Programmable Temperature Controller (Digital Controller)
E5AN-HT/E5EN-HT
(96 x 96 mm and 48 x 96 mm)
• Set up to 8 programmed patterns with up to 32 segments (steps) each.
• High-resolution display with 5 digits/0.01°C display.
• High-speed sampling cycle of 60 ms.
• High Accuracy
Thermocouple/Pt input: ±0.1% of PV
Analog input: ±0.1% FS
• Universal inputs on all models (thermocouple, PT, or analog
input) to handle various sensors with one Controller. Models
also available with Remote SP.
• A PV/SV-status display function can be set to automatically alternate
between displaying the status of the Temperature Controller (auto/
manual, RUN/RESET, and alarms) and the PV or SV.
• Flexible contact outputs with logic operations (AND, OR, and
delays) set from the Support Software (CX-Thermo version
4.3). Program settings can be managed.
• An infrared ports enables communications from the front panel.
• Preventive maintenance for relays in the Temperature
Controller using a Control Output ON/OFF Counter.
• Model available with position-proportional control.
*
Refer to
Safety Precautions for E5
@
N/E5
@
N-H/
E5
@
N-HT.
Refer to
Operation for E5
@
N/E5
@
N-H/E5
@
N-HT
for
operating procedures.
CSM_E5AN-HT_E5EN-HT_DS_E_1_10
Programmable Controllers Join the Series!
Program up to 256 segments and take advantage of the high cost performance
of the new LCD that improves both the field of view and contrast.
96
×
96 mm
E5AN-HT
48
×
96 mm
E5EN-HT
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
E5AN-HTPRR2B@-500, E5EN-HTPRR2B@-500 in this
catalog have been discontinued at the end of March 2018.
*
Orders will not be accepted after March 31, 2018.
Main I/O Functions
Remote SP Input
•
One
Event Inputs
• None
• Two
• Four
Universal Sensor Inputs
• Universal thermocouple/
Pt/analog
(current/voltage) inputs.
Indication Accuracy
•
Thermocouple/Pt input:
±0.1%
of PV
•
Analog input:
±0.1%
FS
Sampling Period
•
60 ms
PF Key
(Programmable
key function)
E5AN-HT
E5EN-HT
Three displays
for simultaneous display
of the PV, SV, program, and segment.
5-digit Display with high resolution of 0.01°C
•
Programmable function
8 programs × 32
segments
• Auto/manual switching
• Temperature Controller
status display
• Simple program
function
• Logic operations
• Control output ON/OFF
count alarm
• PV change rate alarm
•
Models available with
RS-485, RS-422, or
RS-232C
communications
Infrared port
Auxiliary Outputs
• Two
• Three
Computer Support Software
CX-Thermo
USB
Control Output 2
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
Control Output 1
Output Unit
• Relay output
• Voltage output (for driving SSR)
• Current output
• Linear voltage output
1
E5AN-HT/E5EN-HT
Lineup
1 control output
E5AN-HT/E5EN-HT
Programmable Type
2 auxiliary outputs
Terminal block
Fully universal input
2 control outputs
2 auxiliary outputs
Note:
The Controller can be used for heating/cooling control even if only 1 control output is used.
Model Number Structure
Model Number Legend
Controllers
Option Units
E5AN/E5EN-@@@@@@@M@-@-500
1 2 3 4 5 6 7 8 9 10
1. Type
HT: Programmable
2. Control Mode
Blank: Standard or heating/cooling control
P: Position-proportional control
*
3. Control Output 1
A: Control Output Unit
R: Relay output
*
4. Control Output 2
A: Control Output Unit
R: Relay output
*
5. Auxiliary Outputs
2: Two outputs
3: Three outputs
6. Option 1
Blank: None
H: Heater burnout/SSR failure/Heater overcurrent detection (CT1)
HH: Heater burnout/SSR failure/Heater overcurrent detection
(CT2)
7. Option 2
B: Two event inputs
BF: Event input + Transfer output
8. Option 3
M: Option Unit can be mounted.
9. Power Supply Voltage
Blank: 100 to 240 VAC
D: 24 VAC/VDC
10.Case Color
Blank: Black
11.Terminal Cover
-500: With Terminal Cover
*
Orders will not be accepted after March 31, 2018.
