https://www.phoenixcontact.com/pi/products/2306993
Passive module - UM-FLK14/SI/LA/PTS/8IM/PLC - 2306993
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
VARIOFACE module, for 8 channels with additional plus and minus terminal blocks. Each channel is secured
with a fuse (5 x 20 mm) and comes with a fuse failure indicator. The signal path can be interrupted with a
disconnect knife.
Key Commercial Data
Packing unit
GTIN
GTIN
4017918976743
1 pc
Technical data
Dimensions
Width
Height
Depth
73 mm
126 mm
76 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-20 °C ... 50 °C
-20 °C ... 70 °C
General
Max. perm. operating voltage
Max. perm. current (per branch)
Max. permissible current (separate power supply)
Number of positions
Status display
Mounting position
Assembly instructions
Degree of protection
25 V DC
1A
2A
14
No
any
In rows with zero spacing
IP00
Connection data for connection 1
10/15/2018 Page 1 / 3
https://www.phoenixcontact.com/pi/products/2306993
Passive module - UM-FLK14/SI/LA/PTS/8IM/PLC - 2306993
Technical data
Connection data for connection 1
Connection name
Connection method
Stripping length
Screw thread
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Field level
Screw connection
6 mm
M3
0.14 mm² ... 1.5 mm²
0.14 mm² ... 1.5 mm²
26 ... 16
Connection data for connection 2
Connection name
Connection method
Number of connections
Number of positions
Pitch
Controller level
IDC/FLK pin strip
1
14
2.54 mm
Supported controller
Controller
- suitable I/O card
ABB S800 I/O
DI810
DI818
DI830
DI840
DO810
DO840
Standards and Regulations
Designation
Standards/regulations
Rated insulation voltage
Rated surge voltage
Insulation
Degree of pollution
Overvoltage category
Air clearances and creepage distances
DIN EN 50178: 1998-04
50 V
0.5 kV (1.2/50 μs)
Functional insulation
2
II
Environmental Product Compliance
REACh SVHC
China RoHS
Lead 7439-92-1
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
10/15/2018 Page 2 / 3
https://www.phoenixcontact.com/pi/products/2306993
Passive module - UM-FLK14/SI/LA/PTS/8IM/PLC - 2306993
Circuit diagram
1
2
3
4
5
6
7
8
9 11 13 10 12 14
F24V
0
1
2
3
4
-
F3
5
-
F4
6
7
-
-
-
-
F0 F1 F2
-
0V
-
F5 F6 F7
+
+
+
+
+
+
+
+
24V
Approvals
Approvals
Approvals
EAC
Ex Approvals
Approval details
EAC
RU C-
DE.A*30.B.01742
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
Tel. +49 5235 300
Fax +49 5235 3 41200
http://www.phoenixcontact.com
10/15/2018 Page 3 / 3