Series IAC, (S)MIAC, X4IAC
AC Input Modules
• S
tatu s
Indicating LED
on
X4 Series
• UL, CSA,
and
CE
Solid state I/O switching modules deliv-
er an electrically clean, photo-isolated,
noise-free "output" interface from
logic level control systems to external
loads such as motors, valves, solenoids,
etc. -- or an "input" interface from the
load or sensors to microprocessor or
computer-based logic level systems.
Designed for long, reliable service in
demanding industrial environments.
INPUT SPECIFICATIONS
IAC5
(S)MIAC 5
X4IAC5
IAC15
(S)MIAC 15
X4IAC15
IAC24
(S)MIAC 24
X4IAC24
IAC5A
(S)MIAC 5A
X4IAC5A
IAC15A
(S)MIAC 15A
X4IAC15A
IAC24A
(S)MIAC 24A
X4IAC24A
Nominal input voltage [Vrms/Vdc]
Minimum Input Voltage [Vrms/Vdc]
Maximum Input Voltage [Vrms/Vdc]
Maximum Input Current [mA rms]
Drop Out Current [mA rms]
Allowable Off-state Current [mA rms]
Allowable Off-state Voltage [Vrms/Vdc]
120
90
140
10
2.5
3.0
50.0
120
90
140
10
2.5
3.0
50.0
120
90
140
10
2.5
3.0
50.0
240
180
280
8
1.5
2.0
120
240
180
280
8
1.5
2.0
120
240
180
280
8
1.5
2.0
120
OUTPUT SPECIFICATIONS
Nominal Logic Voltage [Vdc]
Minimum Logic Voltage [Vdc] (X4 Series)
Maximum Logic Voltage [Vdc] (X4 Series)
Typical Logic Supply Current [mAdc]
Max. Logic Supply Current [mAdc]
Max. Logic Sup. Leak. Current [µAdc]
Maximum Output Voltage [Vdc]
Maximum Output Current [mAdc]
Max. Output Leakage Current [µAdc]
Max. Output Voltage Drop [mVdc]
Maximum Turn-on Time [msec]
Maximum Turn-off Time [msec]
5
1.5 (3)
6.0 (7)
10
18.5
10
30
50
10
200
20
30
15
8.5 (10)
18.5 (20)
10
16
10
30
50
10
200
20
30
24
16.5 (18)
30.5 (32)
10
14
10
30
50
10
200
20
30
5
1.5 (3)
6.0 (7)
10
18.5
10
30
50
10
200
20
30
15
8.5 (10)
18.5 (20)
10
16
10
30
50
10
200
20
30
24
16.5 (18)
30.5 (32)
10
14
10
30
50
10
200
20
30
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 302
SERIES IDC.
Rev. 031902
PAGE 1 OF 2
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506
Series IAC, (S)MIAC, X4IAC
AC Input Modules
GENERAL SPECIFICATIONS
Operating temperatue ranger
Storage temperature range
Isolation
Capacitance input to output
Line frequency range
Package Color
Ð30 to +80˚C
Ð40 to +100˚C
4,000 V rms
8 pF
47 to 63 Hz
Yellow
W IRING & M ECHANICAL DIAGRAMS
Standard Series, IAC
BOTTOM VIEW
Standard
and
Mi
ni
Pack
1
1
X4 Series
.30
(7.6)
.60
(15.2)
Vac/dc
Vac/dc
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
1.70
(43.1)
1.00
(25.4)
.100
(2.5)
2
2
LOGIC
1.25
(31.7)
+
3
LOGIC
+
3
OUT
Schmitt
Trigger
4
OUT
Schmitt
Trigger
4
.25
(6.3)
5
4
3
2
1
.030
(0.8)
.30
(7.6)
GND
-
5
GND
-
5
.040 (1.0) DIA.
(5 PLACES)
.70
(17.8)
1.20
(30.5)
1.40
(35.5)
1.60
(40.6)
X4 Series, X4IAC
MI NI-PACK Series, (S)MIAC
SM Prefix
M Prefix
0.81
(20.6)
0.20
(5.1)
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
APPLICATION NOTES
¥ Do not install or remove modules
in live (electrically hot) circuits.
High voltage may be present.
¥ An externally located
commutating diode must be
installed across inductive loads
¥ I/O module boards also available
.25
(6.35)
.30
(7.6)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.30
(43.1)
1.70
(43.1)
BOTTOM VIEW
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
1.70
(43.1)
1.00
(25.4)
1.70
(43.1)
1.78
(45.2)
1.00
(25.4)
1.00
(25.4)
5
4
3+
2
1
.25
(6.35)
.30
(7.6)
5
4
3+
2
1
.040 (1.0) DIA.
(5 PLACES)
.200
(5.1)
.700
(17.8)
1.100
(27.9)
1.30
(43.1)
1.70
(43.1)
BOTTOM VIEW
1.82
(46.2)
0.48
(12.2)
.040 (1.0) DIA.
(5 PLACES)
.040 (1.0) DIA.
(5 PLACES)
0.15
(3.8)
0.35
(8.9)
0.55
(13.9)
0.20
(5.1)
1.3
(33.0)
1.70
(43.1)
.100
(2.5)
.40
(10.2)
.40
(10.2)
.100
(2.5)
All dimensions are in inches (millimeters)
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 302
SERIES IDC.
Rev. 031902
PAGE 2 OF 2
For recommended applications and more information contact:
USA: Sales Support
(877) 502-5500
Tech Support
(877) 702-7700
FAX
(619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email:
sales@crydom.com
WEB SITE:
http://www.crydom.com
UK:
+44 (0)1202 365070 •
FAX
+44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE,
Email:
intsales@crydom.com.
GERMANY:
+49 (0)180 3000 506