E53-@
1
1. Function
EN01: RS-232C communications
EN02: RS-422 communications
EN03: RS-485 communications
AKB: Event input
11
Output Units
E53-@@
1 2
1. Control Output
R: Relay output
Q: Voltage output (for driving SSR)
Q3: Voltage output (for driving SSR) + 24 VDC (NPN)
Q4: Voltage output (for driving SSR) + 24 VDC (PNP)
C3: Current output + 4 to 20 mA DC
C3D: Current output + 0 to 20 mA DC
V34: Linear voltage output + 0 to 10 VDC
V35: Linear voltage output + 0 to 5 VDC
2. Version
Blank: Available for E5AN-H/E5EN-H/E5AN-HT/E5EN-HT.
N: Available only for E5AN-H/E5EN-H and E5AN-HT/E5EN-HT.
Note:
Estimates can be provided for coatings and other specifications that are not given in the datasheet. Ask your OMRON representative for details.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169)
E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers Communications Manual Programmable Type (Cat. No. H170)
2
E5AN-HT/E5EN-HT
Ordering Information
E5AN-HT
Size
Case
color
Power
supply
voltage
Control Auxiliary
method
output
Control output 1/2
Control Output Unit
×
2
2
Basic
100 to
240 VAC
Valve
1/4 DIN
96
×
96
×
78 Black
(W
×
H
×
D)
2
Basic
24 VAC/
VDC
Valve
3
Control Output Unit
×
2
Control Output Unit
×
2
Relay outputs
×
2
2
Relay outputs
×
2
2
2
2
2
2
3
Control Output Unit
×
2
Control Output Unit
×
2
Relay outputs
×
2
2
Relay outputs
×
2
Control Output Unit
×
2
1
2
2
2
2
2
2
Heater
burnout
1
Optional functions
Event
inputs
2
Transfer
output
RSP
Model
4 to 20-mA
E5AN-HTAA2HBM-500
input
4 to 20-mA 4 to 20-mA
E5AN-HTAA2HHBFM-500
output
input
4 to 20-mA 4 to 20-mA
E5AN-HTAA3BFM-500
output
input
4 to 20-mA
E5AN-HTPRR2BM-500
*
input
4 to 20-mA 4 to 20-mA
E5AN-HTPRR2BFM-500
*
output
input
4 to 20-mA
E5AN-HTAA2HBMD-500
input
4 to 20-mA 4 to 20-mA
E5AN-HTAA2HHBFMD-500
output
input
4 to 20-mA 4 to 20-mA
E5AN-HTAA3BFMD-500
output
input
4 to 20-mA
E5AN-HTPRR2BMD-500
*
input
4 to 20-mA 4 to 20-mA
E5AN-HTPRR2BFMD-500
*
output
input
*
Orders will not be accepted after March 31, 2018.
E5EN-HT
Size
Case
color
Power supply
voltage
Control
method
Auxil-
iary
output
Control output 1/2
Control Output Unit
×
2
2
Basic
100 to 240 VAC
3
Control Output Unit
×
2
Control Output Unit
×
2
Relay outputs
×
2
Valve
1/8 DIN
48
×
96
×
78 Black
(W
×
H
×
D)
2
Basic
24 VAC/VDC
3
Control Output Unit
×
2
Control Output Unit
×
2
Relay outputs
×
2
Valve
2
Relay outputs
×
2
2
2
2
2
2
2
Relay outputs
×
2
Control Output Unit
×
2
1
2
2
2
2
2
2
Optional Functions
Heater
burn- Event
Transfer
RSP
out
inputs
output
1
2
Model
4 to 20-mA
E5EN-HTAA2HBM-500
input
4 to 20-mA 4 to 20-mA
E5EN-HTAA2HHBFM-500
output
input
4 to 20-mA 4 to 20-mA
E5EN-HTAA3BFM-500
output
input
4 to 20-mA
E5EN-HTPRR2BM-500
*
input
4 to 20-mA 4 to 20-mA
E5EN-HTPRR2BFM-500
*
output
input
4 to 20-mA
E5EN-HTAA2HBMD-500
input
4 to 20-mA 4 to 20-mA
E5EN-HTAA2HHBFMD-
output
input
500
4 to 20-mA 4 to 20-mA
E5EN-HTAA3BFMD-500
output
input
4 to 20-mA
E5EN-HTPRR2BMD-500
*
input
4 to 20-mA 4 to 20-mA
E5EN-HTPRR2BFMD-500
*
output
input
*
Orders will not be accepted after March 31, 2018.
