NH Low Voltage Industrial Fuse Links
SIZE:
C00 (000)
CLASS:
aM
500Vac
DIMENSIONAL DATA ON PAGE 33
•
For the protection of motor circuits
•
Partial range breaking capacity
•
Rated at 500Vac to IEC 60269-2-1 (VDE 0636)
•
VDE Licence Mark
•
Other voltage ratings available,
contact Bussmann for further information
1
FUSE LINK SELECTION TABLE
Rated Cur-
rent
Part Number
Watts loss (W)
Breaking Capacity
Weight
Packaging
4
6
8
10
12
16
20
25
32
40
50
4NHC00M
6NHC00M
8NHC00M
10NHC00M
12NHC00M
16NHC00M
20NHC00M
25NHC00M
32NHC00M
40NHC00M
50NHC00M
0.4
0.5
0.6
0.6
0.7
0.9
1.1
1.4
1.8
2.4
3.1
120kA @ 500V ac
0.130 kg
3 pcs per
Carton
2
FUSEHOLDER SELECTION TABLE FOR SIZE C00 (000) FUSE LINKS
No.Poles
Part Number
Material
Max Rated
Current
Max Watts
Loss of Fuse Link
Weight
Packaging
1
1
3
SB00
SBS00
TB00
Fibreglass
Steatite
Fibreglass
160A
160A
160A
12W
12W
12W
0.130 kg
0.280 kg
0.500 kg
3 per box
1 per box
1 per box
3
FUSE SWITCH-DISCONNECTOR SELECTION TABLE FOR SIZE C00 (000) FUSE LINKS
No.Poles
Part Number
Max Rated Current
of Fuse Links
Rated
Voltage
Max Watts
Loss of Fuse Link
Weight
Packaging
1
3
LBS00/1
LBS00/3
160A
690A ac
12W
0.720 kg
1 per Box
21
For more information visit our website at www.bussmann.com
NH Low Voltage Industrial FuseLinks:
Performance Data
Electrical Characteristics
SIZE:
C00 (000)
CLASS:
aM 500Vac
Time Current Characteristics
10
4
10
3
10
2
PRE-ARCING TIME IN SECONDS
10
1
10
-1
10
-2
10
-3
10
-4
10
100
1000
10000
RMS SYMMETRICAL PROSPECTIVE CURRENT IN AMPERES
I
2
t
CHARACTERISTICS
Bussmann
Part Number
Rated Current
RMS-Amps
I
2
t (A
2
S)
Pre Arcing at 500Vac
20 x I
n
at 500Vac
I
1
120kA at 500Vac
4NHC00M
6NHC00M
8NHC00M
10NHC00M
12NHC00M
16NHC00M
20NHC00M
25NHC00M
32NHC00M
40NHC00M
50NHC00M
4
6
8
10
12
16
20
25
32
40
50
31
64
93
290
290
700
860
1300
3000
6000
10000
80
210
390
1100
1600
2100
2700
3700
8000
12000
20000
330
820
1500
3700
4900
6900
8300
11000
21000
32000
47000
For more information visit our website at www.bussmann.com