Power entry modules with line filter
www.schurter.com/pg06
Inlet filter, front side mounting, circuit breaker TA45 2-pole
545
Standard- or Medical-Filter
C14
70° C
Description
- Panel Mount:
Screw-on from front side
- 3 Functions:
Inlet Protection class I, circuit breaker type TA45 2-pole, Line filter in
standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter 6145
- We recommend for new applications type DF12
Characteristics
- All single elements are already wired
Unwired versions available on request
- Line switch non-illuminated or illuminated
Thermal overload protection
Optional with undervoltage release or remote trip release
- Qualified for use in equipment according IEC/EN 60950
References
Weblinks
General Product Information
Approvals: www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
CHINA-RoHS: www.schurter.com/china-rohs
Webstore: www.schurterinc.com/estore/search.ihtml
Approvals
- VDE License Number: 117118
- UL License Number: E72928
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
Dielectric Strength
1 - 10 A @ Ta 40 °C / 250 VAC; Hz 50
1 - 15 A @ Ta 40 °C / 125 VAC; 60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
> 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
-10 °C to 55 °C
10/055/21 acc. to IEC 60068-1
from front side IP 40 acc. to IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminals 6.3 x 0.8 mm
Screw-on: max 8 mm
Mounting screw torque max 0.5 Nm
Thermoplastic, black, UL 94V-0
Appliance-Inlet /-Outlet
C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold
condition) pin-temperature 70 °C, 10 A,
Protection class I
Acc. IEC/EN 60934, UL 1077, CSA
22.2 no. 235
2-pole rocker switch, illuminated or non-
illuminated. Optional with undervoltage-
or remote trip release
Short circuit capacity Icn:
at In < 3A/240VAC : 10 x In
at In ≥ 3A/240VAC : 300A
Rocker switch 2-pole non-illuminated or
illuminated acc. to IEC 61058-1
Technical details
Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
> 100'000 h acc. to MIL-HB-217 F
Circuit breaker
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Panel Thickness s
Material: Housing
Line Switch
Line Filter
MTBF
Connectors
Power entry modules with line filter
www.schurter.com/pg06
545
Technical data (continued)
Circuit breaker
Tripping characteristics
I
n
< 3 A
[ min ] [ sec ]
10’000
Type
Rated current
TA45
In < 3 A
1-pole protected
Tripping characteristics
I
n
3… 15 A
[ min ] [ sec ]
10’000
Type
Rated current
TA45
I n
≥
3...
≤
15 A
1-pole protected
60
30
20
10
5
200
100
1
50
20
10
5
2
1
0,5
Tripping time
60
30
20
10
5
200
100
1
50
20
10
5
2
1
0,5
Tripping time
2000
1000
500
Ambient temp.
2-pole protected
+23
°C
2’000
1’000
500
Ambient temp.
2-pole protected
+23
°C
0,3
0,2
0,1
1,05 1,32
2
3
4
[ x In ]
5
8
10
Multiple of rated current
0,3
0,2
0,1
1,05 1,32
2
3
4
[ x In ]
5
8
10
Multiple of rated current
Effect of ambient temperature
1)
The unit is calibrated for an ambient temperature of +23 °C. To
determine the rated current for a lower or higher ambient tempera-
ture, use a correction factor from the table below.
*
Ambient temperature [°C] Correction factor
–10
0,89
– 5
0,91
0
0,92
+23
1,00
+30
1,03
+40
1,08
+55
1,16
* Temperature must be measured at the rear of the breaker next to
the terminals after equipment operating temperature has been
reached.
Example
Rated current at +23 °C
Ambient temperature
Correction factor
Chosen rated current at
+ 40 °C ambient temperature
1)
6,0 A
+40 °C
1,08
6 A x 1,08 = 6,5 A
Order code (Order example)
Type
Order code TA45
(2-pole rocker-switch without
accessories)
Wiring
0
Without
1
With
Type of line filter
1
Standard
3
Medical
Rated current of line filter
1
1 (A)
5
6 (A)
2
2 (A)
6
8 (A)
3
3 (A)
7
10 (A)
4
4 (A)
8
15 (A)
5145. A B T W F 1 5 0 C 0
see table 1
.
0 0 1
Please note that Schurter will establish an internal part number for logistical use in additional to the order code. The format of this internal part
number is, for example 5145.0031.001
The specifications, descriptions and illustrations indicated in this document are based on
Connectors
current information. All content is subject to modifications anamendments.
5