3
E5AN-HT/E5EN-HT
Accessories (Order Separately)
Output unit
Relay
output
Voltage
output
(for driving
SSR)
Model
E53-RN
E53-QN
E53-Q3
E53-Q4
E53-C3N
E53-C3DN
E53-V34N
E53-V35N
Specifications
SPST-NO, 250 VAC, 5 A (resistive load),
electrical life: 100,000 operations
12 VDC (PNP), max. load current:
40-mA, with short-circuit protection
24 VDC (NPN), max. load current:
20-mA, with short-circuit protection
24 VDC (PNP), max. load current:
20-mA, with short-circuit protection
4 to 20-mA DC, load: 600
Ω
max.,
resolution: approx. 10,000
0 to 20-mA DC, load: 600
Ω
max.,
resolution: approx. 10,000
0 to 10 VDC, load: 1 kΩ min., resolution:
approx. 10,000
0 to 5 VDC, load: 1 kΩ min., resolution:
approx. 10,000
Current
output
Linear
voltage
output
USB-infrared Conversion Cable
Model
E58-CIFIR
USB-Serial Conversion Cable
Model
E58-CIFQ1
Terminal Cover
Connectable models
E5AN-HT
Model
E53-COV16
E5EN-HT
Note:
The Terminal Cover comes with the E5AN/E5EN-@@@-500 models.
Mounting Adapters
Model
Y92H-9
Note:
These Mounting Adapters are provided with the Digital Controller.
Waterproof Packing
Connectable models
E5AN-HT
Model
Y92S-P4
E5EN-HT
Y92S-P5
Note:
The Waterproof Packing is included with the Controller.
Current Transformers (CTs)
Hole diameter
5.8 dia.
12.0 dia.
Model
E54-CT1
E54-CT3
CX-Thermo Support Software
Model
EST2-2C-MV4
4
E5AN-HT/E5EN-HT
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 12 VA
24 VAC/VDC: 8.5 VA (24 VAC)/5.5 W (24 VDC)
Any of the following can be selected.
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150
Ω
max., Voltage input: 1 MΩ min. (Use a 1:1 connection when connecting the ES2-HB-N.)
ON/OFF control or 2-PID control (with auto-tuning)
Sensor input
Input impedance
Control method
Relay output
Control
output
Voltage output
(for driving SSR)
Current output
Linear voltage output
Auxiliary
output
Number of outputs
Output specifications
Number of outputs
Event
input
External contact input
specifications
Number of operations
Output Unit (Install the Output Unit (sold separately).)
2 or 3 max.
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
2 or 4 (with an E53-AKB)
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
8 max.
•
Logic operation: Any of the following four patterns can be selected. The input status may be inverted.
(A and B) or (C and D), (A or C) and (B or D), A or B or C or D, A and B and C and D
(A, B, C, and D are four inputs.)
•
Delay:
ON delay or OFF delay for the results of the logic operation given above.
Setting time: 0 to 9999 s or 0 to 9999 min
•
Output inversion: Possible
One work bit per operation
Any of The following can be assigned to up to eight work bits (logic operation results): operation commands (assigned to event
inputs)
*,
auxiliary outputs, or control outputs.
*
Application is possible with models that do not have event inputs by using an internal assignment.
1 max. (Depends on model. Models with transfer output (F in model number)
Current output: 4 to 20 mA DC, Load: 600
Ω
max., Resolution at 4 to 20 mA: Approx. 10,000
1
Current input: 4 to 20 mA (input impedance: 150
Ω ±10%)
Scaling of signal to engineering units (EU)
−19,999
to 30,000 (display: 30,000 max.)
(±0.2% of FS)
±1
digit max.
60 ms
Set digitally using keys on the front panel or by using the RSP input.
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN-HT: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN-HT: PV: 11.8 mm, SV: 8.1 mm, MV: 5.8 mm
Three displays: PV/SV/Program number/Segment number, PV/SV/MV, or PV/SV/Remaining segment time.
Number of digits: 5 for PV and SV, 4 for MV
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout detection (including SSR
failure and heater overcurrent detection), 40% AT, 100% AT, MV limiter, input digital filter, temperature input shift, run/reset,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, PV/SV status display,
automatic cooling coefficient adjustment, program control functions, etc.
−10
to 55°C (with no condensation or icing), for 3-year warranty:
−10
to 50°C
25% to 85%
−25
to 65°C (with no condensation or icing)
Operations
Logic
operations
Output
Work bit
assignment
Transfer
outputs
Number of outputs
Output specifications
Number of inputs
Signal type
RSP
input
Analog input scaling
Accuracy
Input sampling period
Setting method
Indication method
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
5