A - 5 ms on normally
open contact.
Rated voltage/Maximum switching voltage V AC
mW (V/mA)
12 - 24 - 48 - 110 - 120 - 230 - 240
12 - 24 - 48 - 110 - 125
1.2/0.5
(0.8...1.1)U
N
(0.73...1.1)U
N
0.8U
N
/0.4U
N
0.2U
N
/0.1U
N
10 · 10
6
100 · 10
3
10/3
6 (8 mm)
1,000
–40 ... +70
RT II
1.2/0.5
(0.8...1.1)U
N
(0.73...1.1)U
N
0.8U
N
/0.4U
N
0.2U
N
/0.1U
N
10 · 10
6
100 · 10
3
15/5
6 (8 mm)
1,000
–40 ... +70
RT II
Insulation between coil and contacts (1.2/50 µs)kV
Dielectric strength between open contacts V AC
Ambient temperature range
Environmental protection
Approvals
(according to type)
°C
1
46
SERIES
46 Series - Miniature industrial relays 8 - 16 A
Ordering information
Example: 46 series Miniature industrial relay, 1 CO (SPDT), 24 V DC coil, lockable test button and mechanical indicator.
Plug-in / PCB Relays
A
B
C
D
4 6
.
6
Series
Type
5 = Spade/blade solder terminal
(2.5x0.5)mm
6 = Spade/blade terminal
Faston 187 (4.8x0.5)mm
No. of poles
1 = 1 pole, 16 A
2 = 2 poles, 8 A
Coil version
9 = DC
8 = AC (50/60 Hz)
Coil voltage
See coil specifications
1
.
9
.
0 2 4
.
0
0
4
0
D:
Special versions
0 = Standard
C:
Options
2 =Mechanical indicator
4 =Lockable test button +
mechanical indicator
54 =Lockable test button + LED (AC) +
mechanical indicator
74 =Lockable test button + double LED
(DC non-polarized) + mechanical indicator
A:
Contact material
0 = AgNi
4 = AgSnO
2
(46.61 only)
5 = AgNi + Au
B:
Contact circuit
0 = CO (nPDT)
Selecting features and options: only combinations in the same row are possible.
Preferred selections for best availability are shown in
bold.
Type
46.52
Coil version
AC - DC
AC
DC
AC - DC
AC
DC
A
0
-5
0-5
0-5
0
-4-5
0-4-5
0-4-5
B
0
0
0
0
0
0
C
2-
4
54
74
2-
4
54
74
D
0
/
/
0
/
/
46.61
Special versions for Rail Applications on request
Descriptions: Options
C:
Option 54
LED (AC)
C:
Option 74
LED (DC, non-polarized)
EUR
2
Lockable test button and mechanical flag indicator (0040, 0054, 0074)
1
3
O
PEAN
N
T E
O
T
EUR
P A
The dual-purpose Finder test button can be used in two ways:
Case 1) The plastic pip (located directly below the test button) remains intact. In this case, when
the test button is pushed, the contacts operate. When the test button is released the contacts return
to their former state.
Case 2) The plastic pip is broken-off (using an appropriate cutting tool). In this case, (in addition
to the above function), when the test button is pushed and rotated, the contacts are latched in
the operating state, and remain so until the test button is rotated back to its former position.
In both cases ensure that the test button actuation is swift and decisive.
X-2013, www.findernet.com
2
PEAN
46
46 Series - Miniature industrial relays 8 - 16 A
Technical data
Insulation according to EN 61810-1
Nominal voltage of supply system
Rated insulation voltage
Pollution degree
Insulation between coil and contact set
Type of insulation
Overvoltage category
Rated impulse voltage
Dielectric strength
Insulation between adjacent contacts
Type of insulation
Overvoltage category
Rated impulse voltage
Dielectric strength
Insulation between open contacts
Type of disconnection
Dielectric strength
Conducted disturbance immunity
Burst (5...50)ns, 5 kHz, on A1 - A2
Surge (1.2/50 µs) on A1 - A2 (differential mode)
Other data
Bounce time: NO/NC
Vibration resistance (10…150)Hz: NO/NC
Shock resistance
Power lost to the environment
without contact current
with rated current
Recommended distance between relays mounted on PCB
ms
g
g
W
W
mm
2/6
20/12
20
0.6
1.6
≥
5
EN 61000-4-4
EN 61000-4-5
46.61
1/4
20/15
20
0.6
2
level 4 (4 kV)
level 3 (2 kV)
46.52
V AC/kV (1.2/50 µs)
Micro-disconnection
1,000/1.5
Micro-disconnection
1,000/1.5
kV (1.2/50 µs)
V AC
—
—
—
—
Basic
III
4
2,000
kV (1.2/50 µs)
V AC
Reinforced (8 mm)
III
6
4,000
Reinforced (8 mm)
III
6
4,000
V AC
V AC
230/400
250
3
400
2
230/400
250
3
400
2
SERIES
Contact specification
F 46 - Electrical life (AC) v contact current
Type 46.52
F 46 - Electrical life (AC) v contact current
Type 46.61
Cycles
H 46 - Maximum DC1 breaking capacity
•
When switching a resistive load (DC1) having voltage and current
values under the curve, an electrical life of
≥
100·10
3
can be expected.
