economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
virtually any kind of power electronics with front-end
six-pulse rectifiers, 3-phase diode or thyristor bridges,
where harmonic current distortion needs to be
reduced to defined limits.
Technical specifications
Nominal operating voltage
Operating frequency
Nominal motor drive input power rating
Total harmonic current distortion THID*
Efficiency
High potential test voltage
Protection category
Cooling
Overload capability
Ambient temperature range
3 x 380 VAC to 415 VAC ±10%
50 Hz ±1 Hz
1.1 to 200 kW
≤5% at rated power
>98% for rated voltage and power
P –> E 2160 VAC (1 s)
IP 00, IP 20
Internal fan cooling or external cooling**
1.6x rated current for 1 minute, once per hour
–25°C to +45°C fully operational
–25°C to +85°C transport and storage
+45°C to +70°C derated operation***
UL 94 V-2
Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6
>200,000 hours
100 kA
TN, TT, IT
OV III (IEC 60664-1 / UL 61800-5-1)
Typical applications
Equipment with front-end six-pulse rectifier
Motor drives
Factory automation equipment
Water/wastewater treatment facilities
Fan and pump applications
HVAC installations
Mission-critical processes
DC fast chargers
Flammability corresponding to
Design corresponding to
MTBF @ 45°C/415 V (Mil-HB-217F)
SCCR****
Earthing System
Overvoltage category
Typical electrical schematic
***
*System
requirements: THVD <2%, line voltage unbalance <1%
****
Note: performance specifications in this brochure refer to six-pulse diode rectifiers with 8% DC-link choke.
THID ~5% at rated power for filter <6 kW
***
*Please
check the inlet air flow required for cooling table on page 6 of this document.
**** I
derated
= I
nominal
*√((T
max-
T
amb
)/(T
max-
T
nominal
)) = I
nom
*√((70°C-T
amb
)/25°C)
**** External UL-rated fuses required. Please consult the user manual.
(all configurable optional fuctionalities shown)
2
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Filter selection table – IP 00 enclosure
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN 3441-1-110-E0_ _ _ _ _*
FN 3441-2-110-E0_ _ _ _ _*
FN 3441-4-112-E0_ _ _ _ _*
FN 3441-6-112-E0_ _ _ _ _*
FN 3441-8-112-E0_ _ _ _ _*
FN 3441-11-113-E0_ _ _ _ _
FN 3441-15-113-E0_ _ _ _ _
FN 3441-19-113-E0_ _ _ _ _
FN 3441-22-115-E0_ _ _ _ _
FN 3441-30-115-E0_ _ _ _ _
FN 3441-37-115-E0_ _ _ _ _
FN 3441-45-115-E0_ _ _ _ _
FN 3441-55-115-E0_ _ _ _ _
FN 3441-75-116-E0_ _ _ _ _
FN 3441-90-116-E0_ _ _ _ _
FN 3441-110-118-E0_ _ _ _ _
FN 3441-132-118-E0_ _ _ _ _**
FN 3441-160-118-E0_ _ _ _ _**
FN 3441-200-118-E0_ _ _ _ _**
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
Motor drive
input current***
[Arms]
1.7
3.4
6.2
8.5
12
17
23
29.3
34
46
57
70
85
116
140
171
205
249
312
Rated filter
input current
[Arms]
1.62
3.23
5.9
8.1
11
16
22
28
32
44
54
66
81
110
133
162
195
238
297
Min. required
L
DC
****
[mH]
37.41
18.71
10.29
7.483
5.487
3.741
2.744
2.166
1.871
1.372
1.112
0.915
0.748
0.549
0.457
0.374
0.312
0.257
0.206
Min. required
L
AC
****
[mH]
9.8
6.01
3.48
2.548
1.818
1.264
0.909
0.724
0.637
0.454
0.361
0.297
0.245
0.178
0.147
0.12
0.099
0.085
0.064
[kg]
6
9
12
15
16
23
26
30
38
43
48
54
63
98
106
127
149
167
209
110
110
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
C
C
D
D
D
E
E
E
E
E
G
G
H
H
H
H
Weight
Terminal
Frame size
*
Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** In order to apply FN 3441 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3441 filter must not be used. In this case, FN 3440 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
4
8
8
14
14
25
25
25
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
3
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Filter selection table - IP 20 enclosure
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN 3441-1-110-E2_ _ _ _ _*
FN 3441-2-110-E2_ _ _ _ _*
FN 3441-4-112-E2_ _ _ _ _*
FN 3441-6-112-E2_ _ _ _ _*
FN 3441-8-112-E2_ _ _ _ _*
FN 3441-11-113-E2_ _ _ _ _
FN 3441-15-113-E2_ _ _ _ _
FN 3441-19-113-E2_ _ _ _ _
FN 3441-22-115-E2_ _ _ _ _
FN 3441-30-115-E2_ _ _ _ _
FN 3441-37-115-E2_ _ _ _ _
FN 3441-45-115-E2_ _ _ _ _
FN 3441-55-115-E2_ _ _ _ _
FN 3441-75-116-E2_ _ _ _ _
FN 3441-90-116-E2_ _ _ _ _
FN 3441-110-118-E2_ _ _ _ _
FN 3441-132-118-E2_ _ _ _ _**
FN 3441-160-118-E2_ _ _ _ _**
FN 3441-200-118-E2_ _ _ _ _**
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
Motor drive
input current
[Arms]***
1.7
3.4
6.2
8.5
12
17
23
29.3
34
46
57
70
85
116
140
171
205
249
312
Rated filter
input current
[Arms]
1.62
3.23
5.9
8.1
11
16
22
28
32
44
54
66
81
110
133
162
195
238
297
Min. required
L
DC
****
[mH]
37.41
18.71
10.29
7.483
5.487
3.741
2.744
2.166
1.871
1.372
1.112
0.915
0.748
0.549
0.457
0.374
0.312
0.257
0.206
Min. required
L
AC
****
[mH]
9.8
6.01
3.48
2.548
1.818
1.264
0.909
0.724
0.637
0.454
0.361
0.297
0.245
0.178
0.147
0.12
0.099
0.085
0.064
[kg]
7
9
13
16
18
27
30
34
44
48
54
59
68
107
115
144
166
185
226
110
110
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
C
C
D
D
D
E
E
E
E
E
G
G
H
H
H
H
Weight
Terminal
Frame size
*
Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** In order to apply FN 3441 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3441 filter must not be used. In this case, FN 3440 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
M3
M4
M6
M8
M8
M10
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
[Nm]
0.5
1.2
3
8
8
10
[mm]
7
10
15
15
17
35
A
B, C
D
E, F
G
H
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
M3*
M5
M6
M6
M8
M8
M10
M10
M10
0.5
4
8
8
14
14
25
25
25
All
A
B
C
D
E
F
G
H
Frame size
