EEWORLDEEWORLDEEWORLD

Part Number

Search

PEA30PS-50-1MM2

Description
Single Phase EMI Filter, 250V, 50/60HzHz,
Categoryfilter   
File Size150KB,3 Pages
ManufacturerPower Dynamics, Inc.
Websitehttp://www.powerdynamics.com/
Environmental Compliance  
Download Datasheet Parametric View All

PEA30PS-50-1MM2 Overview

Single Phase EMI Filter, 250V, 50/60HzHz,

PEA30PS-50-1MM2 Parametric

Parameter NameAttribute value
Is it lead-free?Lead free
Is it Rohs certified?conform to
MakerPower Dynamics, Inc.
Reach Compliance Codecompliant
Is SamacsysN
Other featuresMEDICAL APPLICATION
CertificationUL; VDE
filter typeSINGLE PHASE EMI FILTER
high potential2250 V
Maximum leakage current0.005 mA
Manufacturer's serial numberPEA
Installation typePANEL MOUNT
working frequency50/60Hz Hz
Maximum operating temperature85 °C
Minimum operating temperature-25 °C
Rated current30 A
Rated voltage250 V
Base Number Matches1
PEA Series
CHASSIS MOUNT, HIGH PERFORMANCE, SINGLE STAGE
EMI/RFI LINE FILTER.
MECHANICAL DIMENSIONS
(Unit: mm)
A2, A3
A
C
2x 4.8
D
B
E
10.0
G
DIMENSIONS
CASE
CODE A
B
C
F
D
E
G
A2
33.8 45.0 30.0 64.5 54.5 14.9 59.0
A3 46.5 51.8 30.0 70.9 60.9 14.9 71.7
F
FEATURES
The PEA series offers wide variety of EMI filters in numerous
packages and current ratings. This series offers superior
performance in controlling EMI suppression in Line-to-Line
noise up to 30 Amp, 250VAC.
These filters are also available for Medical application.
The absence of C(y) capacitors offer extremely low leakage
current to comply with various industry standards especially
for medical equipment with Switching power supplies.
B1
51.5
85.3
74.7
64.0
APPLICATIONS
39.1
2x
4.8
Computer & networking equipment, Measuring & control
equipment, Data processing equipment, laboratory instruments,
Switching power supplies, other electronic equipment.
(14.9)
(4.6)
TECHNICAL DATA
Rated Voltage: 115/250VAC
Rated Current: 1A, 2A, 3A, 5A, 6A, 10A, 15A, 20A, 30A
Power Line Frequency: 50/60Hz
Max. Leakage Current each
Line to Ground:
@ 115VAC 60Hz: 0.25mA
@ 250VAC 50Hz: 0.45mA
@ 115VAC 60Hz: 2
µ
A*
@ 250VAC 50Hz: 5
µ
A*
Hipot Rating (one minute)
Line to Ground: 2250VDC
Line to Line: 1450VDC
Temperature Range: -25C to +85C
* Medical application
G1
100.0
82.5
105.0
95.3
86.4
38.6
4X 6.5X4.0
50.8
(17.3)
(6.1)
Specifications subject to change without notice. Dimensions (mm).
145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076
e-mail: filtersales@powerdynamics.com •
www.powerdynamics.com
33

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号