UDM40LSXSYR4HTX Overview

Digital Panel Meters Modular Indicator and Controller

Digital Panel Meters
Modular Indicator and Controller
Type UDM40
Multi-input modular instrument 4 dgt LED
0.1% RDG basic accuracy
TRMS AC current and voltage measurements
AC/DC current measurements; selectable full scales
(200µA to 5A)
AC/DC voltage measurements; selectable full scales
(200mV to 500V)
°C or °F temperature measurements
(Pt100-250-500-1000, Ni100, TC J-K-S-T-E)
Resistance measurements; selectable full scales
(20Ω to 20kΩ)
Up to 4 independent alarm set-points (optional)
20mA/10VDC analog output (optional)
Serial port RS485 or RS232 (optional)
MODBUS, JBUS communication protocol
Front protection degree: IP67, NEMA4x
LED display, selectable colour (red, amber, green)
• The alarm status can be coupled to the different
colour of the display
• Linearization of V and A inputs up to 16 points
Product Description
digital
panel
µp-based
meter, 4-dgt LED indicator,
for current, voltage, temper-
ature and resistance mea-
surements.
Measuring
ranges and functions easily
programmable from the key-
pad or from the PC by
means of optional UdmSoft
software. UDM
40
includes
storage min-max functions
and double level protection
password. Housing for panel
mounting with front protec-
tion degree: IP67, NEMA4x.
How to order
Model
Slot A
Slot B
Slot C
Slot D
Options
UDM40 XXX XX XX X XX
How to order
UdmSoft-kit
Type Selection
Slot A (measuring inputs)
LSX:
signal inputs:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
LSE/
LSF:
signal inputs: + AUX:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
HSX:
signal inputs:
0.2-2-5A DC/AC;
20-200-500V DC/AC
TRX:
signal inputs: TC tem-
perature probes (J-K-
S-T-E, Pt100-250-500-
1000) and resistance
(0.02-0.2-2-20kΩ)
Slot B (communication)
XX:
SX:
SY:
AV(*):
None
Serial port RS485
Serial port RS232
Single analogue output,
0 to 20mA DC and
0 to 10V DC
The two analogue
outputs cannot be
used at the same
time. It is possible to
plug in only one
module by instru-
ment.
UdmSoft-kit: software plus “UCOM1” communication cable for
programming UDM40 by means of PC .
Slot C (communication and alarm)
XX:
R1:
None
Single relay output,
(AC1-8AAC, 250VAC)
R2:
Dual relay output,
(AC1-8AAC, 250VAC)
R4:
Dual relay output, (AC1-
8AAC, 250VAC) + dual
open collector output
(NPN, 100mA)
R5:
4 relay outputs
(AC1-5AAC, 250VAC)
AV(*):
Single analogue output,
0 to 20mA DC and
0 to 10V DC
Slot D (power supply)
H:
L:
90 to 260V AC/DC
18 to 60V AC/DC
Options
XX:
TX:
None
Tropicalization
(*):
Input Specifications
Analogue inputs
BQ LSX module
BQ LSE/LSF module
BQ HSX module
BQ TRX module
BQ TRX module
Digital inputs
Number of inputs
Use
Channels and variable
1, mA and V DC/AC
1, mA and V DC/AC + AUX
1, A and V DC/AC
1, temperature
1, resistance
Incl. in the measuring module
1 (voltage-free)
key-pad lock
Display hold
Reset of latch alarms
Contact reading signal
Close contact resistance
Open contact resistance
Insulation
Accuracy
(display, RS485)
BQ xxx: <0.1mA, <3,5V DC
BQ LSE/BQ LSF: <2.5mA,
<14V DC
Max 1kΩ
Min 500kΩ
Non-insulated
See table “Measuring
accuracy”, temperature drifts
and minimum-maximum
indications”
Specifications are subject to change without notice
UDM40DS 040706
1

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号