Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
TM12-MSM
Circuit Breaker for Equipment thermal-magnetically with Metal Actuator
See below:
Approvals and Compliances
Description
-
-
-
-
Thermal-magnetic circuit breaker ,
Metal switch non-illuminated and illuminated
1-pole
Quick connect terminals 6.3 x 0.8 mm or screw terminals
Applications
-
-
-
-
Power supplies
Uninterruptible power supply
Power tools
Household appliances
References
Component 1: circuit breakers
Component 2: metal switch
Component 3: Coupler
Weblinks
pdf datasheet, html-datasheet, General Product Information, Distributor-
Stock-Check, Detailed request for product, Product News
Technical Data
Rated Voltage AC
Rated Voltage DC
Rated current range AC
Conditional short circuit ca-
pacity
Dielectric Strength
Insulation Resistance
Endurance typical
␣
240 V; 50/60
28 V
0.05 - 15 A
IEC: Inc, PC1, AC 240 V: 1 kA
50 Hz: > 1.5 kV
Impulse 1.2/50
μs:
> 2.5 kV
500 VDC > 100 MΩ
2 x Ir: 5000 switching cycles
Reset type
AC : 2 x Ir , cos
φ
0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
50 switching cycles
Manual ON/OFF type
AC : 2 x Ir , cos
φ
0.6 :
DC : 2 x Ir , L/R = 2 - 3 ms :
5000 switching cycles
Overload
␣
Ambient temperature
Vibration Resistance
IEC: min. 40 trips
@ 6 x Ir, cos
φ
0.6
UL / CSA: min. 50 trips
@ 1.5 x Ir, cos
φ
0.75
-5 °C to 60 °C
± 0.75 mm @ 5 - 60 Hz
acc. to IEC 60068-2-6, test Fc
7 G @ 60 - 500 Hz
acc. to IEC 60068-2-6, test Fc
60 G / 18 ms
acc. to IEC 60068-2-27, test Ea
Thermal-Magnetic
Manual ON/OFF
IK 07
12 Nm for thread M19, 16 Nm for M22
24 h / 48 h / 96 h Residence Time
24 VDC Ring Illumination without series
resistor Point Illumination
ca. 55 g
Shock Resistance
Tripping Type
Actuation Type
Shock Protection
Tightening Torque Stainless
Steel Nut
Salt Spray Test (acc. to DIN
50021-SS)
Supply Voltage
Weight
␣
Approvals and Compliances
Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in
Details about
Approvals
Product standards
Product standards that are referenced
Organization
Design
Designed according to
Designed according to
Designed according to
Standard
IEC 60934
UL 1077
GB 17701
Description
Circuit-breakers for equipment (CBE)
Standard for Supplementary Protectors for Use in Electrical Equipment
Circuit-breaker for equipment
Circuit Breakers
1
TM12-MSM
Application standards
Application standards where the product can be used
Organization
Design
Designed for applications acc.
Standard
IEC/UL 60950
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
Description
IEC 60950-1 includes the basic requirements for the safety of information
technologyequipment.
Compliances
The product complies with following Guide Lines
Identification
Details
CE declaration of conformity
Initiator
SCHURTER AG
Description
The CE marking declares that the product complies with the applicable
requirements laid down in the harmonisation of Community legislation on
its affixing in accordance with EU Regulation 765/2008.
EU Directive RoHS 2011/65/EU
The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March
2007. It is similar to the EU directive RoHS.
On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration,
Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as
"REACH") entered into force.
RoHS
China RoHS
REACH
SCHURTER AG
SCHURTER AG
SCHURTER AG
Dimension [mm]
TM12 MSM 19
ø 22
ø 15.5
max. 10
1.8
M19 x 0.75
1.7
1)
78.85
15.5
1
3 7 8 2
6.3
42
11.5
0.8
1) only among MSM PI / RI quick connect terminal 2.8x0.5 mm
2
Circuit Breakers
ø 24
17.8
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
TM12-MSM
TM12 MSM 22
ø 25
ø 17.7
1.8
M22 x 1
max. 9
1.7
1)
78.85
15.5
1
3 7 8 2
6.3
42
11.5
0.8
1) only among MSM PI / RI quick connect terminal 2.8x0.5 mm
TM12 MSM 22 screw version
ø 25
ø 17.7
1.8
M22 x 1
max. 9
1.7
1)
15.5
1
3 7 8 2
84.75
42
11.5
1) only among MSM PI / RI quick connect terminal 2.8x0.5 mm
Circuit Breakers
17.8
17.8
3
TM12-MSM
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
MSM 19 LA ST / MSM 19 LA RI
MSM 19 LA LE / MSM 19 LA PI /
MSM 19 LA RI optional
MSM 22 LA ST / MSM 22 LA RI
MSM 22 LA LE / MSM 22 LA PI /
MSM 22 LA RI optional
Drilling diagram
Drilling diagram
Drilling diagram
Drilling diagram
Point Illumination
Operating Data
LED red
LED green
LED blue
Forward Current max.
30 mA
30 mA
20 mA
Forward Voltage at 10 mA
1,9 VDC
2,1 VDC
3,7 VDC
Forward Voltage at 8 mA
Forward Voltage max.
3,0 VDC
3,0 VDC
4,5 VDC
Attention: Switches are delivered without series resistor.
Recommendation of series resistors for point illumination
4
Circuit Breakers
Thermal-magnetic (TM and AS-line)
https://www.schurter.com /PG20
TM12-MSM
Typical internal resistance TMF12
Rated Current [A]
0.05
0.50
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
11.00
12.00
13.00
14.00
15.00
16.00
Internal Resistance [Ω]
335.00
4.37
1.23
0.369
0.181
0.097
0.055
0.044
0.0231
0.0227
0.0142
0.0123
0.012
0.012
0.0108
0.0091
0.0089
0.0071
Effect of ambient temperature
The units are calibrated for an ambient temperature of +23°C. To determine the rated cur-
rent for a lower or higher ambient temperature, use a correction factor (typical value) from
the table below:
Ambient temperature [°C]
-5
0
10
23
30
40
50
60
Correction factor
0.87
0.90
0.95
1.00
1.05
1.12
1.20
1.30
Example: Rated current = 5 A; Environmental temperature = 50 °C; --> Correction factor =
1.2; Resulting current = 6.0 A
Lettering
The last three digits in the order number define the lettering:
000
001-074
101-
No Lettering
Standard Lettering
Customized Lettering
Lettering options see on Datasheet MSM LA 22
Circuit Breakers
5