4−line filters
for converters and power electronics
520/300 V ac, 50/60 Hz, 8...200 A, 50
°C
Ordering code:
Date:
Version:
B84144A0008...A0200R120
2009−01−16
09
©
EPCOS AG 2008. Reproduction, publication and dissemination of this publication, enclosures
hereto and the information contained therein without EPCOS’ prior express consent is prohibited.
4−line filters
for converters and power electronics
B84144A0008...A0200R120
Construction
S
4−line filter
S
Metal case
Features
S
Easy to install
S
Compact design
S
Design complies with IEC 60939
S
cULus, ENEC approval
S
Optimized for long motor cable
and operation under full load
Applications
S
Frequency converters for motor drives, e.g.
− elevators
− pumps
− traction systems
− conveyor systems
− HVAC systems (heating, ventilation and air conditioning)
S
Power supplies
Terminals
S
Line side: finger−safe terminal blocks
S
Load side: finger−safe terminal blocks
Marking
S
Marking on component:
manufacturer’s logo, ordering code, rated voltage, rated current,
rated temperature, climatic category, date code
S
Minimum marking on packaging: maufacturer’s logo, ordering code,
date code, quantity
1
)
To IEC 60529:2001
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 2 of 15
B84143-A*-R120-09-7659
4−line filters
for converters and power electronics
B84144A0008...A0200R120
Typical circuit diagram
LINE
L1
L2
L3
LOAD
L1’
L2’
L3’
N
N’
Technical data and measuring conditions
Rated voltage
Rated frequency
Test voltage line to line for 2 s
Test voltage line to case for 2 s
Rated temperature
Overload capability (thermal)
for 3 min per hour or
for 30 s per hour
Climatic category (IEC 60068−1)
U
R
f
R
U
test
U
test
T
R
520/300
50/60
2240
2720
50
1.5 x I
R
2.5 x I
R
25/100/21
V AC
Hz
V DC
V DC
°C
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 3 of 15
B84143-A*-R120-09-7659
4−line filters
for converters and power electronics
B84144A0008...A0200R120
Characteristics and ordering codes
I
R
Terminal
cross
section
I
leak 2)
R
typ
Approx.
weight
kg
1,55
1,6
1,7
2,15
2,2
3,6
5,1
9,5
11,7
12,5
Ordering code
Approvals
A
8
16
25
36
50
66
90
120
150
200
mm
2
4
4
4
10
10
16
25
50
95
95
mA
<3,5
<3,5
<3,5
<3,5
<3,5
<3,5
<3,5
<3,5
<3,5
<3,5
mΩ
13,6
7,5
3,9
2,7
1,3
1,1
0,76
0,47
0,32
0,23
B84144A0008R120
B84144A0016R120
B84144A0025R120
B84144A0036R120
B84144A0050R120
B84144A0066R120
B84144A0090R120
B84144A0120R120
B84144A0150R120
B84144A0200R120
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
X = approval granted
2) 3 phase operation in TN network; maximum voltage = U
R
; frequency = 50 Hz without harmonics; tolerance of capacitors −20%/ 0%; worst
case positioning of the components; unbalance 2% according EN 50160:2000.
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 4 of 15
B84143-A*-R120-09-7659
4−line filters
for converters and power electronics
B84144A0008...A0200R120
Dimensional drawings
B84144A0008R120
B84144A0016R120
B84144A0025R120
60
2
80
65$0,3
225$0,5
6,5
200
238
12
45
All dimensions in mm!
Please read and
Cautions and warnings
and
Important notes
at the end of this document.
Page 5 of 15
Tightening torque of screw 0,65 − 0,8Nm
Tightening torque 2
±
0,1 Nm
PE M5x19
Terminals 4mm
2
80
B84143-A*-R120-09-7659