NEW Series DRL
Single Output to 35A 510 Vac
DIN-Rail Solid-State Relay
Part Number
DRL48R35
DRL48D35-21
DRL48D35
DRL48A35-22
DRL48A35
Description
35A 510 Vac Output
35A 480 Vac Output
35A 510 Vac Output
35A 510 Vac Output
35A 510 Vac Output
Part Number Explanation
DRL
48
D
35
-21
NOTES
1) Line Voltage (nominal): 48 = 480 Vac
2) Switch Type: D = Zero-cross turn-on; A = Zero-cross, AC control;
R = Random turn-on
3) Features: -21 = Self turn-on suppression; -22 = 24 Vac control
FEATURES/BENEFITS
• Mounting and dismounting on DIN rail without
any tool or directly mountable on panel
• Zero-cross and random models; thyristors output
• Large control range
• Green control LED
• Very high immunity
• Low leakage current
• Internal transient suppression
DESCRIPTION
The Series DRL single-phase DIN-rail relays are
designed for all types of loads. The relays utilize
optical isolation to protect the control from load
transients. DRL relays have an integral heat sink, and
can be mounted and dismounted onto a DIN rail
without any tools. The relays may also be panel
mounted. All relays offer a green control LED and
transient suppression.
APPLICATIONS
• Heating control
• Motor control
• Industrial and process control
APPROVALS
Series DRL relays are pending UL recognition.
MECHANICAL SPECIFICATION
Figure 1 — DRL relay; dimensions in inches (mm)
© 2003 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
DRL 1
DRL\032003\Q1
Series DRL
CONTROL CHARACTERISTIC
12
INPUT (CONTROL) SPECIFICATION
Min
Control Range
DRL48R35
DRL48D35-21
DRL48D35
DRL48A35-22
DRL48A35
Control Current Range
3.5
3
3.5
17
150
Max
32
32
32
60
240
Units
Vdc
Vdc
Vdc
Vac/Vdc
Vac/Vdc
Control Current (mA)
10
8
6
4
2
0
0
2
4
6
8 10 12 14 16 18 20 22 24 26 28 30 32
Control Voltage (V)
DRL48R35
DRL48D
DRL48A35-22
DRL48A35
3
3
10
10
20
7
mAdc
mAdc
mA
mA
Figure 2a — DR38R and DR48D relays
20
Control Current (mA)
Must Turn-off Voltage
15
10
DRL48R35
DRL48D35-21
DRL48D35
DRL48A35-22
DRL48A35
2
1
2
4
15
32
42
Green
V
V
V
V
V
V
V
5
0
0
10
20
30
40
50
60
Control Voltage (V)
Reverse Voltage (DC Control)
Clamping Voltage (DC Control)
Input LED
Figure 2b — DRL48A35-22 relay
8
Control Current (mA)
6
4
TYPICAL APPLICATION
400 Vac 60Hz
400 Vac 60Hz
Protection
Protection
2
0
0
50
100
150
200
250
L1
L1
SSR
SSR
Control Voltage (V)
T1
T1
A2 A1
Figure 2c — DRL48A35 relay
Load
A2 A1
–
+
Control
Control
Load
Figure 3 — DRL relay DC control (left) and DRL relay
AC control (right)
DRL 2
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2003 TELEDYNE RELAYS
DRL\032003\Q1
Series DRL
OUTPUT (LOAD) SPECIFICATION
Min
Operating Range
Peak Voltage
Clamping Voltage
-21 feature (On voltage, typical)
All others (@1mA)
Zero-Cross Window (Typical)
DRL48R35
DRL48D35-21
DRL48D35
DRL48A
Non-Repetitive Surge Current
(See Figure 5)
On-State Voltage Drop (Typical)
Output Power Dissipation
(Typical)
Thermal Resistance
(Junction to Air)
Off-State Leakage Current (60Hz)
Turn-On Time (60Hz)
DRL48R35
DRL48D
DRL48A
Turn-Off Time (60Hz)
DRL48R35
DRL48D
DRL48A
Operating Frequency Range 0.1
Off-State dv/dt
I t for match fusing (<8.3ms)
2
ENVIRONMENTAL SPECIFICATION
Unit
Vrms
Vpeak
Storage Temperature
Operating Temperature
Input-Output Isolation
Output-Case Isolation
Min
–30
–30
4000
4000
100
4000
Max
100
80
