EEWORLDEEWORLDEEWORLD

Part Number

Search

UDM40TRXSXR5HTX

Description
Digital Panel Meters Modular Indicator and Controller
File Size504KB,11 Pages
ManufacturerETC
Download Datasheet View All

UDM40TRXSXR5HTX Overview

Digital Panel Meters Modular Indicator and Controller

Digital Panel Meters
Modular Indicator and Controller
Type UDM40
Multi-input modular instrument 4 dgt LED
0.1% RDG basic accuracy
TRMS AC current and voltage measurements
AC/DC current measurements; selectable full scales
(200µA to 5A)
AC/DC voltage measurements; selectable full scales
(200mV to 500V)
°C or °F temperature measurements
(Pt100-250-500-1000, Ni100, TC J-K-S-T-E)
Resistance measurements; selectable full scales
(20Ω to 20kΩ)
Up to 4 independent alarm set-points (optional)
20mA/10VDC analog output (optional)
Serial port RS485 or RS232 (optional)
MODBUS, JBUS communication protocol
Front protection degree: IP67, NEMA4x
LED display, selectable colour (red, amber, green)
• The alarm status can be coupled to the different
colour of the display
• Linearization of V and A inputs up to 16 points
Product Description
digital
panel
µp-based
meter, 4-dgt LED indicator,
for current, voltage, temper-
ature and resistance mea-
surements.
Measuring
ranges and functions easily
programmable from the key-
pad or from the PC by
means of optional UdmSoft
software. UDM
40
includes
storage min-max functions
and double level protection
password. Housing for panel
mounting with front protec-
tion degree: IP67, NEMA4x.
How to order
Model
Slot A
Slot B
Slot C
Slot D
Options
UDM40 XXX XX XX X XX
How to order
UdmSoft-kit
Type Selection
Slot A (measuring inputs)
LSX:
signal inputs:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
LSE/
LSF:
signal inputs: + AUX:
0.2-2-20mA DC/AC;
0.2-2-20V DC/AC
HSX:
signal inputs:
0.2-2-5A DC/AC;
20-200-500V DC/AC
TRX:
signal inputs: TC tem-
perature probes (J-K-
S-T-E, Pt100-250-500-
1000) and resistance
(0.02-0.2-2-20kΩ)
Slot B (communication)
XX:
SX:
SY:
AV(*):
None
Serial port RS485
Serial port RS232
Single analogue output,
0 to 20mA DC and
0 to 10V DC
The two analogue
outputs cannot be
used at the same
time. It is possible to
plug in only one
module by instru-
ment.
UdmSoft-kit: software plus “UCOM1” communication cable for
programming UDM40 by means of PC .
Slot C (communication and alarm)
XX:
R1:
None
Single relay output,
(AC1-8AAC, 250VAC)
R2:
Dual relay output,
(AC1-8AAC, 250VAC)
R4:
Dual relay output, (AC1-
8AAC, 250VAC) + dual
open collector output
(NPN, 100mA)
R5:
4 relay outputs
(AC1-5AAC, 250VAC)
AV(*):
Single analogue output,
0 to 20mA DC and
0 to 10V DC
Slot D (power supply)
H:
L:
90 to 260V AC/DC
18 to 60V AC/DC
Options
XX:
TX:
None
Tropicalization
(*):
Input Specifications
Analogue inputs
BQ LSX module
BQ LSE/LSF module
BQ HSX module
BQ TRX module
BQ TRX module
Digital inputs
Number of inputs
Use
Channels and variable
1, mA and V DC/AC
1, mA and V DC/AC + AUX
1, A and V DC/AC
1, temperature
1, resistance
Incl. in the measuring module
1 (voltage-free)
key-pad lock
Display hold
Reset of latch alarms
Contact reading signal
Close contact resistance
Open contact resistance
Insulation
Accuracy
(display, RS485)
BQ xxx: <0.1mA, <3,5V DC
BQ LSE/BQ LSF: <2.5mA,
<14V DC
Max 1kΩ
Min 500kΩ
Non-insulated
See table “Measuring
accuracy”, temperature drifts
and minimum-maximum
indications”
Specifications are subject to change without notice
UDM40DS 040706
1
Common problems and solutions in CCS compilation
1. warning: creating .stack section with default size of 400 (hex) words.This is because there is no set value for -stack in Project---Build Option---Linker. 2. warning: creating .sysmem section with ...
fish001 Microcontroller MCU
#SpaceX sends 4 civilians into space#When can I travel in space too???
I just saw a news video saying that at 8 a.m. on September 16, the U.S. space exploration technology company SpaceX used the manned Dragon spacecraft and the Falcon 9 rocket to launch the first purely...
okhxyyo Talking
Please tell me the circuit composed of TL431 directly and optocoupler inside the power supply
In this circuit, the secondary circuit voltage regulator TL431 is used as the reference and feedback error amplifier, sampling the output, generating an error voltage, which is converted into an error...
灞波儿奔 Power technology
The problem of via aperture and line width
Now I use AD software to draw pictures The problems encountered are: The trace width is 0.4mm and 0.8mm, and the maximum current will not exceed 500mA. I thought that when the hole was punched The via...
shaorc PCB Design
Use one data line to control full-color LED lights! Single bus LED usage guide
I believe that the first lesson for everyone to learn about single-chip microcomputers is to light up the first LED lamp. The first time you light up an LED, you must be very excited. You can control ...
灞波儿奔 Microcontroller MCU
【Portable Programmable Meter】Sliding Rheostat Arrived
In order to facilitate testing the power supply, I spent ten yuan to buy a sliding rheostat, which makes testing easier....
dcexpert DigiKey Technology Zone

Technical ResourceMore

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

Datasheet   0 1 2 3 4 5 6 7 8 9 A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
Room 1530, 15th Floor, Building B, No. 18 Zhongguancun Street, Haidian District, Beijing Telephone: (010) 82350740 Postal Code: 100190
Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号