economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
virtually any kind of power electronics with front-end
six-pulse rectifiers, 3-phase diode or thyristor bridges,
where harmonic current distortion needs to be
reduced to defined limits.
Technical specifications
Nominal operating voltage
Operating frequency
Nominal motor drive input power rating
Total harmonic current distortion THID*
Efficiency
High potential test voltage
Protection category
Cooling
Overload capability
Ambient temperature range
3 x 440 VAC to 500 VAC ±10%
50 Hz ±1 Hz
1.1 to 315 kW
≤5% at rated power
>98% for rated voltage and power
P –> E 2160 VAC (1 s)
IP 00, IP 20
Internal fan cooling or external cooling**
1.6x rated current for 1 minute, once per hour
–25°C to +45°C fully operational
–25°C to +85°C transport and storage
+45°C to +70°C derated operation***
UL 94 V-2
Filter: UL 61800-5-1, EN 61800-5-1
Chokes: EN 61558-2-20 or EN 60076-6
>200,000 hours
100 kA
TN, TT, IT
OV III (IEC 60664-1 / UL 61800-5-1)
Typical applications
Equipment with front-end six-pulse rectifier
Motor drives
Factory automation equipment
Water/wastewater treatment facilities
Fan and pump applications
HVAC installations
Mission-critical processes
DC fast chargers
Flammability corresponding to
Design corresponding to
MTBF @ 45°C/415 V (Mil-HB-217F)
SCCR****
Earthing System
Overvoltage category
Typical electrical schematic
****System requirements: THVD <2%, line voltage unbalance <1%
** *
Note: performance specifications in this brochure refer to six-pulse diode rectifiers with 8% DC-link choke.
THID ~5% at rated power for filter <6 kW
** Please check the inlet air flow required for cooling table on page 6 of this document.
*** I
derated
= I
nominal
*√((T
max-
T
amb
)/(T
max-
T
nominal
)) = I
nom
*√(70°C-T
amb
)/25°C
**** External UL-rated fuses required. Please consult the user manual.
(all configurable optional fuctionalities shown)
2
Ecosine passive
Schaffner Group
Datasheets
03 Sep 2019
Filter selection table – IP 00 enclosure
Filter
Rated load power
@ 480 VAC/50 Hz
[kW]
FN 3451-1-110-E0_ _ _ _ _*
FN 3451-2-110-E0_ _ _ _ _*
FN 3451-4-112-E0_ _ _ _ _*
FN 3451-6-112-E0_ _ _ _ _*
FN 3451-8-112-E0_ _ _ _ _*
FN 3451-11-112-E0_ _ _ _ _*
FN 3451-15-113-E0_ _ _ _ _
FN 3451-19-113-E0_ _ _ _ _
FN 3451-22-113-E0_ _ _ _ _
FN 3451-30-115-E0_ _ _ _ _
FN 3451-37-115-E0_ _ _ _ _
FN 3451-45-115-E0_ _ _ _ _
FN 3451-55-115-E0_ _ _ _ _
FN 3451-75-115-E0_ _ _ _ _
FN 3451-90-116-E0_ _ _ _ _
FN 3451-110-116-E0_ _ _ _ _
FN 3451-132-118-E0_ _ _ _ _
FN 3451-160-118-E0_ _ _ _ _**
FN 3451-200-118-E0_ _ _ _ _**
FN 3451-250-118-E0_ _ _ _ _**
New
FN 3451-315-119-E0XXSXX
315
410
392
0.188
0.059
252
1553
119
J
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
250
Motor drive
input current
[Arms]***
1.4
2.8
5.1
7.1
9.6
14.1
19.3
24.4
28
38.5
47.5
58
71
97
116
142
170
207
259
324
Rated filter
input current
[Arms]
1.3
2.7
4.9
6.7
9.2
13.4
18.3
23
27
36.6
45
55
67
92
110
135
162
197
246
308
Min. required
L
DC
[mH]*****
53.87
26.94
14.82
10.78
7.90
5.39
3.95
3.12
2.69
1.98
1.60
1.32
1.08
0.79
0.66
0.54
0.45
0.37
0.30
0.24
Min. required
L
AC
[mH]*****
16.70
7.85
4.47
3.48
2.55
1.82
1.26
1.02
0.88
0.64
0.527
0.451
0.357
0.265
0.218
0.176
0.149
0.118
0.094
0.073
[kg]
5
7
10
12
15
17
24
27
31
38
43
49
54
70
100
108
130
149
183
221
Weight
Typical
losses
[W]****
40
61
104
104
143
193
233
292
274
355
426
458
611
781
740
799
1063
1039
1232
1262
110
110
112
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
B
C
C
D
D
D
E
E
E
F
F
G
G
H
H
H
H
Terminal
Frame size
*
Filter rating which does not require forced cooling or fan module
** Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 480V, 50Hz and rated load power
***** In order to apply FN 3451 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3451 filter must not be used. In this case, FN 3450 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
119
M3
M4
M6
M8
M8
M10
M16
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
350-750 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
185-400
[Nm]
0.5
1.2
3
8
8
10
10
[mm]
7
10
15
15
17
35
48
A
B, C
D
E, F
G
H
J
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
M3*
M5
M6
M8
M10
M12
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
0.5
2.2
4
9
17
25
All
A
B, C
D, E
F, G, H
J
Frame size
* Max width cable lug = 7 mm
3
Ecosine passive
Schaffner Group
Datasheets
03 Sep 2019
Filter selection table – IP 20 enclosure
Filter
Rated load power
