EEWORLDEEWORLDEEWORLD

Part Number

Search

PK02W-50-3M8

Description
Single Phase EMI Filter, 250V, 50/60HzHz,
CategoryAnalog mixed-signal IC    filter   
File Size529KB,3 Pages
ManufacturerPower Dynamics, Inc.
Websitehttp://www.powerdynamics.com/
Environmental Compliance  
Download Datasheet Parametric View All

PK02W-50-3M8 Overview

Single Phase EMI Filter, 250V, 50/60HzHz,

PK02W-50-3M8 Parametric

Parameter NameAttribute value
Is it lead-free?Lead free
Is it Rohs certified?conform to
MakerPower Dynamics, Inc.
Reach Compliance Codecompliant
Other featuresMEDICAL APPLICATION; ADDITIONAL COMPONENT BLEED RESISTOR
CertificationUL; CSA; VDE
filter typeSINGLE PHASE EMI FILTER
high38.6 mm
high potential2250 V
Maximum leakage current0.005 mA
length105 mm
Manufacturer's serial numberPK
Installation typePANEL MOUNT
working frequency50/60Hz Hz
Maximum operating temperature85 °C
Minimum operating temperature-25 °C
physical sizeL105.0XB100.0XH38.6 (mm)/L4.134XB3.937XH1.52 (inch)
Rated current2 A
Rated voltage250 V
PK Series
CHASSIS MOUNT, HIGH PERFORMANCE, MULTIPURPOSE,
SINGLE STAGE EMI/RFI LINE FILTER.
MECHANICAL DIMENSIONS
(Unit: mm)
A1, A2, A3
C
A
2x 4.8
D
B
E
10.0
G
DIMENSIONS
CASE
CODE A
B
C
F
G
D
E
24.4 45.0 17.5 64.5 54.1 8.5 49.6
A1
33.8 45.0 30.0 64.5 54.5 14.9 59.0
A2
46.5 51.8 30.0 70.9 60.9 14.9 71.7
A3
F
FEATURES
The PK series offers a wide variety of EMI filters in numerous
styles of packages and current ratings. The filters are effective
in reducing both Line-to-Line and Line-to-Ground noise up to
30 Amp at 250VAC. This series offers very low leakage
current suitable for medical and non-medical applications.
These filters are also available for Medical applications.
The absence of C(y) capacitors offers extremely low Leakage
current to comply with various industry standards especially
the medical equipment with Switching power supplies.
A Bleeder resistor can also be added to prevent excessive
voltages from developing across the filter capacitors when
there is no load.
51.5
B1
85.3
95.3
64.0
39.1
2x
4.8
(14.9)
(4.6)
APPLICATIONS
Computer & networking equipment, Measuring & control
equipment, Data processing equipment, laboratory instruments,
Switching power supplies, other electronic equipment.
G1
100.0
82.5
TECHNICAL DATA
Rated Voltage: 115/250VAC
Rated Current: 1A, 2A, 3A, 5A, 6A, 10A, 15A, 20A, 30A
Power Line Frequency: 50/60Hz
Max. Leakage Current each
Line to Ground:
@ 115VAC 60Hz: 0.25mA
@ 250VAC 50Hz: 0.45mA
@ 115VAC 60Hz: 2
µ
A*
@ 250VAC 50Hz: 5
µ
A*
Hipot Rating (one minute)
Line to Ground: 2250VDC
Line to Line: 1450VDC
Temperature Range: -25C to +85C
* Medical application
105.0
95.3
86.4
38.6
4X 6.5X4.0
50.8
(17.3)
(6.1)
Specifications subject to change without notice. Dimensions (mm).
145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076
e-mail: filtersales@powerdynamics.com •
www.powerdynamics.com
35

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号