150W Single Output with PFC Function
HRPG-150
series
■
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
‧
Bauar t gepruft
Sicherheit
egel ma ge
od
o s
be wac
g
www. tuv.com
ID 2000000000
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
HRPG-150-3.3 HRPG-150-5
3.3V
30A
0 ~ 30A
99W
5V
26A
0 ~ 26A
130W
80mVp-p
4.3 ~ 5.8V
±2.5%
±0.5%
±1.0%
7.5V
20A
0 ~ 20A
150W
100mVp-p
6.8 ~ 9V
±2.5%
±0.5%
±1.0%
12V
13A
0 ~ 13A
156W
120mVp-p
10.2 ~ 13.8V
±1.5%
±0.3%
±0.5%
15V
10A
0 ~ 10A
150W
150mVp-p
13.5 ~ 18V
±1.5%
±0.3%
±0.5%
24V
6.5A
0 ~ 6.5A
156W
150mVp-p
21.6 ~ 28.8V
±1.5%
±0.2%
±0.5%
36V
4.3A
HRPG-150-7.5 HRPG-150-12 HRPG-150-15 HRPG-150-24 HRPG-150-36 HRPG-150-48
48V
3.3A
0 ~ 3.3A
158.4W
240mVp-p
40.8 ~ 55.2V
±1.5%
±0.2%
±0.5%
0 ~ 4.3A
154.8W
200mVp-p
28.8 ~ 39.6V
±1.5%
±0.2%
±0.5%
RIPPLE & NOISE (max.)
Note.2
80mVp-p
2.8 ~ 3.8V
VOLTAGE TOLERANCE
Note.3
±2.5%
±0.5%
±1.0%
16ms/230VAC
3000ms, 50ms/230VAC
3000ms, 50ms/115VAC at full load
16ms/115VAC at full load
120 ~ 370VDC
PF>0.99/115VAC at full load
86%
87%
87%
87%
88%
88%
0.9A/230VAC
70A/230VAC
VOLTAGE RANGE
Note.5
85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION
OVER VOLTAGE
OVER TEMPERATURE
5V STANDBY
REMOTE CONTROL
WORKING TEMP.
PF>0.95/230VAC
78.5%
1.7A/115VAC
35A/115VAC
<1mA / 240VAC
84%
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6 ~ 7V
9.4 ~ 10.9V
14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V
41.4 ~ 48.6V
3.96 ~ 4.62V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
5VSB : 5V@0.3A ; tolerance±5%, ripple : 50mVp-p(max.)
RC+ / RC-: 4 ~ 10V or open = power on ; 0 ~ 0.8V or short = power off
-40 ~ +70℃ (Refer to "Derating Curve")
57.6 ~ 67.2V
FUNCTION
20 ~ 90% RH non-condensing
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
-40 ~ +85℃, 10 ~ 95% RH
±0.04%/℃
(0 ~ 50℃)
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
NOTE
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1,
EAC TP TC 004
approved
I/P-O/P:3KVAC
I/P-FG:2KVAC
O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2, heavy industry level, criteria A , EAC TP TC 020
213.4K hrs min.
MIL-HDBK-217F (25℃)
159*97*38mm (L*W*H)
0.63Kg; 24pcs/16Kg/0.76CUFT
℃
trongly
recommended that external output capacitance should not exceed 5000uF.
(Only
for:
℃℃
File Name:HRPG-150-SPEC 2018-04-28
150W Single Output with PFC Function
Function Description of CN100
HRPG-150
series
Pin No. Function Description
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted in pair to
1
-S
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
2
3
4
5
6
+S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted in pair to
minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
AUXG Auxiliary voltage output ground. The signal return is isolated from the output terminals (+V & -V).
Auxiliary voltage output, 4.75~5.25V, referenced to pin 3(AUXG). The maximum load current is 0.3A. This output is not controlled by the
AUX "remote ON/OFF control".
RC-
RC+
Remote control ground.
Turns the output on and off by electrical or dry contact between pin 5 (RC-). Short: Power OFF, Open: Power ON.
Function Manual
1.Remote Control
The PSU can be turned ON/OFF by using the "Remote
ON/OFF" function
Between RC-(pin5) and RC+(pin6)
SW ON (Short)
SW OFF (Open)
Output Status
OFF
ON
CN100
6
5
RC+
AUX
+S
-S
2
SW
RC- AUXG
1
-V
-V +V
+V
CN100
642
531
LOAD
-
+
Fig 1.1
2.Remote Sense
The remote sensing compensates voltage drop on the
load wiring up to 0.5V.
-V
-V +V
+V
CN100
642
531
CN100
6
RC+
AUX
+S
-S
2
1
-S
(Pin1)
LOAD
-
+
+S
(Pin2)
Sense lines should
be twisted in pairs
5
RC- AUXG
Fig 2.1