@ 400 V/50 Hz
[kW]
FN 3451-1-110-E2_ _ _ _ _*
FN 3451-2-110-E2_ _ _ _ _*
FN 3451-4-112-E2_ _ _ _ _*
FN 3451-6-112-E2_ _ _ _ _*
FN 3451-8-112-E2_ _ _ _ _*
FN 3451-11-113-E2_ _ _ _ _
FN 3451-15-113-E2_ _ _ _ _
FN 3451-19-113-E2_ _ _ _ _
FN 3451-22-115-E2_ _ _ _ _
FN 3451-30-115-E2_ _ _ _ _
FN 3451-37-115-E2_ _ _ _ _
FN 3451-45-115-E2_ _ _ _ _
FN 3451-55-115-E2_ _ _ _ _
FN 3451-75-116-E2_ _ _ _ _
FN 3451-90-116-E2_ _ _ _ _
FN 3451-110-118-E2_ _ _ _ _
FN 3451-132-118-E2_ _ _ _ _
FN 3451-160-118-E2_ _ _ _ _**
FN 3451-200-118-E2_ _ _ _ _**
FN 3451-200-118-E2E2_ _ _ _ _**
New
FN 3451-315-119-E2FASXX
315
410
392
0.188
0.059
278
1553
119
J
1.1
2.2
4
5.5
7.5
11
15
19
22
30
37
45
55
75
90
110
132
160
200
250
Motor drive
input current
[Arms]***
1.4
2.8
5.1
7.1
9.6
14.1
19.3
24.4
28
38.5
47.5
58
71
97
116
142
170
207
259
324
Rated filter
input current
[Arms]
1.3
2.7
4.9
6.7
9.2
13.4
18.3
23
27
36.6
45
55
67
92
110
135
162
197
246
308
Min. required
L
DC
[mH]*****
53.87
26.94
14.82
10.78
7.90
5.39
3.95
3.12
2.69
1.98
1.60
1.32
1.08
0.79
0.66
0.54
0.45
0.37
0.30
0.24
Min. required
L
AC
[mH]*****
16.70
7.85
4.47
3.48
2.55
1.82
1.26
1.02
0.88
0.64
0.527
0.451
0.357
0.265
0.218
0.176
0.149
0.118
0.094
0.073
[kg]
6
8
11
13
16
19
28
30
34
44
49
55
62
77
109
117
147
166
200
238
Weight
Typical
losses
[W]****
40
61
104
104
143
193
233
292
274
355
426
458
611
781
740
799
1063
1039
1232
1262
110
110
112
112
112
112
113
113
113
115
115
115
115
115
116
116
118
118
118
118
A
A
B
B
C
C
D
D
D
E
E
E
F
F
G
G
H
H
H
H
Terminal
Frame
size
*
Filter rating which does not require forced cooling or fan module
**
Filter rating which does not require RC damping module for rectifiers with EMI filter
*** Motor drive input current without harmonic filter
**** Typical losses @ 45°C, 400V, 50Hz and rated load power
***** In order to apply FN 3451 filters, motor drives have to be equipped with either DC-link choke or AC line choke. The minimum required inductance
values are given in mH in the filter selection table. If neither DC-link choke nor AC line choke is present, or if the minimum mH rating is not fulfilled,
FN 3451 filter must not be used. In this case, FN 3450 need to be chosen.
Filter power terminals
Terminal designation*
Screw thread
Flex wire AWG
Flex wire
Screw torque value
Max width**
cable lug
[mm
2
]
110
112
113
115
116
118
119
M3
M4
M6
M8
M8
M10
M16
14-22
10-22
6-18
1/0-8
3/0-8
3/0-500 kcmil
350-750 kcmil
0.4-2.5
0.4-6
0.75-16
10-50
10-95
95-240
185-400
[Nm]
0.5
1.2
3
8
8
10
10
[mm]
7
10
15
15
17
35
48
A
B, C
D
E, F
G
H
J
Frame size
* Recommended connector type: wire or cable lug for 110 to 113, only cable lug for 115 to 118
** To fulfill creepage/clearance acc. UL 61800-5-1 without additional protection (insulation). Creepage/clearance can vary depending on applicable standard and must
be reviewed by customer. Creepage/clearance may be reduced when additional protection (insulation) is provided.
Filter signal and earth terminals
Terminal type
Screw thread
M3*
M5
M6
M8
M10
M12
Screw torque value
[Nm]
Signal
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
Earth (PE)
0.5
2.2
4
9
17
25
All
A
B, C
D, E
F, G, H
J
Frame size
* Max width cable lug = 7 mm
4
Ecosine passive
Schaffner Group
Datasheets
03 Sep 2019
Product selector
Table 1: Filter configurations if external air flow is available for cooling
(Filters do
not contain fan
and do
not contain aux. power supply)
E0XXXXX
- For rectifiers with DC-link choke
E0XXJXX
- For rectifiers with DC-link choke
- Filters contain trap disconnect
jumper
E0XXXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module
E0XXJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain RC damper
module and trap disconnect
jumper
5
Ecosine passive
Schaffner Group
Datasheets
03 Sep 2019
Table 2: Filter configurations with embedded ventilation
(Filters
contain fan
and
aux. power supply)
E0FAXXX and E2FAXXX
- For rectifiers with DC-link choke
- Filters contain fan and aux. power
supply
E0FAJXX and E2FAJXX
- For rectifiers with DC-link choke
- Filters contain fan, aux. power
supply and trap disconnect
jumper
E0FAXRX and E2FAXRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply and RC damper module
E0FAJRX and E2FAJRX
- For rectifiers with DC-link choke
and with EMI filter
- Filters contain fan, aux. power
supply, RC damper module and
trap disconnect jumper
Table 3: Filter configurations if external aux. power supply for the fan is available