* Max width cable lug = 7 mm
4
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Product selector
Table 1: Filter configurations if external air flow is available for cooling
(Filters do
not contain fan
and do
not contain aux. power supply)
E0XXXXX
- For rectifiers with DC-link choke
E0XXJXX
- For rectifiers with DC-link choke
- Filters contain trap disconnect
jumper
E0XXXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module
E0XXJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module and trap disconnect
jumper
5
Ecosine passive
Schaffner Group
Datasheets
15 Nov 2018
Table 2: Filter configurations with embedded ventilation
(Filters
contain fan
and
aux. power supply)
E0FAXXX and E2FAXXX
- For rectifiers with DC-link choke
- Filters contain fan and aux. power
supply
E0FAJXX and E2FAJXX
- For rectifiers with DC-link choke
- Filters contain fan, aux. power
supply and trap disconnect
jumper
E0FAXRX and E2FAXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply and RC damper module
E0FAJRX and E2FAJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply, RC damper module and
trap disconnect jumper
Table 3: Filter configurations if external aux. power supply for the fan is available
The one used is IAR EW8051-EV-750A.Errors often occur during runtime, such as: Fatal Error[Pe005]: could not open source file "hal.h" D:\CC2430 Tester-0.6\PER-Receive\Library\cc2430\HAL\source\wait.c ...
Basic diode circuit and its analysis method In electronic technology, diode circuits are widely used. This section only introduces several basic circuits, such as limiter circuits, switch circuits, l...
The update speed of MicroPython has slowed down significantly recently. It is estimated that the official team has new plans. The main recent improvements are: [list] [*][url=https://github.com/microp...
I want to design a bandpass filter to filter out signals within a certain range, but when designing the circuit parameters, I have to consider the passband cutoff frequency fc and the stopband cutoff ...
Isn't it cool to start your 2022 New Year journey with an open source DIY? The "Pingtou Ge RVB2601 Application Solution Collection Activity" planned by EEWorld community and Pingtou Ge has officially ...
1. Output characteristics of ordinary switching power supplies For switching power supplies in the usual sense, it is generally required to have a fast output response. Figure 1-1 is a standard power ...
1. Three-terminal fixed type
Integrated voltage regulator
If the aforementioned series-type voltage-stabilized power supply circuit is all integrated on a piece of silicon chip, pack...[Details]
Adding electrical components to the drivetrain makes a car's internal combustion engine more efficient, and the effect is more obvious than just making minor adjustments to the engine. It reduces...[Details]
0 Introduction
In electrical measurement and control systems, it is often necessary to collect various analog signals and digital signals and process them accordingly. In general, ordinary MCUs (suc...[Details]
1 Introduction
A stepper motor is an electromagnetic mechanical device that converts an electrical pulse signal into a corresponding angular displacement or linear displacement. It is an incre...[Details]
The MTS-4000 is a highly integrated platform that includes two module slots, a large 7-inch color screen with touch screen option, a high-capacity lithium-ion battery, and an optional video inspectio...[Details]
Recently, Lynk & Co officially announced that the new electric car Lynk & Co ZERO ( parameters | inquiry ) released in the first half of this year will be equipped with a fully automatic air su...[Details]
Whether it is called iPhone 12S or iPhone 13, there is no doubt that Apple's research and development work is in full swing. In a latest investment report, well-known analyst Ming-Chi Kuo sa...[Details]
Among the industrial and domestic electrical loads, resistive and inductive loads account for a large proportion. Asynchronous motors, transformers, fluorescent lamps, etc. are typical resistive ...[Details]
A Unique Instrument
Network analyzers are powerful instruments that can achieve extremely high accuracy when used correctly. They are also widely used and indispensable in many industries, especia...[Details]
Whether it is necessary to buy a robot vacuum cleaner depends mainly on one's actual situation and needs. Robot vacuum cleaners are very practical for people who do not have the time or are unwilli...[Details]
The magnetic flap is located outside the float and is the core component of the magnetic flap level gauge. When the magnetic float in the float rises and falls with the liquid level, the magnet in ...[Details]
On the 3rd, the procurement department of Samsung SDI, a representative company of the Korean battery industry, held a meeting with small and medium-sized enterprises in the Korean battery industry to...[Details]
"Common Mode Semiconductor" launches the GM4500 series of 5V precision CMOS operational amplifiers. The GM4500 series of products are the lowest noise precision CMOS amplifiers in industrial applicat...[Details]
This article mainly discusses the application of database systems based on different data storage technology solutions, so as to deepen the understanding of the application of different data storage ...[Details]
AC power control circuit is an important part of modern power system, which involves the control and regulation of AC power. In practical applications, there are many control methods for AC power c...[Details]