•
In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
46.61 current limit
DC breaking current (A)
46.52 current limit
X-2013, www.findernet.com
DC voltage (V)
3
Cycles
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
Resistive load - cosϕ = 1
Inductive load - cosϕ = 0.4
Plug-in / PCB Relays
1 pole
2 pole
46
SERIES
46 Series - Miniature industrial relays 8 - 16 A
Coil specifications
DC coil data
Nominal
voltage
U
N
V
12
24
48
110
125
AC coil data
Coil
code
Operating range
U
min
V
8.8
17.5
35
80
91.2
U
max
V
13.2
26.4
52.8
121
138
Resistance Rated coil
consumption
R
I
at U
N
Ω
mA
300
40
1,200
20
4,800
10
23,500
4.7
32,000
3.9
Nominal
voltage
U
N
V
12
24
48
110
120
230
240
Coil
code
Operating range
U
min
V
9.6
19.2
38.4
88
96
184
192
U
max
V
13.2
26.4
52.8
121
132
253
264
Resistance Rated coil
consumption
R
I
at U
N
Ω
mA
80
90
320
45
1,350
21
6,900
9.4
9,000
8.4
28,000
5
31,500
4.1
Plug-in / PCB Relays
9.012
9.024
9.048
9.110
9.125
8.012
8.024
8.048
8.110
8.120
8.230
8.240
R 46 - DC coil operating range v ambient temperature
R 46 - AC coil operating range v ambient temperature
1
- Max. permitted coil voltage.
2
- Min. pick-up voltage with coil at ambient temperature.
1
- Max. permitted coil voltage.
2
- Min. pick-up voltage with coil at ambient temperature.
Accessories
Flange mount adaptor
for relays types 46.52 and 46.61
36.6
3.6
2
046.05
046.05
14.4
46
38
18.1
046.05 with relay
046.05
046.05 with relay
35 mm rail adaptor
for relays types 46.52 and 46.61
42.4
14.4
39.8
046.07
046.07
46.9
34.8
Sheet of marker tags
for relays types 46.52 and 46.61 (72 tags), 6x12mm
060.72
060.72
4
X-2013, www.findernet.com
046.07 with relay
046.07
35.4
046.07 with relay
46
97 Series - Sockets and accessories for 46 series relays
Screw terminal socket
panel or 35 mm rail (EN 60715) mount
For relay type
Accessories
Plastic retain and release clip
(supplied with socket - packaging code SPA)
Metal retaining clip
Identification tag
8-way jumper link
Modules (see table below)
Timer modules (see table below)
Technical data
Rated current
Dielectric strength
Protection category
Ambient temperature
°C
Screw torque
Nm
Wire strip length
mm
Max. wire size for 97.01 and 97.02 sockets
mm
2
AWG
97.01 (blue)
46.61
97.01.0 (black) 97.02 (blue)
46.52
097.01
097.71
095.00.4
095.18.0 (black)
99.02
86.30
97.02.0 (black)
SERIES
97.01
Approvals
(according to type):
095.18 (blue)
097.01
16 A - 250 V AC
8 A - 250 V AC
6 kV (1.2/50 µs) between coil and contacts
IP 20
–40…+70 (see diagram L97)
0.8
8
solid wire
stranded wire
1x6 / 2x2.5
1x4 / 2x2.5
1x10 / 2x14
1x12 / 2x14
L 97 - Rated current vs ambient temperature
(for 46.61 relay / 97.01 socket combination)
Rated current (A)
97.01
O
PEAN
N
T E
O
97.01
97.02
97.02
EUR
T
8-way jumper link
for 97.01 and 97.02 sockets
Rated values
095.18 (blue)
10 A - 250 V
095.18.0 (black)
P A
095.18
86 series timer module
(12…24)V AC/DC; Bi-function: AI, DI; (0.05s…100h)
(110...125)V AC; Bi-function: AI, DI; (0.05s…100h)
(230...240)V AC; Bi-function: AI, DI; (0.05s…100h)
86.30
86.30.0.024.0000
86.30.8.120.0000
86.30.8.240.0000
Approvals
(according to type):
99.02 coil indication and EMC suppression modules
for 97.01 and 97.02
Diode (+A1, standard polarity)
(6...220)V DC
LED
(6...24)V DC/AC
LED
(28...60)V DC/AC
LED
(110...240)V DC/AC
LED + Diode (+A1, standard polarity)
(6...24)V DC
LED + Diode (+A1, standard polarity)
(28...60)V DC
LED + Diode (+A1, standard polarity)
(110...220)V DC
LED + Varistor
(6...24)V DC/AC
LED + Varistor
(28...60)V DC/AC
LED + Varistor
(110...240)V DC/AC
RC circuit
(6...24)V DC/AC
RC circuit
(28...60)V DC/AC
RC circuit
(110...240)V DC/AC
Residual current by-pass
(110...240)V AC
sockets
99.02.3.000.00
99.02.0.024.59
99.02.0.060.59
99.02.0.230.59
99.02.9.024.99
99.02.9.060.99
99.02.9.220.99
99.02.0.024.98
99.02.0.060.98
99.02.0.230.98
99.02.0.024.09
99.02.0.060.09
99.02.0.230.09
99.02.8.230.07
5
99.02
Approvals
(according to type):
X-2013, www.findernet.com
DC Modules with
non-standard polarity
(+A2) on request.
Plug-in / PCB Relays
EUR
PEAN