Unit
°C
°C
Vrms
Vrms
MΩ
V
Max
510
1200
24
950
820
V
V
Insulation Resistance
Rated Impulse Voltage
Random
±10
±20
±20
V
Load Current (Arms)
45
40
35
30
25
20
15
10
5
THERMAL CHARACTERISTICS
V
V
550
A
0.9 V
0.81xIe+0.08xIe
2.6
1
2
0
0
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85
°C/W
mA
Ambient Temperature (°C)
Figure 4 — DRL relays
0.1
8.3
24.9
ms
ms
ms
400
600
SURGE CURRENTS
Non-Repetitive
Apeak
200
Repetitive with initial Tj = 70˚C
0
0.01
0.1
1
10
8.3
8.3
24.9
440
500
1500
ms
ms
ms
Hz
V/µs
A
2
S
t (s)
Figure 5 — DRL relays
© 2003 TELEDYNE RELAYS
(800) 284-7007 • www.teledynerelays.com
DRL 3
DRL\032003\Q1
Series DRL
DIN-RAIL MOUNTING
NOTES:
1. Connections: For output terminals, the wire cross-sections must be
adapted to the load current and to the overcurrent protection device
characteristics. The relay rated voltage must be adapted to the mains
rated voltage. These relays use screw clamp connections.
2. Mounting: Only in vertical position.
Protect heat-sensitive materials as well
as people from contact with the heat
sink. For non-vertical mounting, the load
current must be derated by 50%. The
SSR requires air convection. Lack of air
convection produces an abnormal
heating. Keep a distance between the
upper SSR and the lower SSR (see
vertical
3.15 inches
position
(80mm)
figure on the right). In case of zero space
between two SSRs, reduce the load
current. It’s suggested to maintain the
heat sink temperature under 90°C.
Forced cooling significantly improves the
thermal performances.
3. Typical application loads: The DRL relay
may handle motor and resistive loads.
For different loads, check the inrush current at turn-ON and possible
overvoltages at turn-OFF or contact the factory.
• Incandescent lamps — Inrush current is generally 10 times the
nominal current for 10ms.
• Electric discharge lamp — These loads often have overcurrent at
turn-ON and overvoltage at turn-OFF. Use 480Vac SSR on 240Vac
mains.
• Transformer loads — Very high inrush current, up to 100 times the
nominal current.
• Capacitive loads — Very high current at turn-ON and overvoltage
at turn-OFF. Use only zero-cross models.
4. Protection: To protect the SSR against a
1~
short-circuit of the load, use a fuse with a I
2
t
Fuse
value = 1/2 I
2
t value.
5. EMC:
Immunity: lmmunity levels of the DRL comply
L1
with EN61000-4-4 &5.
Emission: The system integrator must ensure
that systems containing SSRs comply with the
requirements of any rules and regulations
applicable at the system level. The very low
T1
zero-cross voltage (<20V) improves the
conducted emission level in comparison with
A1
+
control
most SSRs with zero-cross voltage higher
A2
Load
–
than 50V.
6. All electrical parameters specified at 25°C
unless otherwise noted.
N
Mounting
Recommended to connect
DIN rail to ground.
Dismounting
Figure 6 — DRL relays
PANEL MOUNTING
M5
M4
Drill for vertical can be adjusted
3.47
±
.08
(88
±
2)
.5 (12.7)
Figure 7 — DRL relays
CONNECTIONS
L
wires
(mm
2
)
L
torques
screwdriver
control
1 x (0.75-->2.5)
L = 6mm
0.4N.m
(0.6N.m max)
3.5 x 0.5mm
Power
1 x (1.5-->16) 1 x (1.5-->10)
L = 10mm
1.2N.m
(1.8N.m max)
Pozidriv2/
0.8 x 5.5 (1 x 6)
Figure 8 — DRL relays
DRL 4
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2003 TELEDYNE RELAYS
DRL\032003\Q1