1
/
4
˝ x 1
1
/
4
˝ Time-Delay, Glass Tube Fuses
MDL Series
Description
• Time-delay, glass tube fuse
• Optional axial leads available
•
1
⁄
4
x 1
1
⁄
4
(6.4 x 31.7mm) physical size
• Glass tube, nickel-plated brass endcap construction
• UL Listed product meets standard 248-14
Rated Current
1/16 - 30A
1/16 - 3A
3-2/10 - 8A
Electrical Characteristics
% of Amp Rating
Opening Time
100%
None
135%
60 minutes maximum
200%
120 seconds maximum
200%
5 seconds minimum
200%
12 seconds minimum
Agency Information
• UL Listed Card: MDL 1/16 - 8A (Guide JDYX, File E19180)
• UL Recognized Card: MDL 9 - 30A (Guide JDYX2,
File E19180)
• CSA Certification Card: MDL 1/16 - 8A (Class No. 1422-01)
• CSA Component Acceptance: MDL 9-30A
(Class No. 1422-30)
• CE
Environmental Data
• Shock: 1A thru 30A – MIL-STD-202, Method 207, (HI Shock)
• Vibration: 1/4A thru 30A – MIL-STD-202, Method 204, Test
Condition C (Except 5g, 500HZ)
Ordering
Specify packaging code
• Insert packaging code prefix before part number. E.g., BK
(or BK1)-MDL-5-R
Specify option codes if desired
• For axial leads, insert “V” between catalog series and amp
rating. E.g., BK-MDL-V-5-R
Voltage
Rating
Vac
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
32
32
32
32
32
32
• For board washable, insert “B” between catalog series and
amp rating. E.g., BK-MDL-B-5-R
• For axial leads and board washable, insert “B” then “V”
between catalog series and amp rating. E.g., BK-MDL-BV-5-R
Dimensions - mm
(in)
Drawing Not to Scale
38.10
(1.500)
32.82
(1.292)
38.10
(1.500)
6.76
(0.266)
DIA. OF LEADS
0.81
0–15 AMP:
(0.032)
20–30 AMP: 1.02
(0.040)
31.75
(1.250)
6.35
(0.250)
Specifications
AC Interrupting Rating* (amps)@
250Vac
125Vac
32Vac
35
35
35
35
35
35
35
35
35
35
35
100
100
100
100
100
100
200
200
200
200
200
200
-
-
-
-
-
-
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1000
1000
1000
1000
1000
1000
Part
Number
MDL-1/16-R
MDL-1/10-R
MDL-1/8-R
MDL-3/16-R
MDL-2/10-R
MDL-1/4-R
MDL-3/10-R
MDL-3/8-R
MDL-1/2-R
MDL-3/4-R
MDL-1-R
MDL-1-1/4-R
MDL-1-1/2-R
MDL-2-R
MDL-2-1/4-R
MDL-2-1/2-R
MDL-3-R
MDL-4-R
MDL-5-R
MDL-6-R
MDL-6-1/4-R
MDL-7-R
MDL-8-R
MDL-9-R
MDL-10-R
MDL-15-R
MDL-20-R
MDL-25††
MDL-30††
Typical DC Cold
Resistance**
Ω
(Ω)
45.6
15.68
12.238
4.81
5.234
3.208
2.046
1.567
0.943
0.397
0.273
0.205
0.156
0.116
0.096
0.081
0.057
0.038
0.025
0.022
0.02
0.018
0.015
0.012
0.01
0.005
0.004
0.01225
0.0011
Typical
Melting I
2
t†
AC
0.0046
0.0420
0.0422
0.116
0.314
0.447
0.412
0.982
1.656
4.343
11.498
86.2
22.7
62.3
49.6
63.1
67.5
19.3
32.0
37.4
38.7
42.7
47.8
51.5
64.4
354.0
2914.0
15221.0
15581.0
Typical
Voltage
Drop‡
2.79
1.95
1.52
1.05
0.972
0.965
0.808
1.46
1.27
1.01
0.995
0.722
0.721
0.644
0.535
0.410
0.345
0.187
0.160
0.155
0.152
0.140
0.119
0.124
0.114
0.130
0.530
0.30
0.40
* Interrupting Ratings (Interrupting ratings were measured at 70% - 80% power factor on AC)
** DC Cold Resistance (Measured at ≤10% of rated current)
† Typical Melting I
2
t (A
2
Sec) (I
2
t was measured at listed interrupting rating and rated voltage.)
‡ Typical Voltage Drop (Voltage drop was measured at 25°C±3°C ambient temperature at rated current)
†† MDL-25 & MDL-30 not available in RoHS compliant construction.
11-08
SB-BU08675
Page 1 of 2
Data Sheet 2004
TIME CURRENT CURVE
Current in Amps
Time in Seconds
Time in Seconds
Current in Amps
Packaging Code
Packaging Code
BK
BK1
BK8
Description
100 fuses packed into a cardboard carton
1,000 fuses packed into a cardboard carton
8,000 fuses packed into a cardboard carton
Option Code
Option Code
B
V
Description
Board Washable - Hermetically sealed to withstand aqueous cleaning
Axial leads - copper tinned wire with nickel plated brass overcaps
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
Life Support Policy: Cooper Bussmann does not authorize the use of any of its products for use in life support devices or systems without the express written approval of an officer of the Company. Life support
systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with instructions for use provided in the labeling, can be reasonably expected to result in
significant injury to the user.
© 2008 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
11-08
SB-BU08675
Page 2 of 2
Data Sheet 2004